SPRINT 11 SW

ENGLISH

Guide for the installer

Pagina 1

Gate at closure

If the encoder operates during the gate closing movement, the consequence is a brief reversal of movement, then the control 

unit goes into STOP condition, disabling thus any automatic functions to make the obstacle removal possible. To resume normal 

memory-stored cycle, send an OPEN impulse after having removed the obstacle.

  At the fourth closing movement, if the obstacle has not been removed for any reason whatsoever, the gate stops without 

performing any reversal of movement. The next movement will be performed in slow-down mode to enable new 

memory storage of the limit switches.

9. ADJUSTMENT OF MOTOR POWER

By using trimmer “

TR1

” you can adjust the power of the motor. Variation of motor power also influences the obstacle detection 

sensitivity. To be more precise, by increasing motor power, one reduces obstacle detection sensitivity and vice versa by reducing 

motor power, one increases obstacle detection sensitivity.

Turn the trimmer anti-clockwise to reduce motor power, vice versa, turn it clockwise to increase motor power.

  Motor power must be adjusted according to the characteristics of the gate, the weight, friction, etc..

 

Adjust motor power only after having cut power to the control unit.

10. PROGRAMMING

  Never perform the programming procedure when the control unit is powered only by batteries.

After having carried out the connections necessary for a correct operation of the operator and set the desired operating 

parameters using the DIP-SWITCHES, before starting and using the automated system you need to perform a programming 

operation to teach the correct operating cycle.

Instructions for the programming operation:

Cut power to the system using the differential switch upstream of the system.

Prepare the operator for manual operation as shown in the operator instructions and take the gate to about half of 

total opening.

Re-block the gearmotor and make sure that it cannot be moved manually.

Power up the system.

Press and hold down push-button 

PROG

 for about 1 second till the flashing lamp goes ON on steady beam.

Send a total opening pulse using any pulse generator connected to the 

OPEN A

 input.

  The first manoeuvre the gate performs must be closing. If the gate starts with an opening manoeuvre, stop gate motion 

pressing the RESET push-button and reverse the two power cables of the motor connected to terminals “OP & CL” of 

terminal board CN2.

When the closing travel limit device has been reached, the gate begins the opening manoeuvre till reaching the relevant 

travel limit.

When the opening travel limit device has been reached, the following occurs according to the selected logic:

With manual or step-by-step manual logic: the programming phase has finished, send an

 OPEN A

 pulse to end the 

programming phase and close the gate.

With automatic or step-by-step automatic logic: the control unit starts the pause time count. When the required time has 

elapsed, send an 

OPEN A 

command, the programming phase has finished and the gate starts to close.

  During programming, gate movement is slowed down.

  For a successful programming, we recommend you not to engage, during the programming phase, any safety devices 

(i.e. photocells) connected to the control unit.

 

In the event of a mains voltage cut and if there are no buffer batteries (or if there are flat batteries) the following behaviours 

will be present when mains voltage is restored:

Gate closed: at the first OPEN (OPEN A or OPEN B) pulse, the gate performs the opening phase in a decelerated way (reset 

cycle). When the opening travel limit device has been reached, the cycle is complete and, according to the selected 

function logic, it re-closes after pause time or waits for an OPEN (OPEN A or OPEN B) pulse to re-close the gate.

Gate open: when mains voltage has been restored, independently of the selected logic, at the first (OPEN A or OPEN B) 

pulse, it performs the reset cycle (opening in a decelerated way) but, since the travel limit has already been reached 

no movement occurs and the reset cycle is complete. Now, according to the selected logic, it re-closes after pause 

time or a pulse (OPEN A or OPEN B) is necessary to close the gate.

Gate at rest in any position different from the two cases above: at the first OPEN (OPEN A or OPEN B) pulse, the gate 

performs the opening phase in a decelerated way. When the opening travel limit device has been reached, the reset 

cycle is complete and, according to the selected function logic, it re-closes after the pause time or waits for an OPEN 

(OPEN A or OPEN B) pulse to re-close the gate.

  As long as the reset operation is occurring, the control unit disables every connected pulse generator; only safety devices 

are active. When the reset phase has finished, normal operation is resumed.

1.

2.

3.

4.

5.

6.

7.

8.

a–

b–

1.

2.

3.

Содержание SPRINT 11 SW

Страница 1: ...SPRINT 11 SW Istruzioni per l uso Instructions for use Instructions pour l usager Instrucciones para el uso Gebrauchsanleitung Gids voor de gebruiker...

Страница 2: ...ct underwent a test in a typical uniform configuration all products manufactured by GENIUS S p A Grassobbio October 22 2009 Managing Director D Gianantoni INDEX 1 GENERAL CHARACTERISTICS page 13 2 TEC...

Страница 3: ...trimmer adjustable Terminal board inputs Mains power supply Travel limit device at opening Travel limit device at closing STOP Safety devices OPEN A OPEN B Batteries Rapid connector Battery charger Ra...

Страница 4: ...LED for OPEN B radio input status JP3 Quick fit connector for battery kit on board the machine FSW LED for FSW input status DP Programming dip switch STOP LED for STOP input status POWER Trimmer for...

Страница 5: ...nnected in series If safety devices are not connected these two terminals must be jumper connected 5 2 4 Stop Terminals STOP COM Normally closed contact Connect any pulse generator i e push button key...

Страница 6: ...T Only common lead batteries can be used having a capacity not exceeding 4Ah The operation of the battery kit is described in the following paragraph The compartment housing the remote batteries must...

Страница 7: ...e Safety devices active during both closure and opening OPENA input use this dip switch to select between two operations of the devices connected to the OPENA command Every pulse of the command revers...

Страница 8: ...top gate motion pressing the RESET push button and reverse the two power cables of the motor connected to terminals OP CL of terminal board CN2 When the closing travel limit device has been reached th...

Страница 9: ...Put the two radio controls frontally into contact On the memory stored radio control press and hold down the push button relating to the channel you wish to transfer the radio control LED lights up o...

Страница 10: ...Ds LED ON OFF OPA OPEN A radio command active OPEN A radio command inactive OPB OPEN B radio command active OPEN B radio command inactive FSW Safety devices free Safety devices engaged STOP STOP comma...

Страница 11: ...ffect No effect Stops operation No effect Stops operation and resumes after release STEP BY STEP AUTOMATIC LOGIC DIP SWITCH 3 ON DIP SWITCH 5 ON GATE STATUS INPUTS OPEN A OPEN B STOP PHOTOCELLS DIP SW...

Страница 12: ...ffect Stops operation No effect Stops operation and resumes after release STEP BY STEP MANUAL LOGIC DIP SWITCH 3 OFF DIP SWITCH 5 ON GATE STATUS INPUTS OPEN A OPEN B STOP PHOTOCELLS DIP SWITCH 4 OFF D...

Отзывы: