GE-NUTRI USER’S GUIDE 

 

GE-NUTRI 

 

Section C-65 

5.

  This  parameter  is  used  to  set  the  potentiometer  lower  limit  for  the  actuator 

calibration.  This  will  effectively  define  the  lowest  possible  value  for  the 
actuator’s potentiometer. To obtain this value, completely close the actuator 
using 

OPER  MANUAL  [4]

.  Once  the  actuator  is  completely  closed,  press 

 SELECT 

 when the cursor is on this parameter. At this point, the text displayed 

here will change to 

"Low Limit Saved"

 if the value was correctly saved, 

"Can’t Save Check Pot"

 if the value of the potentiometer could not be 

read  or 

"Can’t  Save  Low  Limit"

  if  an  error  occurred  during  the 

operation.  In  the  two  later  cases,  calibration  must  be  performed  once  the 
situation is corrected. 

6.

  This parameter is used to set the potentiometer upper limit for calibration of 

the actuator. This will effectively define the highest value that can be read by 
the  actuator  potentiometer.  To  get  this  value,  completely  open  the  actuator 
using 

OPER  MANUAL  [4]

.  Once  the  actuator  is  completely  open,  press 

 SELECT 

  when  the  cursor  is  on  this  setting.  At  this  point,  the  text  displayed 

here will change to 

"High Limit Saved"

 if the value was correctly saved, 

"Can’t Save Check Pot"

 if the value of the potentiometer could not be 

read  or 

"Can’t  Save  Hi  Limit"

  if  an  error  occurred  during  the 

operation.  In  the  two  later  cases,  calibration  must  be  performed  once  the 
situation is corrected. 

7.

  This parameter is used to set the maximum run time of the actuator within a 

ten-minute period. When an actuator has moved for a time greater than the 
value  of  this  parameter  within  a  ten-minute  period,  the  module  will  not 
activate the open or close relays until the actuator has had time to cool down 
and an alarm message will be logged in the alarm history. The alarm goes off 
if  the 

ACTUATOR  ALARM  [3]

  is  set  to 

"ON"

.  This  value  should  be  set 

according to the manufacturer’s specifications. Setting this value to “

OFF

” will 

deactivate  the  module  cool  down  function.  If  the  actuator  is  already  in  cool 
down mode when this parameter is set to  “

OFF

”, it will finish the cool down 

period  before  deactivating  the  function.  This  parameter  is  adjusted  in  1-
minute increments from 1 minute to 9 minutes, “

OFF

”. 

 

Содержание GE-NUTRI

Страница 1: ...INFORMATION IN SECTION B MANUA NUTRI Installation User s Guide ATTENTION ELECTRICIAN SEE WIRING DETAILS ON PAGES A ADDITIONAL INFORMATION IN SECTION B MANUAL NUTRI Installation User s Guide ELECTRICIA...

Страница 2: ...quipment may damage this equipment For added security against line voltage surges it is recommended that surge and noise suppression devices be installed at the electrical distribution panel Use of sh...

Страница 3: ...GE NUTRI WIRING DIAGRAM GE NUTRI Section A 3 WIRING DIAGRAM GE NUTRI SECTION A...

Страница 4: ...ntification WARNING MAKE SURE T HE VOLTAGE SELECTOR MATCHES THE VOLTAGE LINE BOARD LAYOUT AND ACTUATOR IDENTIFICATION GE NUTRI 1HP RELAY LIN E VOLTA GE SELECTOR 230V 5 OPEN OUVR E F ER ME POS 3 OPEN C...

Страница 5: ...d relay Identification WARNING MAKE SURE T HE VOLTAGE SELECTOR MATCHES THE VOLTAGE LINE BOARD LAYOUT AND RELAY IDENTIFICATION GE NUTRI 1HP RELAY LIN E VOLTA GE SELECTOR 230V 5 4 2 3 1 PO S 1 POS 2 POS...

Страница 6: ...B 4 WARNING MAKE SURE THE VOLTAGE SELECTOR MATCHES THE VOLTAGE LINE PR B 7 PRB 8 FEEDER FEED AUGER MICRO SWITCH POTENTIOMETER FOR POSITIONER C1 B1 A1 POS1 POT 1 3 9 POT 2 C2 B2 A2 POS 2 C3 B3 A3 POS3...

Страница 7: ...R4 6 5 ON OFF BOARD L2 N L1 L2 N L1 L2 N L1 3 REL 1 REL 2 X1314 R2 6 5 ON OFF BOARD 4 2 L2 N L1 L2 N L1 REL 1 REL 2 X1314 R2 6 5 ON OFF BOARD 5 L2 N L1 L2 N L1 L2 N L1 POS 1 OPEN FEEDER FEED AUGER 15...

