22
NRS 2-50, NRS 2-51 - Installation & Operating Manual -
819179-05
Operation, alarm and testing
Indications
continued
Level switch NRS 2-51 only: Fill control
Water level below pump ON
switchpoint.
Pump LED lights up amber.
Pump output contact 19/20 closed.
Water level above pump OFF
switchpoint.
Pump LED is not lit.
Pump output contact 19/20 open.
Level switch NRS 2-51 only: Discharge control
Water level above pump ON
switchpoint.
Pump LED lights up amber.
Pump output contact 19/20 closed.
Water level below pump OFF
switchpoint.
Pump LED is not lit.
Pump output contact 19/20 open.
Note
The actual value is shown on the 7-segment display.
Testing the MIN alarm and MAX alarm
Action
Indication
Function
In operating mode:
Water level between MIN
and MAX
Select Test parameter. Press
and hold the pushbutton.
MAX LED flashes red
Off delay in progress.
MAX LED lights up red for 3
seconds
MAX output contact 21/23 closed, 22/23 open.
The MIN and MAX LED are not
lit for 1 second
MIN output contact 16/18 open, 17/18 open.
MAX output contact 21/23 open, 22/23 closed.
MIN LED flashes red
Off delay in progress.
MIN LED lights up red for 3
seconds
MIN output contact 16/18 closed, 17/18 open.
Test complete, release
pushbutton. Equipment
switches to operating mode.
Note: If you continue holding the pushbutton, the test sequence will start again.
You can interrupt the test sequence at any time by releasing the pushbutton.
Turn the rotary knob until the actual value is displayed.
Or after 30s, the actual value is displayed automatically.
Checking the function of the MIN/MAX output contacts