47
Problem
Possible reasons
Possible solutions
The product
does not
supply hot
water
The unit is not connected to the
power supply
Make sure the display turns ON
Alarms from the controller stop the
operation of the unit
Check the alarms in the Info menu Er
Low water temperature set points
Increase all temperature set points in menu
A Temperatures
Low airflow in evaporator
Clean the evaporator and the air ducts
Fan does not work
Make sure that the fan is connected to the
PCB or substitute the component.
SG Ready function is active
Switch OFF SG Ready function
Themal safety switch FN1 opens
and stops the power supply to the
electric heater
Restore the original conditions of the ther-
mal safety switch FN1.
High sound
emissions
Too high maximum fan speed
Reduce the fan maximum speed in the
Installer menu
Activate the SILENT mode
Obstruction of the air ducts.
Remove the obstruction
Dirt on fan or evaporator.
Clean the evaporator and the fan. Do not
use cleaning spray that can be damage the
EPS housing
Components vibration
Make sure all components as compressor
and solenoid valve are well fastened