Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. Please consult a Generac Power Systems Industrial
Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528 and DIN6271 standards.
POWER RATINGS (kW)
STARTING CAPABILITIES (sKVA)
FUEL
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
STANDBY
Three-Phase 120/208VAC @0.8pf
600 kW
Amps: 2081
Three-Phase 120/240VAC @0.8pf
600 kW
Amps: 1804
Three-Phase 277/480VAC @0.8pf
600 kW
Amps: 903
Three-Phase 346/600VAC @0.8pf
600 kW
Amps: 723
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
Alternator
kW
10%
15%
20%
25%
30%
35%
Standard
600
743
1114
1486
1857
2229
2600
Standard
600
543
814
1086
1357
1629
1900
Upsize 1
832
757
1136
1514
1893
2271
2650
Upsize 1
723
571
857
1143
1429
1714
2000
Upsize 2
-
-
-
-
-
-
-
Upsize 2
-
-
-
-
-
-
-
Fuel Consumption Rates*
STANDBY
Fuel Pump Lift - m (ft)
Percent Load
gph
lph
3.7 (12)
25%
18.4
69.7
50%
28.2
88.7
75%
35.6
134.8
100%
41.4
156.7
* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.
STANDBY
Coolant Flow per Minute
gpm (lpm)
114.1 (432)
Heat Rejection to Coolant
BTU/hr
1,589,760
Inlet Air
cfm (m3/min)
30,088 (852)
Max. Operating Radiator Air Temp
Fº (Cº)
122 (50)
Max. Operating Ambient Temperature
Fº (Cº)
104 (40)
Coolant System Capacity
gal (L)
13 (49)
Maximum Radiator Backpressure
in H
2
O
0.5
STANDBY
Flow at Rated Power
cfm (m3/min)
1836 (52)
STANDBY
Rated Engine Speed
rpm
1800
Horsepower at Rated kW**
hp
909
Piston Speed
ft/min
2161.4
BMEP
psi
361
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD
permitting purposes.
STANDBY
Exhaust Flow (Rated Output)
cfm (m
3
/min) 4980 (141)
Max. Backpressure (Post Silencer)
inHg (Kpa)
2.03 (6.9)
Exhaust Temp (Rated Output)
ºF (ºC) 1029 (554)
Exhaust Outlet Size (Open Set)
8"
3 of 4
SD600
operating data (60Hz)
600 kW Diesel