Output- Presence (n.31)
This object is used to report the presence on HVAC 2 channel.
The enabled flags are C (communication), R (read by bus) and T (Trasmission).
The standard format of the object is 1.001 DPT_Switch.
The standard format of the object is
1 bit and the information it contains is
“On/Off”.
Input- Locking object (n.32)
This object is used to block the HVAC 3 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.010 DPT_Switch.
The standard format of the object is
1 bit and the information it contains is
“Start/Stop”.
Input- External influence (n.33)
This object is used to receive external control of the HVAC 3 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.001 DPT_Switch.
The standard format of the object is
1 bit and the information it contains is
“On/Off”.
Input- Follow time in minutes (n.34)
This object is used to set follow time on HVAC 3 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 7.006 DPT_TimePeriodMin.
The standard format of the object is
2 byte and the information it contains is
”VALUE
(min)”
Input- Overwrite threshold (n.35)
This object is used to overwrite threshold on HVAC 3 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 9.004 DPT_Value_Lux.
The standard format of the object is
a 2 byte and the information it contains is
“Value_lux”.
Input-Switch on upon movement (n.36)
This object is used to set automatic mode or semy-automatic on HVAC 3 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.003 DPT_Enable.
The standard format of the object is
1 bit and the information it contains is
“enable/disable”.
Output- Presence (n.37)
This object is used to report the presence on HVAC 3 channel.
I flag abilitati sono C (communication), W (written by bus) and T (trasmission).
The standard format of the object is 1.001 DPT_Switch.
The standard format of the object is 1 bit and the information it contains is
“On/Off”.