Installation

When installing the units follow these instructions:

1) Tilt the machine 10-15 mm towards the drainpipe 

to  allow  condensing  water  to  run  to  drain. 

(Does not apply for GES)

2) Install  an  airtight  water  trap  on  a  non-freezing 

location, to compensate for fan pressure.

3) The water trap hight 

must be

 at least 100 mm.

4) Make sure that the drain flows downwards all the 

way from the unit.

5) Pour  1  liter  water  into  the  driptray  in  the  unit  to 

verify that it is drained properly. Up to the heating 

season make sure that the drain is properly filled 

with water. 

6) If freezing of the water trap may occur, it is necessary 

to install a thermostat and electrical heater to prevent 

freezing, when the temperature drops below +2C°.

7) Airflow adjustments must be made on both supply 

and exhaust sides for a normal use of the machine. 

It  is  important  to  have  a  balance  between  supply 

and exhaust air volumes

8) It  is  recommended  to  keep  the  ducts  closed  until 

the unit is adjusted and used.

This  instruction  must  be  followed.  If  the  drain  is  not 

made according to this instruction, GENVEX A/S can 

not be made responsible for any additional damages, 

which have nothing to do with the GENVEX unit.

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

  IMPORTANT 

.

100 mm

Siphon

To internal drain

Extract Air

Fresh Air

Supply Air

Exhaust Air

Lack of water in siphon = water damage

1%

Содержание GE ENERGY 1

Страница 1: ...Version 1 02 0110 GB Installations Manual Passive Ventilation Counter Current Heat Exchanger GE Energy 1 GE Energy 2 GE Energy 3...

Страница 2: ...on of ducts in cold loft spaces 7 Insulation of ducts in heated spaces 8 Reheating of supply air 8 Electrical installation 9 Inspection and initial adjustment of appliance 9 Optimum initial adjustment...

Страница 3: ...occur it is necessary to install a thermostat and electrical heater to prevent freezing when the temperature drops below 2C 7 Airflow adjustments must be made on both supply and exhaust sides for a no...

Страница 4: ...d rear panels may be removed the back panel mounted on the front and the unit rotated 180 This will cause the supply to exchange places with the escaping and the fresh air with the extract with the co...

Страница 5: ...to an internal drain without danger of freezing in cold weather as a unit may produce up to 8 10 litres of condensate per day To allow access for service and maintenance there must be a clear space of...

Страница 6: ...escaping roof cowls external grills Duct system It is recommended that the duct system is executed in spiral ducting connected with rubber ring seal fittings in order to provide a leak free and durabl...

Страница 7: ...sure that the water in it does not freeze If installation problems make it impossible to secure the condensate drain pipe from freezing by insulation it will be necessary to mount a thermostat control...

Страница 8: ...pply it to the supply air the supply air will be about 1 4 C colder than the room temperature in the dwelling for the whole winter season If this lower supply temperature is insupportable during cold...

Страница 9: ...ck that hatches can be opened so that service and maintenance on the unit can be carried out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is cor...

Страница 10: ...d by shaking it and by removing the worst dirt switch on the unit and press the enter button on the control panel for 10 15 seconds until the Genvex logo starts flashing again and the equipment is bac...

Страница 11: ...ery year If it is dirty remove it and wash in warm soapy water and then rinse possibly in the bathroom using the shower head Fans Every year check the two fan wheels for dirt If they are dirty they ma...

Страница 12: ...oms Error Defective fan Blocked bag filter Fresh air grill blocked by dirt and leaves in the autumn or snow and ice in the winter Fuse on control circuit board has blown No power No extract air from w...

Страница 13: ...Yell Green Yell Green Blue Blue Yellow Yellow L N Wire no 5 Is not used No 3 White Nr 1 Black Nr 2 Red No 1 Black Nr 3 White No 2 Red Hy Set T1 90 C manu T1 90 C manu N PE L L PE N Optima 250 Control...

Страница 14: ...vex Hygrostat Potentialfree Contact Must be used Mains U 1x230V 50Hz 13 A 230V Controlrelay for Electrial Reheater L1 N Sensor Heatrelay Sensor defrost Optima 100 RJ 45 Hy Set T1 M1 Supply M2 Exhaust...

Страница 15: ...15 Installation EU Declaration of conformity...

Страница 16: ...m Artiklima bvba B 9220 Hamme Tel 32 0 52 41 25 41 Fax 32 0 52 41 29 66 E Mail info artiklima be Great Britain Total Home Environment Ltd GB Moreton in Marsh GL 56 0JQ Tel 44 0 845 260 0123 Fax 44 0 1...

Отзывы: