Installation

Automatic Transfer Switch Owner’s Manual

7

Figure 2-3. Wiring Connections

5.

Connect generator neutral wire to top neutral lug or 
side lugs on the panel board.

6.

Connect neutral conductors to the lugs and termi-
nals along the neutral/ground bars in panel board

 

section of transfer switch.

7.

Connect  a  maximum  200A  subpanel  feeder  to 
lower T1 and T2 connections. Connect feeder neu-
tral  and  equipment  grounding  conductors  to  the 
neutral/grounding  terminal  bar  in  the  transfer 
switch.

8.

Connect  grounding  electrode  conductors  to  neu-
tral/ground terminal bars in panel board portion of 
transfer switch.

NOTE: 

A  neutral  to  equipment  ground  main  bonding 

screw  (A)  is  provided  for  use  where  transfer  switch  is 
installed as service equipment.

Conductor  sizes must  be adequate to  handle maximum

 

current they will be subjected to, based on the 75 °C col-
umn  of  tables,  charts,  etc.  used  to  size  conductors. 
Installation  must  fully  comply  with  all  applicable  codes, 
standards, and regulations.

All  power  cables  can  enter  enclosure  through  provided

 

knockouts. Additional knockouts into transfer switch can 
be made in the field as needed. Conduit entry shall main-
tain  correct  wire  bending  spaces  required  by  Tables 
312.6  (A)  and  (B)  in  the  NEC.  Conduits  should  be

 

arranged to provide separation between utility and gener-
ator supply conductors inside the enclosure.

NOTE: 

If aluminum conductors are used, apply corrosion

 

inhibitor  to  conductors.  After  tightening  terminal  lugs, 
carefully wipe away any excess corrosion inhibitor.

Tighten terminal lugs to required torque values as noted 
on decal located on the inside of the door. After tighten-
ing terminal lugs, carefully wipe away any excess corro-
sion inhibitor. 

Connecting Start Circuit Wires

Control  system  interconnections  consist  of  N1,  N2,  and 
T1, and leads 23, 194, and 9 (ground). The connections 
are color coded on the load shed to match connections in 
the Generac genset. Generac Type TC-ER-JP tray cable 
includes  power  cables  with  all  necessary  color-coded 
control  wiring.  It  is  suitable  for  direct  burial,  overhead, 
and indoor wiring.

NOTE: 

See Article 336 in the 2017 and 2020 editions of 

the NEC for more information on the installation require-
ments for Type TC-ER-JP cable.

The generator control wiring is a Class 1 signaling circuit. 
See  instruction  manual  of  specific  engine  generator  for 
wiring  connection  details.  Recommended  wire  gauge 
sizes  for  this  wiring  depends  on  wire  length,  as  recom-
mended in the following chart:

 

Exception: 

Conductors  of  AC  and  DC  circuits,  rated 

1000 volts nominal or less, shall be permitted to occupy 
the  same  equipment,  cable,  or  conduit.  All  conductors 
shall have an insulation rating equal to at least the maxi-
mum  circuit  voltage  applied  to  any  conductor  within  the

 

equipment, cable, or conduit. See NEC 300.3(C)(1).

N2

004982a

N1

E1

E2

A

T1

T2

Maximum Wire Length

Recommended Wire Size

1–115 ft (1–35 m)

No. 18 AWG

116–185 ft (36–56 m)

No. 16 AWG

186–295 ft (57–89 m)

No. 14 AWG

296–460 ft (90–140 m)

No. 12 AWG

Содержание RXGW20SHA3

Страница 1: ...el Number RXGW20SHA3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product suppo...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...Manual Operation 11 Close to Utility Source Side 11 Close to Generator Source Side 12 Return to Utility Source Side 12 Voltage Checks 12 Utility Voltage Checks 12 Generator Voltage Checks 12 Generato...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...anufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WA...

Страница 6: ...warning could result in death or serious injury WARNING Equipment damage This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply in the event...

Страница 7: ...ements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductors are tightened to the factory specified torque value Failure to do so...

Страница 8: ...Safety Rules General Information 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...Install transfer switch as close as possible to electrical loads that will be connected to it Mount transfer switch vertically to a rigid supporting structure Level all mount ing points to prevent tr...

Страница 10: ...Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and local codes It is the responsibility of the ins...

Страница 11: ...used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe away any excess corrosion inhibitor Tighten terminal lugs to required torque values as noted on decal locate...

Страница 12: ...4 12V N1 N2 T1 Replace with Littlefuse 021606 3MXHP Generac 10000005117 250 vac 6 3A 23TRANSFER 1 1 1 1 2 2 2 2 J T1 N2 0 194 23A N1 004435 A Thermostat 1 B Air conditioner 1 C Thermostat 2 D Air cond...

Страница 13: ...ch manual operating handle The 2017 NEC requires the short circuit current rating of the trans fer equipment based on type of overcurrent protective device protecting transfer equipment be field marke...

Страница 14: ...Installation 10 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 15: ...g narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in UP position LOAD terminals T1 T2 are connected to util ity ter...

Страница 16: ...art 2 Allow generator to stabilize and warm up at no load for at least five minutes 3 Set generator s main circuit breaker CB1 to ON CLOSED 4 Verify no load voltage and frequency with an accurate AC v...

Страница 17: ...when utility source power is turned off after a five second delay factory default setting After starting transfer switch should connect load circuits to standby side after a five second delay Allow sy...

Страница 18: ...M 4 Verify all of the connected loads to be shed are disabled 5 After five minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status...

Страница 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Section 4 Drawings and Diagrams Installation Drawing No 10000047450...

Страница 20: ...Drawings and Diagrams 16 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000047283 Page 1 of 4 Liquid Cooled Engine Generator...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 No 10000047283 Page 2 of 4 Liquid Cooled Engine Generator...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual No 10000047283 Page 3 of 4 Air Cooled Engine Generator...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 No 10000047283 Page 4 of 4 Air Cooled Engine Generator...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 This page intentionally left blank...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 27: ......

Страница 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: