
8
3.3 GK-403 Readout Box (Obsolete Model)
The GK-403 can store gauge readings and apply calibration factors to convert readings to
engineering units. The following instructions explain taking gauge measurements using Mode
“B”. Consult the GK-403 Instruction Manual for additional information.
3.3.1 Connecting Sensors
Connecting Sensors with 10-pin Bulkhead Connectors Attached:
Align the grooves on the sensor connector (male), with the appropriate connector on the
readout (female connector labeled senor or load cell). Push the connector into place, and
then twist the outer ring of the male connector until it locks into place.
Connecting Sensors with Bare Leads:
Attach the GK-403-2 flying leads to the bare leads of a Geokon vibrating wire sensor by
connecting each of the clips on the leads to the matching colors of the sensor conductors,
with blue representing the shield (bare).
3.3.2 Operating the GK-403
1)
Turn the display selector to position “B”.
2)
Turn the unit on.
3)
The readout will display the vibrating wire output in digits. The last digit may change
one or two digits while reading.
The thermistor reading will be displayed above the gauge reading in degrees
centigrade.
4)
Press the “Store” button to record the value displayed.
If the no reading displays or the reading is unstable see Section 5 for troubleshooting
suggestions. The unit will automatically turn itself off after approximately two minutes to
conserve power.
3.4 Measuring Temperatures
All vibrating wire pressure cells are equipped with a thermistor which gives a varying resistance
output as the temperature changes. The white and green leads of the instrument cable are
normally connected to the internal thermistor. Readout boxes will read the thermistor and display
the temperature in degrees C. To read temperatures using an ohmmeter complete the following:
1.
Connect an ohmmeter to the green and white thermistor leads coming from the pressure
cell. (Since the resistance changes with temperature are large, the effect of cable
resistance is usually insignificant. For long cables a correction can be applied, equal to
approximately 14.7
Ω
for every 1000 ft (48.5
Ω
per km) at 20 °C. Multiply these factors
by two to account for both directions.)
2.
Look up the temperature for the measured resistance in Appendix B, Table 4.