3
Installation
When installing the units follow these instructions:
1) Tilt the machine 10-15 mm towards the drainpipe
to allow condensing water to run to drain.
(Does not apply for GES)
2) Install an airtight water trap on a non-freezing
location, to compensate for fan pressure.
3) The water trap hight
must be
at least 100 mm.
4) Make sure that the drain flows downwards all the
way from the unit.
5) Pour 1 liter water into the driptray in the unit to
verify that it is drained properly. Up to the heating
season make sure that the drain is properly filled
with water.
6) If freezing of the water trap may occur, it is necessary
to install a thermostat and electrical heater to prevent
freezing, when the temperature drops below +2C°.
7) Airflow adjustments must be made on both supply
and exhaust sides for a normal use of the machine.
It is important to have a balance between supply
and exhaust air volumes
8) It is recommended to keep the ducts closed until
the unit is adjusted and used.
This instruction must be followed. If the drain is not
made according to this instruction, GENVEX A/S can
not be made responsible for any additional damages,
which have nothing to do with the GENVEX unit.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
100 mm
Siphon
To internal drain
Extract Air
Fresh Air
Supply Air
Exhaust Air
Lack of water in siphon = water damage
1%