Important notes
Usage for the intended purpose
The NRS 2-50, NRS 2-51 level switch is used in combination with NRG 2.-.. level electrodes and
NRGT 26-. level transmitters as a limit switch and water level controller, e.g. in steam boilers and hot
water installations or in condensate and feedwater tanks. The level switch indicates when a MIN and
MAX water level has been reached, and switches the feedwater pump on and off (NRS 2-51).
The NRS 2-50, NRS 2-51 level switch can be combined with the NRG 21-.. and NRG 26-21 level
electrodes and the NRGT 26-. level transmitter.
The
NRS 2-50, NRS 2-51 level switch
processes the voltage signals from the NRG 2..-.. level electrodes
or the current signal from the NRGT 26-. level transmitter. These voltage and current signals vary depend-
ing on the level.
In the
NRS 2-50, NRS 2-51 level switch
, the input signal is normalised to 0 and 100% of the boiler
measuring range, and the switchpoints for the MIN/MAX water level are adjusted as required within this
range. Then, during normal operation the actual value is shown on the 7-segment LED display.
If the MIN or MAX water level is reached, the MIN or MAX output contact switches over after the off delay
and the MIN or MAX LED lights up.
The
NRS 2-51 level switch
also functions as an interval level control system
(fill/discharge, switch-
selectable)
. With this equipment, if the lower or upper water level switchpoint is reached, the controller
output contact switches – depending on which function is set – which then turns the feedwater pump on
or off. The amber LED lights up when the level switch has switched the feedwater pump on, for example.
Faults or malfunctions in the level electrode or level transmitter, the electrical connection or the settings
are indicated on the 7-segment LED display. In the event of a malfunction, the MIN and MAX alarm is
triggered.
If faults occur only in the
NRS 2-50, NRS 2-51 level switch
, the MIN and MAX alarm is triggered and the
system is restarted.
Parameters can be changed or the MIN/MAX alarm simulated by operating the rotary knob.
The equipment has an actual value output 4 - 20 mA for external level indication.
Function
Safety note
The equipment may only be installed, wired and brought into service by qualified and competent staff.
Maintenance and setup work may only be performed by authorised staff who have undergone specific
training.
Danger
The terminal strips of the equipment are live during operation.
There is a risk of serious injury due to electric shock!
Always
cut off power
to the equipment before working on the terminal strips (installa-
tion, removal, connecting cables).
Attention
The name plate indicates the technical features of the equipment. Do not bring into
service or operate any equipment that does not bear its own specific name plate.