20
4.4 INITIAL CONFIGURATION
Select Voltage
• Before starting the unit, confirm power supply voltage and
circuit breaker.
• Confirm the voltage switch is on the correct voltage as
described in Section 3.
• Press the
ON
button (item 13), the unit switches on and the
display show
03
, with the
“RESET/SEL”
symbol flashing.
• Press the
“RESET/SEL”
button and then select the value on
the display to one of the four options shown below. Press
the
“DRAIN/ENT”
button to confirm.
OPTION VOLTAGE CURRENT OUTPUT OUTPUT OUTPUT
1
115 V
11 A
10.1 gpd 1.6 kg/h
3.5 lbs/hr
2
115 V
14.5 A
13.9 gpd 2.2 kg/h
4.9 lbs/hr
3
*
230 V
11 A
20.9 gpd 3.3 kg/h
7.3 lbs/hr
4
230 V
14.5 A
28.5 gpd 4.5 kg/h
9.9 lbs/hr
*
Default seeting if no selection is made
Tab. 4.b
• At the end of this initialization operation, a sequence of
characters will be shown on the display to indicate the
selected output and voltage, according to the following
scheme:
• CH + size (kg/h) + U + voltage (1 = 115V, 2 = 230V)
1. CH01U1 = 1.6 kg/h 115V
2. CH02U1 = 2.2 kg/h 115V
3. CH03U2 = 3.3 kg/h 230V
Default setting is Option
3 if no selection is made.
4. CH04U2 = 4.5 kg/h 230V
• If no selection is made within 10 seconds, the unit will
start using the default setting
Option 3
. The unit can be
config.d again the next time it is turned on.
• The unit can produce steam even if not config.d, but the
warning
‘EH’
will be shown on the display.
• If the incorrect selection has been made, please contact
customer service or follow the following procedure:
Units with revision 3.323 or lower:
1. Turn the humidifier off.
2. Press “
RESET
/
SEL + DRAIN/ENT
” buttons together and
turn the machine on.
3. The “
00set
” should be displayed.
4. Press “
RESET
/
SEL
” to increase the value to 12 and then
press “
DRAIN/ENT
”.
5. You are in the P4 parameter: Once again with “
RESET
/
SEL
” you can modify its value and with the “
DRAIN/ENT
”
button you can confirm.
6. If you selected the wrong parameter or value,
immediately turn the unit off and try again. It is critical
that other values are not changed because it may cause
the unit not to operate or operate incorrectly.
Units with revision 3.324 or higher:
1. Turn the humidifier off.
2. Press “
RESET
/
SEL
” button during the startup.
3. The voltage/capacity parameter is reset and the new
wizard will be displayed.
4. Press the
“RESET/SEL”
button and then select the value
on the display to one of the four options shown below.
Press the ‘
DRAIN/ENT
’ button to confirm.
• The yellow power LED comes on and steam unit is ready to
operate.
• The green LED ‘cloud’ will light up when the boiler electrodes
are powered on and creating steam.
4.5 NEW STEAM SYSTEM OR REPLACEMENT
STEAM CYLINDER
When starting with a new cylinder, you should activate the
cylinder cleaning function as follows:
1. Switch the 5500 Steam Humidifier off.
2. Press and hold both buttons,
“RESET/SEL”
and
“DRAIN/
ENTER”,
and switch the 5500 Steam Humidifier back on.
When the wrench blinks then release the two buttons.
3. Press and hold
“RESET/SEL”
until the display shows 04.
WARNING:
DO NOT confirm any value higher than
04.
If 05 or higher is displayed, press
“RESET/SEL”
until
the display goes back to the normal operating mode and
restart from step 1.
4. Press
“DRAIN/ENTER”
(minimum 1 second): the cleaning
starts and the display shows PC.
Содержание GeneralAire 5500
Страница 6: ...6...
Страница 37: ...31 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Страница 38: ...32 NOTES...
Страница 39: ...33 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Страница 41: ...35 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Страница 42: ...36...
Страница 43: ...37 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG Mode d emploi...
Страница 48: ...42...
Страница 79: ...31 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE...
Страница 81: ...33 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE NOTES...