Operation

Automatic Transfer Switch Owner’s Manual

13

5.

Set generator MLCB to ON (CLOSED). Generator 
now  powers  all  LOAD  circuits.  Verify  generator 
operation under load as follows:

Turn  on  electrical  loads  to  the  full  rated  watt-
age/amperage capacity of generator. DO NOT

 

OVERLOAD.

With maximum rated load applied, check volt-
age  and  frequency  across  transfer  switch  ter-
minals  E1  and  E2.  Voltage  should  be  greater 
than  230  VAC  (240  VAC  system);  frequency 
should be greater than 59 Hz.

Verify fuel pressure remains within acceptable

 

parameters  (see  generator  installation  man-
ual).

Allow generator to run under rated load for at 
least 30 minutes. With unit running, inspect for 
unusual  noises,  vibration,  or  overheating  that 
might indicate a problem.

6.

Set  generator  MLCB  to  OFF  (OPEN)  when  test 
under load is complete.

7.

Allow generator to run at no-load for several min-
utes. Then, shut down generator by pressing OFF.

8.

Set main switch contacts to utility. 

NOTE: 

See 

Manual Operation

.  Handle  and  operating 

lever of transfer switch should be in down position.

9.

Set  utility  service  disconnect  circuit  breaker  of 
transfer switch to ON (CLOSED).

System is now set for fully automatic operation.

Checking Automatic Operation

Proceed as follows to check system for correct automatic 
operation:

1.

Verify generator is in OFF mode.

2.

Set utility service disconnect circuit breaker of the 
transfer switch to OFF (OPEN).

3.

Verify switch is de-energized.

4.

Install front cover of transfer switch.

5.

Set transfer switch utility service disconnect circuit 
breaker to ON (CLOSED).

6.

Set generator MLCB to ON.

7.

Select AUTO on generator control panel. System is 
now ready for automatic operation.

8.

Set transfer switch utility service disconnect circuit 
breaker to OFF (OPEN).

With  generator  ready  for  automatic  operation,  engine 
should crank and start when utility source power is turned 
off after a five second delay (factory default setting). After 
starting,  transfer  switch  should  connect  load  circuits  to

 

standby  side  after  a  five  second  delay. Allow  system  to
operate through entire automatic sequence of operation.

With generator running and loads powered by generator 
AC  output,  set  transfer  switch  utility  service  disconnect 
circuit breaker to ON (CLOSED). The following will occur:

After  approximately  15  seconds,  transfer  switch  will 
transfer loads to utility power source.

Approximately  one  minute  after  transfer,  generator 
should shut down.

With generator in AUTOMATIC mode, system is now set 
for fully automatic operation.

Installation Summary

1.

Verify installation has been performed correctly as 
outlined  by  the manufacturer  and  that  it  meets  all 
applicable laws and codes.

2.

Test and verify correct operation of the system as 
outlined in the appropriate installation and owner’s 
manuals.

3.

Educate  end-user  on  correct  operation,  mainte-
nance, and service call procedures. 

NOTE: 

The utility power circuit breaker in transfer switch

 

must be turned OFF to simulate a utility outage. Shutting 
off main disconnect in a subpanel connected to transfer 
switch will NOT simulate an outage. 

Shutting Generator Down While 

Under Load

IMPORTANT NOTE: To avoid equipment damage, fol-
low these steps, in order, when shutting the genera-
tor  down  during  utility  outages.  Shutdowns  may  be

 

required  during  outages  to  perform  routine  mainte-
nance or to conserve fuel.

To  turn  generator  OFF  (while  running  in AUTO  and

 

online):

1.

Turn main utility disconnect off.

2.

Turn  generator  MLCB  (generator  disconnect)  to 
OFF (OPEN).

3.

Run  generator  for  approximately  one  minute  to

 

cool down.

4.

Turn generator OFF.

To turn generator back ON:

1.

Put  generator  into  AUTO  mode.  Start  generator 
and warm-up for a few minutes.

2.

Set  MLCB  (generator  disconnect)  to  ON

 

(CLOSED).

The system now operates in AUTO mode. The main util-
ity disconnect can be turned ON (CLOSED). To shut unit 
off, repeat this complete process.

Содержание RXGW20SHA3

Страница 1: ...el Number RXGW20SHA3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product suppo...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...Manual Operation 11 Close to Utility Source Side 11 Close to Generator Source Side 12 Return to Utility Source Side 12 Voltage Checks 12 Utility Voltage Checks 12 Generator Voltage Checks 12 Generato...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...anufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WA...

Страница 6: ...warning could result in death or serious injury WARNING Equipment damage This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply in the event...

Страница 7: ...ements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductors are tightened to the factory specified torque value Failure to do so...

Страница 8: ...Safety Rules General Information 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...Install transfer switch as close as possible to electrical loads that will be connected to it Mount transfer switch vertically to a rigid supporting structure Level all mount ing points to prevent tr...

Страница 10: ...Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and local codes It is the responsibility of the ins...

Страница 11: ...used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe away any excess corrosion inhibitor Tighten terminal lugs to required torque values as noted on decal locate...

Страница 12: ...4 12V N1 N2 T1 Replace with Littlefuse 021606 3MXHP Generac 10000005117 250 vac 6 3A 23TRANSFER 1 1 1 1 2 2 2 2 J T1 N2 0 194 23A N1 004435 A Thermostat 1 B Air conditioner 1 C Thermostat 2 D Air cond...

Страница 13: ...ch manual operating handle The 2017 NEC requires the short circuit current rating of the trans fer equipment based on type of overcurrent protective device protecting transfer equipment be field marke...

Страница 14: ...Installation 10 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 15: ...g narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in UP position LOAD terminals T1 T2 are connected to util ity ter...

Страница 16: ...art 2 Allow generator to stabilize and warm up at no load for at least five minutes 3 Set generator s main circuit breaker CB1 to ON CLOSED 4 Verify no load voltage and frequency with an accurate AC v...

Страница 17: ...when utility source power is turned off after a five second delay factory default setting After starting transfer switch should connect load circuits to standby side after a five second delay Allow sy...

Страница 18: ...M 4 Verify all of the connected loads to be shed are disabled 5 After five minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status...

Страница 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Section 4 Drawings and Diagrams Installation Drawing No 10000047450...

Страница 20: ...Drawings and Diagrams 16 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000047283 Page 1 of 4 Liquid Cooled Engine Generator...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 No 10000047283 Page 2 of 4 Liquid Cooled Engine Generator...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual No 10000047283 Page 3 of 4 Air Cooled Engine Generator...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 No 10000047283 Page 4 of 4 Air Cooled Engine Generator...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 This page intentionally left blank...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 27: ......

Страница 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: