6
ORGS 112
Technical data
Oil detector & alarm ORGS 112
(equipment unit)
Service pressure
6 bar
Service temperature
110 °C
Flow velocity
100 l/h to 300 l/h, recommended 200 l/h
Pressure drop
∆
p
v
0.06 bar (under test conditions)
Alarm
Raised when approx. 50 ml oil has accumulated
Water inlet, drain
Ball valve with EO-connection 15 L
Water outlet
Ball valve with EO-connection 12 L
Weight
approx. 7.4 kg
Measuring electrode ORGS 111
(component of ORGS 11-2)
Mechanical connection
Screwed G 1 A, ISO 228
Materials
Screw-in body: 1.4571, X6CrNiMoTi17-12-2
Electrode rods: 1.4571, X6CrNiMoTi17-12-2
Insulating sheath: PTFE
Terminal box: 3.2161 G AlSi8Cu3
Supply voltage
230 V +/- 10 %, 50/60 Hz
115 V +/- 10 %, 50/60 Hz
24 V +/- 10 %, 50/60 Hz (optional)
Power consumption
5 VA
Fuse
external slow-blow 0.5 A
internal
thermal fuse T
max
= 102 °C
Response sensitivity
Range 1: 10 µS/cm
Range 2: 0.5 μS/cm
Code-switch selectable
Electrode voltage
10 V
pp
Содержание ORGS 11-1
Страница 1: ...1 E N English Oil Detector Alarm ORGS 11 1 ORGS 11 2 Original Installation Instructions 810801 06 ...