Страница 8: ...RD PR B 1 PR B 2 PRB 3 PR B 4 PR B 6 PRB 7 PR B 8 9 PRB 5 SHEILD JP1 JP2 12 VDC X1399 8 M GCB P 0 IN PUT DC 12V JP3 ID 1 ID 2 J P4 J P3 2 4 0 0 1 9 2 0 0 JP4 10 10 B A FEEDER FEED AUGER MICRO SWITCH E...

Страница 9: ...SISTIVE MOTOR 1HP 240VAC 1 2HP 120VAC AT EACH OUTPUT 1 WIRE ONLY PER GREEN TERMINAL USE WIRE CONNECTOR IF YOU WANT TO CONNECT MORE THAN 1 WIRE NO BIGGER THAN AWG 12 NO SMALLER THAN AWG 28 CHECK INSTAL...

Страница 10: ...GE NUTRI INSTALLATION Section B 10 GE NUTRI INSTALLATION GE NUTRI SECTION B...

Страница 11: ...r damage Should the contents appear to be damaged contact your local distributor to return the equipment The package should contain the following standard items 1 GE NUTRI control 4 Brackets 4 screws...

Страница 12: ...ectrical cables All electrical cables must be installed according to local wiring codes All cable shields must be connected to the shield terminal on the cord to which the cable is connected except fo...

Страница 13: ...mounting holes on the back of the enclosure using the four screws provided with the brackets Then mount the enclosure on the wall by inserting screws through the brackets adjustment slots into the wa...

Страница 14: ...diagrams Typical positioner wiring Follow the calibration procedure in the user guide otherwise the positioner positioning will be erratic FIGURE NO 2 Typical 115V Positioner Wiring CLOSE OPEN COM WIN...

Страница 15: ...if source 1 is disabled The backup relay should be selected to ensure it is able to support the required power load FIGURE NO 3 Typical Power Backup Wiring 8 PIN RELAY DPDT OMRON model MK2EP UA AC120...

Страница 16: ...r this same contact can be used to signal a power failure or other malfunctions It may be connected to an alarm system or directly to a siren and or auto dialer Make the normally closed NC or normally...

Страница 17: ...the GE NUTRI controller and a short description of their function Micro Switch On off switch read by the controller CSD 1 Current detector for feed augers GE NUTRI Controller compatible modules This...

Страница 18: ...commended wires 2 strands shielded AWG 22 8 INPUT MGCB BOARD X1276 PROBE INPUTS PRB1 PRB8 Input measuring range 0 Ohm open circuit 0 5000 mV 0 20 mA PRB 7 and 8 Maximum frequency for the water meter 5...

Страница 19: ...ded maximum current for fans 12A 120 208 240VAC Minimum load 300mA 230VAC PLS OUTPUTS Recommended wires 2 conductors twisted pair 8 twist ft AWG 22 Maximum wire length 350pF m cable 160ft 50m Maximum...

Страница 20: ...ION Screen is blank GE NUTRI Controller is not powered The connector between the top and the main boards or between the relay control and the main boards of the GE NUTRI Controller is disconnected Mak...

Страница 21: ...GE NUTRI USER S GUIDE GE NUTRI Section C 21 USER S GUIDE GE NUTRI SECTION C...

Страница 22: ...GE Section C Control NUTRI USER S GUIDE Section C 22 Control Description 2 1 USER S GUIDE Description USER S GUIDE Description 3 4 5 GE NUTRI NUTRI 6 7...

Страница 23: ...navigation buttons are represented by 4 squares with arrows on them 5 Select Button The SELECT button allows the users to select a parameter activate an option or access a screen 6 Value Setting Butt...

Страница 24: ...rsion Date Modification C2V27V0 9 06 15 2017 New C2V27V1 9 07 17 2017 Add English language Correction on feeder s alarm Correction on certain parameters visibility Modification on alarm reset paramete...

Страница 25: ...AD mode Add an option to stop active cycle C2V27V4 9 06 25 2018 Modification on program state control Modification on proximity switch influence on feed auger activated manually in multi feed mode Add...

Страница 26: ...n default values Change in terminology for the drop phase Modification on the starting and stopping time of the drop phase for relative values when no potentiometers are used Add an activation delay f...

Страница 27: ...Each feed auger has a unique feeding timer This timer works by an On time and an Off time in multi feed mode The status screens show the actual cycle the time pas since the beginning of the cycle and...

