background image

 

  

13

Remember to switch off the power by removing the appli-

ance connector from the ECO 360 R or at the socket (it can 

be difficult to reach the appliance connector on the unit 

when ducts have been mounted and insulated) before 

changing the filter or opening the unit.

Filters

When the filter timer reaches the set value for a filter 

change, this will appear in the text in the Optima Touch 

display or in the Genvex app, or be indicated by a yellow 

flashing light in Optima Basic. This means that the filters 

must be replaced/cleaned.

The system is stopped by removing the appliance connec-

tor from the ECO 360 R or at the socket. The filter plugs 

are opened and the filter drawer is pulled out. Once the 

filters have been cleaned/replaced, insert the filter drawer 

with the clean filters and click the filter plugs into place in 

the cabinet again. Reconnect the 230V power.

The filter alarm can now be reset via the display or the app.  

The system then returns to normal operation.

If you want to replace the filters with a different time 

interval,this can be done via the user menu.

 Do not vacuum or clean at high air pressure.  

 

This will damage the filter!

SYSTEM MAINTENANCE

Содержание ECO 360 R

Страница 1: ...INSTALLATION MANUAL ECO 360 R Mechanical ventilation with passive heat recovery A...

Страница 2: ...e system 12 Optimal initial commisioning of the system 12 System maintenance 13 Filters 13 Access to internal parts 14 Cleaning and inspection of rotary heat exchanger 15 Post heating surface 16 Fan 1...

Страница 3: ...guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be performed by children without su...

Страница 4: ...g and reduced to a level necessary for efficient defrosting During defrosting an integrated modulating electric reheater ensures that the supply air temperature is maintained at an appropriate level T...

Страница 5: ...vy structural component such as concrete It should also be ensured that no sound or vibra tions can be transmitted through materials in contact with the technical system If there is a risk of propagat...

Страница 6: ...to the filter frame e g using elastic straps as shown in the picture below so that the filter is held in place and ensures 100 filtration Please note that this type of installation of the unit will r...

Страница 7: ...there must be a clearance of at least 600 mm in front of the ECO 360 R 5 5 34 600 600 596 4 131 131 143 2 282 200 160 3 4 1 2 Right hand version 1 Discharge air 2 Extract air 3 Outdoor air 4 Supply ai...

Страница 8: ...supply air to the right of the unit and a left hand version charac terised by the reheater being located in the supply air to the left of the unit It is possible to convert a right hand unit into a l...

Страница 9: ...e duct installation it is recommended using 4 x 160 mm nipple connectors with double sealing lips Alternatively a 200 mm spiro pipe can be used which is connected directly to the outside of the ECO 36...

Страница 10: ...grates should be placed on the north or east side of the house to achieve optimal comfort in homes flats It is recommended that the air intake should be located on the north or east side of the house...

Страница 11: ...rovided with 50 mm of insulation finished with alumini um foil Supply air and exhaust air ducts routed through heated rooms in the home do not need to be insulated unless cooling a bypass or a geother...

Страница 12: ...osition The intermediate valves are opened between 4 and 7 turns depending on how close they are to the unit 5 It is recommended setting the integrated post heating surface to a supply air temperature...

Страница 13: ...means that the filters must be replaced cleaned The system is stopped by removing the appliance connec tor from the ECO 360 R or at the socket The filter plugs are opened and the filter drawer is pull...

Страница 14: ...removed 1 Remove the screws from the front plate to access internal parts 2 Remove the protective plate covering the control board 3 Remove the 230V power cable and the control cable for the rotary ex...

Страница 15: ...ng brushes unscrew the strips as shown in the picture below New brushes are fitted and the strips screwed back on BE CAREFUL not to overtighten the screws for the brush strips Check that the drive bel...

Страница 16: ...do not use power tools to tighten the bolts as this may result in damage to the threaded connections Carefully tighten all the front plate bolts until the front plate is firmly seated on the housing...

Страница 17: ...ets in general Check gaskets on the unit and make sure they are intact 12 months Supply air and exhaust valves Check for dirt in supply air and exhaust valves Clean as needed Check that the valves hav...

Страница 18: ...l 21 071025 Converter 230V 24V DC 22 071069 Vibration damper 20x10 M6 PARTS LIST PART NUMBER STOCK NUMBER ITEM Gummifod 25x25 M6x18 068098 1 OPTIMA 270 Print 069875 2 IO print 069876 3 Samlet ventilat...

Страница 19: ...an Clogged supply air filter Outdoor air grille clogged with dirt and leaves in the autumn or snow and ice in the winter Fuse on control board has blown Unit is defrosting supply air fan runs at reduc...

Страница 20: ...utdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1x230V 50Hz Blue Yellow green Humidity sensor P1 EC fan S...

Страница 21: ...fan Supply air EC fan Extract air 1x230V 50Hz Black Blue Yellow green Humidity sensor P1 EC fan Supply air 1x230V 50Hz Control signal Rotor Modulating Reheating Modulating Preheating Potential free i...

Страница 22: ...2 4 6 8 10 12 14 0 5 10 15 20 25 30 Watt RPM Power consumption of display control board and rotor Heat and moisture recovery rotor according to 13141 7 0 10 20 30 40 50 60 70 80 90 100 1 3 5 10 15 20...

Страница 23: ...DE COMMISIONING INSTRUCTIONS The declaration of conformity can be downloaded from www genvex com For further information on dismantling components with a view to disposal and recycling see illustrati...

Страница 24: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: