Geokon 4855 Скачать руководство пользователя страница 9

 

2. INSTALLATION 

 

2.1 Preliminary Tests 

 

It is always wise, before installation commences, to check the cells for proper functioning. Each 

cell is supplied with a calibration sheet, which shows the relationship between readout digits and 

pressure and shows the initial no load zero reading. The transducer’s electrical leads (usually the 

red and black leads) are connected to a readout box and the zero readings given on the sheet is 

now compared to the current zero readings. (See Section 3 for readout instructions.) The reading 

should not differ by more than 

50 digits, after due regard to corrections made for different 

temperatures, barometric pressures and height above sea level and actual cell position (whether 

standing up or laying down).  

 

Take Initial No-Load Reading of pressure and temperature with the cell laying flat on the 

ground. These are important readings and will be used in future calculations of pile-tip load. 

 

By standing on the cell it should be possible to change the readout digits, causing them to fall as 

the pressure is increased. 

 

Checks of electrical continuity can also be made using an ohmmeter. Resistance between the 

gauge leads should be approximately 180 ohms, ±10 ohms. Remember to add cable resistance 

when checking (22 AWG stranded copper leads are approximately 14.7

/1000' or 48.5

/km, 

multiply by two for both directions). Between the green and white should be approximately 

3000Ω at 25 °C (see Table 4 in Appendix B), and between any conductor and the shield should 

exceed 20 megohm. 

 

2.2 Pressure Cell Installation 

 

The short pieces of threaded re-bar are screwed into the lugs welded to the bottom plate of the 

pressures cell. A depression is excavated in the ground and lined with sand. The shape of the 

depression should match the profile of the bottom of the pile shaft, whether conical or 

cylindrical. This depression is now filled with concrete of the same type as the rest of the pile 

and is heaped in the middle so that when the pile tip pressure cell is lowered into it the concrete 

extrudes out to the side carrying any voids with it. The concrete is left to harden. 

 

The lugs protruding from the upper plate of the pressure cell are welded to the rebar of the rebar 

cage as shown in Figure 1. (More details of this operation will be found in Appendix C) The 

cables from the sensors and the hydraulic pressure line to the check valve are fixed firmly to the 

rebar using nylon zip ties every meter or so. The cables and hydraulic line should be positioned 

so that they are protected from the concrete tremie pipe and from being scraped as the rebar cage 

is lowered into the hole.  

 

Preparation of the bottom of the hole should ensure that the surface below the pressure cell is 

clean of debris and is pre-filled with wet concrete to a depth of 30 cm. It is important that there 

be no voids below the cell. 

 

One technique to ensure that there are no voids below the pile tip load cell is shown in Figure 2. 

 

 

Содержание 4855

Страница 1: ... means without the written consent of Geokon The information contained herein is believed to be accurate and reliable However Geokon assumes no responsibility for errors omissions or misinterpretation The information herein is subject to change without notification Copyright 2003 2019 by Geokon Doc REV F 05 1 19 ...

Страница 2: ......

Страница 3: ...nnel There are no warranties except as stated herein There are no other warranties expressed or implied including but not limited to the implied warranties of merchantability and of fitness for a particular purpose Geokon is not responsible for any damages or losses caused to other equipment whether direct indirect incidental special or consequential which the purchaser may experience as a result ...

Страница 4: ......

Страница 5: ...EADOUT BOX 7 3 2 1 Connecting Sensors 7 3 2 2 Operating the GK 405 7 3 3 GK 403 READOUT BOX OBSOLETE MODEL 8 3 3 1 Connecting Sensors 8 3 3 2 Operating the GK 403 8 3 4 MEASURING TEMPERATURES 8 4 DATA REDUCTION 9 4 1 PRESSURE CALCULATION 9 4 2 TEMPERATURE CORRECTION 9 4 3 BAROMETRIC CORRECTION 9 5 TROUBLESHOOTING 10 APPENDIX A SPECIFICATIONS 12 A 1 PRESSURE CELLS 12 A 2 THERMISTOR SEE APPENDIX B A...

Страница 6: ...READINGS RAW READINGS 7 TABLES TABLE 1 SAMPLE RESISTANCE 11 TABLE 2 RESISTANCE WORK SHEET 11 TABLE 3 SPECIFICATIONS 12 TABLE 4 THERMISTOR RESISTANCE VERSUS TEMPERATURE 13 EQUATIONS EQUATION 1 DIGITS CALCULATION 9 EQUATION 2 CONVERT DIGITS TO PRESSURE 9 EQUATION 3 TEMPERATURE CORRECTION 9 EQUATION 4 RESISTANCE TO TEMPERATURE 13 ...

Страница 7: ...ressure cell is directly equivalent to the end bearing load 1 2 Pile Tip Pressure Cell Design and Construction The basic cell is manufactured to be close to the diameter of the pile It is comprised of two circular stainless steel plates welded together around their periphery leaving a thin space between the plates filled with de aired hydraulic oil This oil filled space is connected via a pressure...

Страница 8: ...a space between it and the surrounding concrete which if allowed to remain might prevent the transmission of pressures from the concrete to the cell To overcome this provision is made so that the cell can be inflated until it comes back into perfect contact with the concrete on both surfaces This re inflation is performed from the surface through a hydraulic line operating through a check valve An...

Страница 9: ...n and white should be approximately 3000Ω at 25 C see Table 4 in Appendix B and between any conductor and the shield should exceed 20 megohm 2 2 Pressure Cell Installation The short pieces of threaded re bar are screwed into the lugs welded to the bottom plate of the pressures cell A depression is excavated in the ground and lined with sand The shape of the depression should match the profile of t...

Страница 10: ...ake readings of pressure and temperature at regular intervals throughout the installation process It should be possible to monitor the pressure of the wet concrete as it is poured Allow the concrete set up and cool to a temperature close to ambient It may be observed that there is a drop in cell pressure from the value observed with the wet cement when the hole was filled Connect the cell re infla...

Страница 11: ...erefore splicing of cables has no ill effects and in some cases may in fact be beneficial The cable used for making splices should be a high quality twisted pair type with 100 shielding and an integral shield drain wire When splicing it is very important that the shield drain wires be spliced together Always maintain polarity by connecting color to color Splice kits recommended by Geokon incorpora...

Страница 12: ... sensor conductors with blue representing the shield bare To turn the GK 404 on press the ON OFF button on the front panel of the unit The initial startup screen will be displayed After approximately one second the GK 404 will start taking readings and display them based on the settings of the POS and MODE buttons The unit display from left to right is as follows The current Position Set by the PO...

Страница 13: ...ctor until it locks into place Connecting Sensors with Bare Leads Attach the GK 403 2 flying leads to the bare leads of a Geokon vibrating wire sensor by connecting each of the clips on the leads to the matching colors of the sensor conductors with blue representing the shield bare 3 2 2 Operating the GK 405 Press the button labeled POWER ON A blue light will begin blinking signifying that the Rem...

Страница 14: ...t may change one or two digits while reading The thermistor reading will be displayed above the gauge reading in degrees centigrade 4 Press the Store button to record the value displayed If the no reading displays or the reading is unstable see Section 5 for troubleshooting suggestions The unit will automatically turn itself off after approximately two minutes to conserve power 3 4 Measuring Tempe...

Страница 15: ...ration Sheet 4 2 Temperature Correction The vibrating wire sensor is relatively insensitive to temperature fluctuations and usually the effect of temperature is insignificant and can be ignored But if desired correction for temperature effects on the sensor can be made using the factors supplied on the calibration sheet and Equation 3 Also there are spurious temperature effects caused by the misma...

Страница 16: ...s the readout work with another pressure cell If not it may have a low battery or possibly be malfunctioning Symptom Pressure Cell Fails to Read Is the cable cut or crushed Check the resistance of the cable by connecting an ohmmeter to the gauge leads Table 1 shows the expected resistance for the various wire combinations Table 2 is provided for the user to enter the actual resistance found Cable ...

Страница 17: ... infinite infinite infinite White infinite infinite N A 3000Ω at 25 C infinite Green infinite infinite 3000Ω at 25 C N A infinite Shield infinite infinite infinite infinite N A Table 1 Sample Resistance Vibrating Wire Sensor Lead Grid SENSOR NAME Red Black White Green Shield Red Black White Green Shield Table 2 Resistance Work Sheet ...

Страница 18: ... 1 FSR optional Operating Temperature 30 to 70 C Frequency range 1400 3500 Hz Dimensions Diameter to suit the pile Thickness approximately 50 mm Material 303 304 Stainless Steel Electrical Cable Two twisted pair four conductor 22 AWG Foil shield PVC jacket nominal OD 6 3 mm 0 250 Table 3 Specifications Consult the factory for other sizes or options available A 2 Thermistor see Appendix B also Rang...

Страница 19: ... 2 83 107 9 123 77 66K 36 8006 4 1363 44 331 5 84 105 2 124 72 81K 35 7618 5 1310 45 321 2 85 102 5 125 68 30K 34 7252 6 1260 46 311 3 86 99 9 126 64 09K 33 6905 7 1212 47 301 7 87 97 3 127 60 17K 32 6576 8 1167 48 292 4 88 94 9 128 56 51K 31 6265 9 1123 49 283 5 89 92 5 129 53 10K 30 5971 10 1081 50 274 9 90 90 2 130 49 91K 29 5692 11 1040 51 266 6 91 87 9 131 46 94K 28 5427 12 1002 52 258 6 92 8...

Страница 20: ...the bottom and a steel belt around the periphery adjacent to the bottom These features require that tapped lugs be welded on the upper plate of the cell at specific locations to match corresponding holes drilled in the cross piece When the cage has been lifted to a vertical position it is lowered onto the cell The bottom of the cage should be guide by at least two people to prevent it from twistin...

Отзывы: