21
NRS 2-50, NRS 2-51 - Installation & Operating Manual -
819179-05
Operation, alarm and testing
Setting switchpoints and indicators
Fig. 6
Pump LED
amber
MAX LED
red
MIN LED
red
OO75
7-segment
display
Rotary knob
with integrated
pushbutton
OO75
Operation
Action
Indication
Function
Water level between MIN and
MAX.
MIN and MAX LEDs are not lit
MIN output contacts 16/18 open,
17/18 closed.
MAX output contacts 21/23 open,
22/23 closed.
MIN alarm
Water level at or below MIN
level switchpoint.
MIN LED flashes red
Off delay in progress.
MIN LED lights up red
Delay time elapsed, MIN output contacts 16/18
closed, 17/18 open.
MAX alarm
Water level at or above MAX
level switchpoint.
MAX LED flashes red
Off delay in progress.
MAX LED lights up red
Delay time elapsed, MAX output contacts 21/23
closed, 22/23 open.
Setting the MIN/MAX switchpoints
Select parameter AL.Lo, enter and save the desired
percentage.
MIN switchpoint is set between 0-100%
Select parameter AL.Hi, enter and save the desired
percentage.
MAX switchpoint is set between 0-100%
Level switch NRS 2-51 only: Setting pump switchpoints (fill control)
Select parameter SP.Lo, enter and save the desired
percentage.
Pump ON switchpoint is set
between 0-100%
Select parameter SP.Hi, enter and save the desired
percentage.
Pump OFF switchpoint is set
between 0-100%
Level switch NRS 2-51 only: Setting pump switchpoints (discharge control)
Select parameter SP.Lo, enter and save the desired
percentage.
Pump OFF switchpoint is set
between 0-100%
Select parameter SP.Hi, enter and save the desired
percentage.
Pump ON switchpoint is set
between 0-100%