TROUBLESHOOTING

Safety thermostat in electric heating surface

If a fault occurs in the built-in electric heating surface, the 

safety thermostat will switch off the unit. The electric 

heating surface is equipped with a fire thermostat, which 

automatically shuts off the power if the temperature 

exceeds 40°C. When the temperature drops, the heating 

surface automatically switches back on.

As an extra safety feature, there is a built-in thermal fuse 

which triggers disconnection if the temperature exceeds 

60°C. 

Reconnection must be executed manually via the red button 

indicated in the pictures below.

System not running

•  Fuse in electric panel has blown, no voltage in the 

system.

•  One of the fuses in the system’s control board has blown.

•  Loose wire, no voltage to the unit.

•  Incorrectly set weekly program.

•  Filter timer has switched off the system.

 

No supply air 

•  Defective supply air fan.

•  Clogged supply air filter.

•  Outdoor air grille clogged with dirt and leaves in the 

autumn, or snow and ice in the winter.

•  Fuse on control board has blown.

•  Unit is defrosting (supply air fan runs at reduced speed)

•  Incorrect setting of Optima controls

No exhaust air

•  Defective exhaust fan.

•  Clogged exhaust filter.

•  Fuse on control board has blown.

Cold supply air

Fault

•  Heat exchanger is clogged.

•  Exhaust fan is defective.

•  Exhaust filter is clogged.

•  The electric post-heating surface has been switched off 

at the overheating thermostat (only systems with 

electric reheater installed).

•  Air in heating pipe, defective thermostat/motor valve, 

incorrect setting of control panel.

If none of the above errors are relevant, contact:

•  During the warranty period (0-2 years), the installer from 

whom the unit was purchased.

•  After the warranty period (2 years ->), the installer from 

whom the unit was purchased or the Genvex Customer 

Centre by calling 7353 2700. 

Please have the data from the type plate ready (silver plate 

on the unit).

Alerts

See Optima 270 operating instructions.

No

.

Item no

.

Description

12

071008

Rotary exchanger Ø375x200

13

071009

Brush TF 4.8x14 4P BK 2TFBK

14

071010

Brush strip

15

071011

Vertical gasket – rotor

16

071012

Peripheral gasket – rotor

17

071017

Wire gasket, rotor cassette

18

071021

Drive belt Ø6

19

071022

24V motor

20

071023

Pulley wheel

21

071025

Converter 230V – 24V DC

22

071069

Vibration damper Ø20x10 M6

Left-hand system

Right-hand system

Содержание ECO 360 R

Страница 1: ...INSTALLATION MANUAL ECO 360 R Mechanical ventilation with passive heat recovery A...

Страница 2: ...e system 12 Optimal initial commisioning of the system 12 System maintenance 13 Filters 13 Access to internal parts 14 Cleaning and inspection of rotary heat exchanger 15 Post heating surface 16 Fan 1...

Страница 3: ...guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be performed by children without su...

Страница 4: ...g and reduced to a level necessary for efficient defrosting During defrosting an integrated modulating electric reheater ensures that the supply air temperature is maintained at an appropriate level T...

Страница 5: ...vy structural component such as concrete It should also be ensured that no sound or vibra tions can be transmitted through materials in contact with the technical system If there is a risk of propagat...

Страница 6: ...to the filter frame e g using elastic straps as shown in the picture below so that the filter is held in place and ensures 100 filtration Please note that this type of installation of the unit will r...

Страница 7: ...there must be a clearance of at least 600 mm in front of the ECO 360 R 5 5 34 600 600 596 4 131 131 143 2 282 200 160 3 4 1 2 Right hand version 1 Discharge air 2 Extract air 3 Outdoor air 4 Supply ai...

Страница 8: ...supply air to the right of the unit and a left hand version charac terised by the reheater being located in the supply air to the left of the unit It is possible to convert a right hand unit into a l...

Страница 9: ...e duct installation it is recommended using 4 x 160 mm nipple connectors with double sealing lips Alternatively a 200 mm spiro pipe can be used which is connected directly to the outside of the ECO 36...

Страница 10: ...grates should be placed on the north or east side of the house to achieve optimal comfort in homes flats It is recommended that the air intake should be located on the north or east side of the house...

Страница 11: ...rovided with 50 mm of insulation finished with alumini um foil Supply air and exhaust air ducts routed through heated rooms in the home do not need to be insulated unless cooling a bypass or a geother...

Страница 12: ...osition The intermediate valves are opened between 4 and 7 turns depending on how close they are to the unit 5 It is recommended setting the integrated post heating surface to a supply air temperature...

Страница 13: ...means that the filters must be replaced cleaned The system is stopped by removing the appliance connec tor from the ECO 360 R or at the socket The filter plugs are opened and the filter drawer is pull...

Страница 14: ...removed 1 Remove the screws from the front plate to access internal parts 2 Remove the protective plate covering the control board 3 Remove the 230V power cable and the control cable for the rotary ex...

Страница 15: ...ng brushes unscrew the strips as shown in the picture below New brushes are fitted and the strips screwed back on BE CAREFUL not to overtighten the screws for the brush strips Check that the drive bel...

Страница 16: ...do not use power tools to tighten the bolts as this may result in damage to the threaded connections Carefully tighten all the front plate bolts until the front plate is firmly seated on the housing...

Страница 17: ...ets in general Check gaskets on the unit and make sure they are intact 12 months Supply air and exhaust valves Check for dirt in supply air and exhaust valves Clean as needed Check that the valves hav...

Страница 18: ...l 21 071025 Converter 230V 24V DC 22 071069 Vibration damper 20x10 M6 PARTS LIST PART NUMBER STOCK NUMBER ITEM Gummifod 25x25 M6x18 068098 1 OPTIMA 270 Print 069875 2 IO print 069876 3 Samlet ventilat...

Страница 19: ...an Clogged supply air filter Outdoor air grille clogged with dirt and leaves in the autumn or snow and ice in the winter Fuse on control board has blown Unit is defrosting supply air fan runs at reduc...

Страница 20: ...utdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1x230V 50Hz Blue Yellow green Humidity sensor P1 EC fan S...

Страница 21: ...fan Supply air EC fan Extract air 1x230V 50Hz Black Blue Yellow green Humidity sensor P1 EC fan Supply air 1x230V 50Hz Control signal Rotor Modulating Reheating Modulating Preheating Potential free i...

Страница 22: ...2 4 6 8 10 12 14 0 5 10 15 20 25 30 Watt RPM Power consumption of display control board and rotor Heat and moisture recovery rotor according to 13141 7 0 10 20 30 40 50 60 70 80 90 100 1 3 5 10 15 20...

Страница 23: ...DE COMMISIONING INSTRUCTIONS The declaration of conformity can be downloaded from www genvex com For further information on dismantling components with a view to disposal and recycling see illustrati...

Страница 24: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: