b. Press the DSP/FUN key to display function number.
c. Press the
▲
or
▼
/RESET key until “F11” is displayed.
d. Press the DATA/ENT key. The function code will be displayed (factory
setting is “000” (Keypad]).
e. Press the
▲
or
▼
/RESET key until the desired setting is displayed. The
programmable codes for F11 are as follows.
f.
Press DSP/FUN key to return to the frequency display or press the
▲
or
▼
/RESET key to change to another function number.
5. F10 (Start/Stop Control) –
Start/Stop Control is used to set the drive for
keypad (factory setting) or external Start/Stop Control, as described in
Section IX, on page 42. F10 is factory set to “000” [Keypad].
WARNING!
The Stop contact is never to be used as a Safety Disconnect
since it is not fail-safe. Use only the AC line for this purpose.
To change the setting of F10 to External Contacts:
a. The drive must be in Stop Mode (press the RUN/STOP key).
b. Press the DSP/FUN key to display function number.
c. Press the
▲
or
▼
/RESET key until “F10” is displayed.
d. Press the DATA/ENT key. The function code setting will be displayed
(factory setting is “000” [Keypad]).
e. Press the
▲
or
▼
/RESET key until code “001” is displayed.
f.
Press DSP/FUN key to return to the frequency display or press the
▲
or
▼
/RESET key to change to another function number.
Notes: 1.
In order for the reverse function to operate, Function F22
must be set to “000” [Enable Reverse Run] (factory setting).
2.
The
STOP key on the keypad is always operative, even if F10 is set to “001”
[External Contacts].
6. F03 (External Forward-Stop-Reverse Control) –
External Forward-Stop-
Reverse Control is used to set the drive for either Forward/Stop-
Reverse/Stop (factory setting) or Run/Stop-Forward/Reverse, as described
in Section IX, on page 39.
F11 = 000:
Keypad (Factory Setting)
001:
Potentiometer, 0 - 10 V, 0 - 20 mA
002:
4 - 20 mA
!
Sec. VIII – Drive Operation (Cont.)
35