Страница 28: ...lter The feed auger stops when the proximity switch indicates that the manger is full for the filter s end time The feeder continues for an adjustable delay until the end of the cycle In feed auger dr...

Страница 29: ...e clock 3 This parameter is used to select the time format for all clock type parameters The display may be 24hr or AM PM 4 This parameter is used to choose the language used by the control The availa...

Страница 30: ...ter is used to access the ALARMS screen page C 52 4 This parameter is used to access the INSTALLATION screen page C 56 5 These parameters display the type of the corresponding program 9 M a i n M e n...

Страница 31: ...reen page C 55 of the corresponding program 9 These parameters are used to access the BACKUP PROGRAM 1 4 screen page C 51 of the corresponding program 10 This parameter allows the changing of the prog...

Страница 32: ...ble between two cycles 5 This parameter displays the time elapsed since the beginning of the cycle The time is display in hh mm format This parameter is not visible between two cycles 6 This parameter...

Страница 33: ...the FEED AUGER 1 8 FEEDER HISTORY screen page C 35 of each feed auger In feed auger drop mode there can be up to 8 feed augers In other modes there can be up to 4 feed augers These parameters display...

Страница 34: ...d feed auger drop and chain feeder drop mode 7 These parameters display the requested positions by the program to the actuators The requested positions are displayed with a resolution of 1 to 0 to 100...

Страница 35: ...are used to navigate through the different days of history by pressing SELECT when the cursor is located on the number The number indicates which ranges of the day will be displayed 3 These parameters...

Страница 36: ...rogram status It can be Auto Pause or Abort When this parameter is set to Auto the outputs assigned to this program will activate accordingly to the current cycle When the mode is Pause all the progra...

Страница 37: ...OFF no cycle can start automatically 4 This parameter is used to access the FEEDS PROGRAM 1 4 screen page C 38 5 This parameter is used to access the TIMERS PROGRAM 1 4 screen page C 40 6 This parame...

Страница 38: ...ion C 38 GE NUTRI MAIN MENU SETTINGS PROGRAM 1 4 FEEDS PROGRAM 1 4 1 This parameter is used to access the FEED 1 4 PROGRAM 1 4 screen page C 39 corresponding F e e d A u g e r P r o g F e e d 1 F e e...

Страница 39: ...der and chain feeder drop mode there is no choice of proximity switch since only one proximity switch is being used 4 This parameter allows you to specify if the bin containing the feed is empty If th...

Страница 40: ...42 3 This parameter is used to access the PROXIMITY SWITCH FILTERS screen page C 43 4 This parameter is used to access the FEEDER TIMER screen page C 44 5 This parameter is used to access the WAITING...

Страница 41: ...This setting varies in increments of 1 second from 0 to 300 seconds 2 This setting allows you to adjust the waiting time of the actuator This setting varies in increments of 1 second from 0 to 300 sec...

Страница 42: ...feed the system will rise to the feeder phase rather than canceling the cycle These parameters are adjustable in increments of 1 minute from 5 to 240 minutes 2 This parameter is used to choose the du...

Страница 43: ...me For the feeding phase to end the start filters need to be done In multi feed mode these time limits are reset for each feed auger of the cycle This setting can be adjusted in increments of 1 second...

Страница 44: ...EDER TIMER This screen is only accessible in multi feed chain feeder and chain feeder drop 1 These parameters allow you to adjust the feeder activation time during the feeder phase This timer can be s...

Страница 45: ...ed they are associated This setting is adjustable in increments of 1 second from 1 to 360 seconds 2 These parameters allow you to adjust the time of feed augers off period In the meantime the correspo...

Страница 46: ...ti feed mode 1 These parameters allow you to adjust the required time to allow the animals to empty their manger Each feed type has its waiting period These parameters are adjustable in increments of...

Страница 47: ...only available in multi feed mode 1 This parameter is used to adjust the time given the corresponding feeder to purge the left over During that time only the feeder assign to the current cycle is act...

Страница 48: ...n MAX TIME 2 2 These parameters are used to set the maximum run time of feed augers assigned to the corresponding feed When a feed auger runs continuously for a period exceeding its assigned feed limi...

Страница 49: ...hen a feed auger does not operate and it has a request for a period exceeding its assigned feed limit the alarm activates Besides if applicable the backup of the corresponding feed will be used instea...

Страница 50: ...to choose the cycle start times The cycles departure times must be in chronological order 4 In multi feed feed auger and feed auger drop mode these parameters are used to select which feed type will...

Страница 51: ...the setting is set to None the corresponding feed does not have a backup If the assigned feed auger engages its feeding time alarm multi feed mode or its minimum or maximum time the backup feed auger...

