![Generac Power Systems R-200 Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/generac-power-systems/r-200/r-200_technical-manual_2208974005.webp)
3
Figure 1 — Dip Switch Settings
RL1
U9
J2
J3
J5
J4
U7
J1
2
3
4
5
7
8
6
1
ON
DATE XXXX
SOFTWARE P/N
REV #
DIP SWITCH
6 CYL
LOW SPD
8
5
6
7
4
3
LP
4 CYL
2.4 - 45kW / 3.0L
NORMAL
NG
POS
1
2
OFF
ATS
GTS
ON
RESERVED
RESERVED
# OF CYLINDERS
FUEL TYPE
ENGINE TYPE / kW RATING
EXERCISE MODE
RESERVED
TRANSFER SWITCH MODE
DESCRIPTION
2.4 - 35kW
If the DIP switch settings are not set correctly,
the generator engine may run rough, not start
or not provide rated power. When LP fuel
is used it is very important that DIP Switch
Position 4 be in the LP fuel position (switch
OFF).
LED Indicators visible through front panel (see Table
1 and Figure 2).
Table 1
System Ready
Green LED
Low Fuel Pressure
Yellow LED
Low Battery
Red LED
Low Oil Pressure
Red LED
Hi Coolant Temp/Low Coolant Level
Red LED
Over Speed/RPM Sensor Loss
Red LED
Over Crank
Red LED
Figure 2 — LED Indicators on Front Panel
OVERCRANK
OVER
S
PEED
LOW COOLANT LEVEL
HI COOLANT TEMPERATURE
LOW OIL PRE
SS
URE
LOW BATTERY
LOW FUEL PRE
SS
URE
S
Y
S
TEM READY
•
•
•
•
•
•
•
General Information
R-panel Technical Manual