50
The standard format of the object is
1 byte
and the information it contains is “VALUE
%”
Output- Value 2 (n.17)
This object is used to send value 2 %
The enabled flags are C (communication), R (read by bus) and T (Trasmission).
The standard format of the object is 5.001 DPT_Scaling.
The standard format of the object is
1 byte and the information it contains is
“VALUE
%”
Output- Current threshold (n.18)
This object is used to send the current threshold.
The enabled flags are C (communication), R (read by bus) and T (Trasmission).
The standard format of the object is
1 bit
Output- Burn-in time status (n.19)
This object is used to receive from the bus the Burn-in time missing.
The enabled flags are C (communication), R (read by bus) and T (Trasmission).
The standard format of the object is 7.006 DPT_TimePeriodMin.
The standard format of the object is
2 byte and the information it contains is
”VALUE
(min)”
Input- Locking object (n.20)
This object is used to block the HVAC 1 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.010 DPT_Switch.
The standard format of the object is
1 bit and the information it contains is
“Start/Stop”.
Input- External influence (n.21)
This object is used to receive external control of the HVAC 1 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 1.001 DPT_Switch.
The standard format of the object is
1 bit and the information it contains is
“On/Off”.
Input- Follow-up time in minutes (n.22)
This object is used to set follow time on HVAC 1 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 7.006 DPT_TimePeriodMin.
The standard format of the object is
2 byte and the information it contains is
”VALUE
(min)”
Input- Overwrite threshold (n.23)
This object is used to overwrite threshold on HVAC 1 channel.
The enabled flags are C (communication) and W (written by bus).
The standard format of the object is 9.004 DPT_Value_Lux.
The standard format of the object is
2 byte and the information it contains is
“Value_Lux”.