TWO POINTS 0%-100%
The operating principle is similar to that of the two points ON-OFF, but with the difference that the
communication objects for temperature adjustment management are of 1 byte.
In heating mode, when the detected temperature is lower than the “setpoint -
heat
” value, the
device activates the heating system by sending the relative percentage command to the actuator
that manages it; when the detected temperature reaches the fixed setpoint value, the device
deactivates the heating system.
H
EATING
In cooling mode, when the detected temperature is higher than the “se
cond
” value,
the device activates the cooling system by sending the relative percentage command to the
actuator that manages it; when the measured temperature reaches the fixed setpoint value, the
device deactivates the cooling system.
C
OOLING
To avoid the continuous switching of the solenoid valve, after a 0%-100%-0% sequence, the next
100% command can only be sent after at least 2 minutes have elapsed.
Setting the adjustment differential
Use the
button keys to set the value of the adjustment
differential of the two-point control algorithm (the gap can be set
from 0.1°C to 2.0°C).
To confirm your choice and move on to the next parameter, press
the
button key within 30 seconds.
T
setpoint
heat
T
setpoint
cond
USER INSTRUCTIONS