Страница 52: ...parameter allows the activation or the deactivation of the alarm relay when a feed auger alarm is occurring If this option is set to ON when a feed auger alarm situation occurs the alarm relay activa...

Страница 53: ...will appear When confirmation is positive the history will be cleared Clearing the alarm history will also reset all alarm counts and timers 2 These parameters indicate the date and time at which the...

Страница 54: ...assigned to the each relay A bin number is only display if the relay type is feed auger 5 These parameters are used to manually override the calculated activation demand by the regulator of each rela...

Страница 55: ...u g 3 F e e d 4 A u g 4 F e e d 3 A u g 5 F e e d 1 A u g 6 F e e d 2 A u g 7 F e e d 3 A u g 8 F e e d 3 MAIN MENU FEED SUMMARY 1 This parameter displays the program type 2 This parameter displays th...

Страница 56: ...ti Feed CF Chain Feeder FA Feed Auger CFD Chain Feeder Drop FAD Feed Auger Drop 5 This setting is used to access the screen INSTALLATION PROGRAM 1 4 page C 58 6 This parameter is used to access the DA...

Страница 57: ...en the RF NETWORK 8 is set to the same value as the RF ADDRESS 9 of the RF communication card of the controller designated as the network master ex WebGate in most installations Other controllers can...

Страница 58: ...INSTALLATION FEED AUGER PROGRAM 1 4 page C 60 4 This setting is used to access the screen PROXIMITY SWITCH INSTALLATION PROGRAM 1 4 page C 61 5 This setting is used to access the screen TRANSMISSION...

Страница 59: ...used to select the feeder relay for a program When the feeder receives an activation request the selected relay will be activated This parameter varies from 1 to 12 and when no relay is selected 3 Th...

Страница 60: ...uts for a program When a feed auger has an activation request the selected relay will be activated These settings vary from 1 to 12 and when no output is selected 4 These parameters show the presence...

Страница 61: ...2 These parameters are used to determine if the corresponding proximity switch contact is normally closed NC or normally open NO When a proximity switch is normally closed NC it shows full when there...

Страница 62: ...vary from 1 to 8 up to 16 with an 8 inputs board and when no input is selected 2 This parameter is used to determine if the transmission chain contact is normally closed NC or normally open NO When a...

Страница 63: ...n have values and 1 to 4 2 These parameters are used to choose on which couples of relay the actuators will be assigned If a potentiometer is assigned to the actuator the relay will be selected automa...

Страница 64: ...ording to the demand in percentage This parameter can be set from 0 00 to 59 59 minutes 3 This setting is used to deactivate or activate the alarm function for the actuator The alarm activates if this...

Страница 65: ...is completely open press SELECT when the cursor is on this setting At this point the text displayed here will change to High Limit Saved if the value was correctly saved Can t Save Check Pot if the v...

Страница 66: ...Unlocked To modify the current state press the SELECT button when cursor is positioned on Locked Unlocked and then enter the first alphanumerical digit Once the first value is entered press SELECT onc...

Страница 67: ...ed while the cursor is positioned on this parameter a confirmation question will appear and if the confirmation is positive the download will begin 2 This parameter is used to confirm a download of th...

Страница 68: ...tion from the controller to the MCHIP When the SELECT button is pressed while the cursor is on this parameter and the latter is adjusted to Y the upload will begin If the SELECT button is pressed whil...

Страница 69: ...ation persists contact your distributor Error Code 2 5 If one or more of these error codes appear contact your distributor Error Code 6 The MCHIP has remained in the socket for five or more minutes Ma...

Страница 70: ...position over 5 after its closing delay An actuator assigned to program in FAD or CFD mode has a position under 95 after its opening delay T r a n s C h a i n P The program transmission chain is activ...

Страница 71: ...GE NUTRI INDEX WARRANTY GE NUTRI Section D 71 INDEX WARRANTY GE NUTRI SECTION D...

Страница 72: ...ng 13 Connection procedure 14 Detailed wiring diagrams 14 Typical positioner wiring 14 Typical power backup wiring 15 Typical alarm connection wiring 16 Powering up procedure 17 Verify all connections...

Страница 73: ...eding Timers 42 Proximity Switch Filters 43 Feeder Timer 44 On Off Feeding Periods 45 Waiting Timer 46 Purge Timer 47 Max Time Alarms Prog 1 4 48 Min Time Alarms Prog 1 4 49 Cycles Program 1 4 50 Back...

Страница 74: ...rtuitous events acts of God flood fire hail or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer f...

Страница 75: ......

Страница 76: ...GE NUTRI VER 1 9 2 September 2020...

Отзывы: