Mounting the coupling
Attention!
Malfunctions may occur if the coupling is
not properly aligned with the stem.
Make sure that the marking on the
stem and the scale are properly
aligned.
Make sure that there is adequate
spacing between the coupling and the
stem.
The spacing must not exceed 10 mm, but it should
be as large as possible.
Place the two halves of the coupling (11) around
the stem (12) and spindle (8) as shown.
The two outer edges of the coupling must be
situated next to the cap support as shown.
Rotate the coupling to align it.
The marking on the coupling must be situated
above the marking on the stem.
Make sure the largest possible gap, of 10 mm
maximum, is left between the coupling and the
stem.
If necessary, turn the cap round so that the
marking of the coupling is lined up with the
scale.
Align the coupling with the cap support as
shown.
The marking on the coupling must match that on
the scale as shown.
If necessary, screw the spindle (8) further in or
out.