Installation

6

Automatic Transfer Switch Owner’s Manual

Installing Breakers

See 

Figure 2-2

. Insert tab on each breaker (A) into the

 

hook on the bus (B). Push breaker into bus until it snaps 
into place.

Figure 2-2.  Install Breakers

NOTE: 

The following 1 in circuit breaker manufacturers 

are  permitted  to  be  installed:  Siemens,  Murray,  Eaton 
BR, and Square D Homeline.

Installing Branch Circuit Conductors

1.

Install correctly sized branch circuit conductors into 
transfer switch. Knockouts can be made in the field 
as needed.

2.

Connect  ungrounded  branch  circuit  conductors 
(hot conductors) to a correctly sized circuit breaker 
approved for use with the transfer switch.

3.

Terminate  neutral  conductor  and  equipment 
grounding  conductor  of  the  branch  circuit  at  neu-
tral/equipment ground terminal bars. 

4.

Size all conductors, raceways, conduits, and junc-
tion boxes, if required, to the applicable NEC code

 

articles  and  follow  NEC  installation  requirements 
for wiring method(s) selected.

NOTE: 

Multi-wire  branch  circuits  must  be  installed  in 

accordance with NEC Article 210.4. 

Connecting Power Source and 

Generator Power Supply

Installation and interconnection diagrams are provided in

 

this manual. 

NOTE: 

All installations must comply with national, state, 

and local codes. It is the responsibility of the installer to 
perform  an  installation  that  will  pass  final  electrical 
inspection.

1.

Connect  utility  supply  at  utility  service  disconnect 
circuit breaker terminals N1 and N2. Utility supply 
lugs  are  equipped  with  the  2017/2020  NEC

 

required  finger  safe  barriers. These  barriers  must 
remain in place after installation.

2.

Connect  utility  neutral  conductor  to  grounded  ter-
minal  bar.  Neutral/grounding  conductor  terminal 
bars are bonded together and to the transfer switch

 

enclosure through the use of a green main bonding 
jumper screw.

3.

Connect  loads  to  integrated  load  center  with  cus-
tomer-supplied circuit breakers.

4.

See 

Figure 2-1

 and 

Figure 2-3

. Connect generator 

to generator terminals (E1 and E2) on the transfer 
mechanism. 

000362

B

A

Electrocution. Turn utility and emergency
power supplies to OFF before connecting 
power source and load lines. Failure to do so 
will result in death or serious injury.

 

(000116)

DANGER

(000120)

CAUTION

Equipment damage. Verify all conductors are
tightened to the factory specified torque value.
Failure to do so could result in damage to the 
switch base.

Содержание RXGW20SHA3

Страница 1: ...el Number RXGW20SHA3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product suppo...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...Manual Operation 11 Close to Utility Source Side 11 Close to Generator Source Side 12 Return to Utility Source Side 12 Voltage Checks 12 Utility Voltage Checks 12 Generator Voltage Checks 12 Generato...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...anufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WA...

Страница 6: ...warning could result in death or serious injury WARNING Equipment damage This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply in the event...

Страница 7: ...ements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductors are tightened to the factory specified torque value Failure to do so...

Страница 8: ...Safety Rules General Information 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...Install transfer switch as close as possible to electrical loads that will be connected to it Mount transfer switch vertically to a rigid supporting structure Level all mount ing points to prevent tr...

Страница 10: ...Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and local codes It is the responsibility of the ins...

Страница 11: ...used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe away any excess corrosion inhibitor Tighten terminal lugs to required torque values as noted on decal locate...

Страница 12: ...4 12V N1 N2 T1 Replace with Littlefuse 021606 3MXHP Generac 10000005117 250 vac 6 3A 23TRANSFER 1 1 1 1 2 2 2 2 J T1 N2 0 194 23A N1 004435 A Thermostat 1 B Air conditioner 1 C Thermostat 2 D Air cond...

Страница 13: ...ch manual operating handle The 2017 NEC requires the short circuit current rating of the trans fer equipment based on type of overcurrent protective device protecting transfer equipment be field marke...

Страница 14: ...Installation 10 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 15: ...g narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in UP position LOAD terminals T1 T2 are connected to util ity ter...

Страница 16: ...art 2 Allow generator to stabilize and warm up at no load for at least five minutes 3 Set generator s main circuit breaker CB1 to ON CLOSED 4 Verify no load voltage and frequency with an accurate AC v...

Страница 17: ...when utility source power is turned off after a five second delay factory default setting After starting transfer switch should connect load circuits to standby side after a five second delay Allow sy...

Страница 18: ...M 4 Verify all of the connected loads to be shed are disabled 5 After five minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status...

Страница 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Section 4 Drawings and Diagrams Installation Drawing No 10000047450...

Страница 20: ...Drawings and Diagrams 16 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000047283 Page 1 of 4 Liquid Cooled Engine Generator...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 No 10000047283 Page 2 of 4 Liquid Cooled Engine Generator...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual No 10000047283 Page 3 of 4 Air Cooled Engine Generator...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 No 10000047283 Page 4 of 4 Air Cooled Engine Generator...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 This page intentionally left blank...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 27: ......

Страница 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: