11
Common Settings
Parameter
Description
Range
Step
Default
Buzzer
Status of alarm buzzer.
Active
– Passive
-
Active
Language
Control unit interface
language.
Türkçe - English
-
Türkçe
Deep
Discharge
Threshold
Threshold of battery group
disconnection from load.
18
– 27 V for 24V
82
– 123 V for 110V
1 V
20 V for 24V
90 V for 110V
Equalize Timer Mode
Parameter
Description
Range
Step
Default
Period
Period of periodic equalizing
charge. Refer to “Equalize
Charge” menu duration for
duration.
1
– 9 hrs
1 hr
1 hr
Status
Status of periodic equalizing
charge.
Active
– Passive
-
Active
Battery Maintenance (TEDAŞ Maintenance Method)
Parameter
Description
Range
Step
Default
Annual
Battery
Maintenance
Quantity
This parameter determines
how many times this
method will be applied.
1
– 6
1
4
Maintenance
Voltage
Minimum battery voltage to
stop discharge.
21
– 24 V for 24V
94
– 108 V for 110V
1 V
22 V for 24V
100 V for 110V
Maintenance
Duration
Duration of maintenance
method if battery voltage
doesn’t drops under prior
setting.
2
– 48 hrs
1 hr
48 hrs
Maintenance
Start Time
Time of day to start
maintenance.
HH:MM
-
00:30
Password Settings
Parameter
Description
Range
Step
Default
Password
4-digit password to prevent
unauthorized access to
control unit.
0
– 9999
1
0000
Status
Status of password
authentication.
Active
– Passive
-
Active
Date / Time Settings
Parameter
Description
Range
Step
Default
Date
In DD/MM/YY format.
Time
In HH:MM format.
DST Setting
Status of day light saving.
Active
– Passive
-
Passive