Operating the level switch
Meaning of codes on the 7-segment display
Code
Meaning
Appears when rotary knob is turned clockwise:
AL.Hi
Alarm High
MAX switchpoint
Adjustable between 0 and 100%
C
AL.Lo
Alarm Low
MIN switchpoint
SP.Hi
Set point High
NRS 2-51 only: Switchpoint for pump off (fill), pump on (discharge),
adjustable between 0 and 100%
C
SP.Lo
Set point Low
NRS 2-51 only: Switchpoint for pump on (fill), pump off (discharge),
adjustable between 0 and 100%
C
tESt
Test
Output relays are tested
PW
Password
on = password protection is enabled
oFF = password protection is disabled
Factory setting
1902 (cannot be changed)
CAL.L
Calibrate L
Only if level electrode
NRG 21-.. or NRG 26-
21 is connected
Set lower end of measuring range
CAL.P
Calibrate %
Adjustable between =/> 25 and =/< 100%
CAL.H
Calibrate H
Set upper end of measuring range
Appears in parameterization mode
quit
Quit
Input is not confirmed
done
Done
Input is confirmed.
Appears in the event of malfunctions
E.005
Error
Level electrode/transmitter defective, measuring voltage/current too low
E.006
Error
Level electrode/transmitter defective, measuring voltage/current too high
E.012
Error
Lower and upper ends of measuring range wrong way round
E.013
Error
MIN switchpoint higher than MAX switchpoint
Fig. 6
Pump LED
amber
MAX LED
red
MIN LED
red
OO75
7-segment
display
Rotary knob
with integrated
pushbutton