3. POSITIONING
The installation site should be equipped with a power supply of 220-240V and 50 Hz.
The power supply and the hydraulic system must comply with the local regulations.
The unit should be placed vertically, with a maximum inclination of 1°. The unit must be
well balanced and stable on the ground surface. Use the built-in adjustable pads to
level the unit.
The unit must be installed as close as possible to the hydraulic system in order to mini-
mize heat losses in the water pipes. The water pipe outlet should be insulated for the
same reason.
The unit should not be placed in direct contact with the sunlight.
The unit can only be installed in a frost-free room and it should follow the criteria:
• Room temperature between 5°C and 40°C.
• Drain possibility for condensate and floor drain.
• No abnormal dust concentration in the air.
• Solid base (approx. 500 kg / m
2
).
• It is necessary to ensure that there is sufficient space around the unit for mainte-
nance and service. A clearance of 0.5 m around the unit is recommended.
Ducted unit
In case of a ducted unit, the unit should be
installed as close as possible to the walls in order
to minimize pressure losses in the air ducts.
Not-ducted unit
In case the unit is used without exhaust/extrac-
tion air ducts, it should be placed in a room with
the following characteristics:
• The volume of the room should be more than
30 m
3
.
• The room should be well ventilated.
• There should be no other appliances that need
air to operate.
• The minimum distances described in Figure 9
should be respected.
Figure 9 - Minimum distance from
walls for not-ducted units