13
Establishing Functions
Establishing functions
1. Set the code switch
&
to the desired function. For this purpose you can use a screwdriver with a
thin blade.
2. Use a waterproof marker to enter the established function for each electrode tip in the labelling
boxes on the lid (see
Fig. 3
).
Key
1
LED 1 red
2
LED 2 red
3
LED 3 amber
4
LED 4 red
5
LED green for Power ON
6
Terminal strip for control lines
7
Cable gland 3 x M16 x 1,5
8
Terminal strip for supply voltage
9
Fixing screws for electronic module
0
PE connection
!
Fixing nut for terminal box
"
Terminal lugs for electrode wires, functional earth
§
RESET button
$
Terminal strip for pushbuttons
%
TEST button
&
Code switch
/
Potentiometer for time delay
(
Cover screws (cross recess head screws M4)
)
Housing cover
Note
To set the
functions
, the
time delay
and the
response sensitivity
open the terminal box.
To do so unscrew the cover screws
(
and remove the housing cover
)
.
After changing the settings replace the housing cover
)
and fasten the cover screws
(
.
Changing the time delay
The default time delay for the pump control is 5 seconds.
1. Turn the potentiometer knob
/
to the left or right to set a time delay between 0 and 30 seconds.
- continued -