Generac Power Systems RXGW20SHA3 Скачать руководство пользователя страница 15

Operation

Automatic Transfer Switch Owner’s Manual

11

Section 3: Operation

Functional Tests and Adjustments

Following transfer switch installation and interconnection, 
inspect entire installation carefully. A competent, qualified 
electrician  should  inspect  it.  The  installation  should 
strictly comply with all applicable codes, standards, and

 

regulations.  When  absolutely  certain  installation  is  cor-
rect, complete a functional test of the system. 

IMPORTANT  NOTE:  Before  proceeding  with  func-
tional tests, read and verify all instructions and infor-
mation  in  this  section  is  understood.  Also  read

 

information  and  instructions  of  labels  and  decals

 

affixed to transfer switch. Note any options or acces-
sories that might be installed and review their opera-
tion.

Manual Operation

See 

Figure 3-1

. A manual handle (B) is shipped with the

 

transfer  switch  manual.  Manual  operation  must  be  veri-
fied BEFORE transfer switch is operated electrically. Pro-
ceed as follows to verify manual operation:

1.

Verify generator is in OFF mode.

2.

Turn  off  both  utility  (service  disconnect  circuit 
breaker)  and  emergency  (generator  main  line  cir-
cuit breaker) power supplies to transfer switch.

3.

Note position of transfer mechanism main contacts 
(A) by observing the movable contact carrier arm. 
This can be viewed through the long narrow slot in

 

the  inside  cover.  The  top  of  the  movable  contact 
carrier arm is yellow to be easily identified.

Manual  operation  handle  in  UP  position—
LOAD terminals (T1, T2) are connected to util-
ity terminals (N1, N2).

Manual  operation  handle  in  DOWN  position–
LOAD  terminals  (T1,  T2)  are  connected  to 
EMERGENCY terminals (E1, E2).

Close to Utility Source Side

Before  proceeding,  verify  position  of  transfer  switch  by 
observing position of manual operation handle in 

Figure 

3-1

.  If  manual  operation  handle  is  UP,  contacts  are 

closed  in  utility  (normal)  position.  No  further  action  is 
required. If manual operation handle is DOWN, proceed 
with Step 1.

1.

With  manual  operation  handle  inserted  into  mov-
able contact carrier arm, move handle UP. Hold on 
to manual operation handle as it will move quickly 
after the center of travel.

2.

Remove  manual  operating  handle  from  movable

 

contact carrier arm. Return manual operation han-
dle to storage bracket.

Figure 3-1. Manual Operation

(000121)

CAUTION

Equipment damage. Perform functional tests in the 
exact order they are presented in the manual. 
Failure to do so could result in equipment damage.

 

(000132)

DANGER

Electrocution. Do not manually transfer under load. 
Disconnect transfer switch from all power sources 
prior to manual transfer. Failure to do so will result in 
death or serious injury, and equipment damage.

(000122)

CAUTION

Equipment damage. Do not use excessive force while 
manually operating the transfer switch. Doing so could 
result in equipment damage.

 

B

009339

A

Содержание RXGW20SHA3

Страница 1: ...el Number RXGW20SHA3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product suppo...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...Manual Operation 11 Close to Utility Source Side 11 Close to Generator Source Side 12 Return to Utility Source Side 12 Voltage Checks 12 Utility Voltage Checks 12 Generator Voltage Checks 12 Generato...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...anufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WA...

Страница 6: ...warning could result in death or serious injury WARNING Equipment damage This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply in the event...

Страница 7: ...ements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductors are tightened to the factory specified torque value Failure to do so...

Страница 8: ...Safety Rules General Information 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...Install transfer switch as close as possible to electrical loads that will be connected to it Mount transfer switch vertically to a rigid supporting structure Level all mount ing points to prevent tr...

Страница 10: ...Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and local codes It is the responsibility of the ins...

Страница 11: ...used apply corrosion inhibitor to conductors After tightening terminal lugs carefully wipe away any excess corrosion inhibitor Tighten terminal lugs to required torque values as noted on decal locate...

Страница 12: ...4 12V N1 N2 T1 Replace with Littlefuse 021606 3MXHP Generac 10000005117 250 vac 6 3A 23TRANSFER 1 1 1 1 2 2 2 2 J T1 N2 0 194 23A N1 004435 A Thermostat 1 B Air conditioner 1 C Thermostat 2 D Air cond...

Страница 13: ...ch manual operating handle The 2017 NEC requires the short circuit current rating of the trans fer equipment based on type of overcurrent protective device protecting transfer equipment be field marke...

Страница 14: ...Installation 10 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 15: ...g narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in UP position LOAD terminals T1 T2 are connected to util ity ter...

Страница 16: ...art 2 Allow generator to stabilize and warm up at no load for at least five minutes 3 Set generator s main circuit breaker CB1 to ON CLOSED 4 Verify no load voltage and frequency with an accurate AC v...

Страница 17: ...when utility source power is turned off after a five second delay factory default setting After starting transfer switch should connect load circuits to standby side after a five second delay Allow sy...

Страница 18: ...M 4 Verify all of the connected loads to be shed are disabled 5 After five minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status...

Страница 19: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 15 Section 4 Drawings and Diagrams Installation Drawing No 10000047450...

Страница 20: ...Drawings and Diagrams 16 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000047283 Page 1 of 4 Liquid Cooled Engine Generator...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 No 10000047283 Page 2 of 4 Liquid Cooled Engine Generator...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual No 10000047283 Page 3 of 4 Air Cooled Engine Generator...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 No 10000047283 Page 4 of 4 Air Cooled Engine Generator...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 This page intentionally left blank...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 27: ......

Страница 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: