3.2. Monitoring and Settings
3.2.1. Default Screen
Default screen displays the following
parameters:
• In-cabinet temperature,
• Mute symbol if buzzer is disabled,
• Fan symbol if operating,
• Time of day,
• AC input voltage (V
g
), frequency (F
g
),
• DC output voltage (U),
• Total current output (I
S
),
• Battery charging current (I
a
),
• Sliding alarm notifications.
Following alarms and status information is shown with LEDs:
• Charging mode LED is on and steady if floating or flashing if equalizing charge mode is active.
• AC High/Low and DC High/Low LEDs are; on and steady if over or flashing if under preset value. If
both in preset limits LED is off.
• Bottom LED is on and steady if output current is limited and flashes if any of alarms is occurred.
Check default screen to see which alarms are occurred.
3.2.2. Muting Buzzer Temporarily
Press UP and DOWN buttons at the same time buttons to mute the buzzer for 30 min. Press again to
unmute or control unit unmute itself after 30 min.