RPM SIGNAL FAILURE (FLASHING RED 
OVERSPEED INDICATOR)

If the R-200 controller does not receive a signal 
from the engine crank or flywheel sensor, the R-200 
controller cannot maintain the generator output fre-
quency or monitor for an overspeed condition. If this 
signal is lost the R-200 controller will shut down the 
engine as follows:

RPM SIGNAL FAILURE DURING CRANKING

The engine control board (R-200 controller) will 
monitor the engine speed signal during engine crank-
ing. If the control board does not see a valid signal 
within the first four seconds of each crank cycle it 
will stop the crank cycle, lock out on a shut down 
fault and flash the overspeed LED.

RPM SIGNAL FAILURE DURING RUNNING

Running mode is handled differently because there 
is always the possibility the engine could slow down 
or stop running due to a temporary overload. To 
avoid shutting down and latching out on a temporary 
problem the following is done. If the engine is up and 
running, and the control board stops receiving a valid 
engine speed input signal it will respond as follows:

1.  It will close the throttle.
2.  It will shut down the engine by turning off the fuel 

supply.

3.  It will wait for 15 seconds to ensure the engine 

has stopped.

4.  It will then energize the starter and monitor the 

engine speed signal.

A.  If the control board does not see the engine 

speed signal it will stop the crank cycle, lock out 
on fault, and flash the overspeed LED.

B.  If the control board does see the engine speed 

input signal during cranking it will start and run 
the engine normally. If the engine speed signal is 
again lost while running it will repeat the above 
procedure one more time.

C.  If the failure should repeat a third time, the con-

trol board will shut down the engine, lock out on 
fault, and flash the over speed LED.

OVERCRANK (RED LED INDICATOR)

Occurs if the engine has not started within the total 
90 second crank cycle. This is a latched fault and will 
shut down the engine.

‹

‹

INVALID DIP SWITCH SETTING
(ALL RED LED’S ON)

All five (5) RED LED’s on the front panel will be ON 
all the time if DIP switch position 5 and DIP switch 
position 6 are not set correctly.

ALARM CANCEL

When the generator is shut down on a latched fault or 
latching alarm, the AUTO/OFF/MANUAL switch must 
be set to the OFF position to turn off the correspond-
ing fault LED. Prior to moving the switch to the OFF 
position, record which LEDs are ON or FLASHING 
and the date on the back cover of this manual.

AUTOMATIC TRANSFER SWITCH (ATS 
MODE)

When this generator, along with an RTS-type or HS-
type automatic transfer switch has been installed and 
connected, a circuit board in the generator control 
panel constantly monitors the utility voltage and con-
trols the operation of the transfer switch.

To implement this mode of operation, Position 2 of 
the eight-position DIP switch, which is located on the 
generator circuit board (see Figure 1), must be in the 
OFF position. In ATS Mode utility voltage sensing, 
weekly exercising, and load transferring is under the 
control of the generator.

Should the utility voltage drop below a preset value, 
and remain at this low voltage for a preset amount 
of time, the generator cranks and starts. After the 
generator starts, the transfer switch transfers the 
load circuits to the generator so the generator can 
power them. When the utility source voltage has been 
restored, the transfer switch re-transfers the load 
circuits back to the utility source voltage and the gen-
erator shuts down.

The transfer switch is controlled by the generator 
circuit board via control wires 23 and 194. Wire 23 
connects the collector of an NPN transistor on the 
generator circuit board to the “low side” (Terminal 
23) of the transfer relay coil in the transfer switch. 
Wire 194 connects positive battery voltage from the 
generator circuit board to the “high side” (Terminal 
194) of the transfer relay coil in the transfer switch.

In order for the generator utility voltage sensing 
function to work, it is necessary to provide a 5 amp 
fused 240VAC for 240V or 480V systems or 208VAC 
utility source connection (depending on the generator 
being used) from the transfer switch main N1 and N2 
terminals to the generator wiring panel N1 and N2 
terminals (See Figure 2).

General Information

R-panel Technical Manual

Содержание R-200

Страница 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200 Digital Controller A new standard of reliability ...

Страница 2: ...s and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical device while standing in water while barefoot or while hands or feet are wet DANGEROUS ELECTRICAL SHOCK MAY RESULT If people must stand on metal or concrete while installing operating servicing adjus...

Страница 3: ...ed High Coolant Temp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indicator 8 Invalid Cylinder Dip Switch Setting All Red LED s On 8 Alarm Cancel 8 Automatic Transfer Switch ATS Mode 8 Engineered Transfer Switch 2 wire Start GTS Mode 9 Voltage Regulator ...

Страница 4: ...ing see Figure 1 To activate the DIP Switch settings place the AUTO OFF MANUAL switch in the OFF Mode make the DIP switch changes and then push and hold the Set Exercise Switch for five seconds DIP Switch Position 1 Reserved for future use The position of this DIP Switch does not affect generator operation DIP Switch Position 2 Selects the type of transfer switch to be used with the generator When...

Страница 5: ...tart or not provide rated power When LP fuel is used it is very important that DIP Switch Position 4 be in the LP fuel position switch OFF LED Indicators visible through front panel see Table 1 and Figure 2 Table 1 System Ready Green LED Low Fuel Pressure Yellow LED Low Battery Red LED Low Oil Pressure Red LED Hi Coolant Temp Low Coolant Level Red LED Over Speed RPM Sensor Loss Red LED Over Crank ...

Страница 6: ...down due OFF X ON O O To Low Oil Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X O O 60 of Nominal 1 sec rate Unit Shutdown due OFF X Flashing O O To Low Coolant Level Engine Speed Signal OFF X Flashing O O Fault RPM Signal Loss Control Board is Fla...

Страница 7: ...gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer expires the R 200 controller will transfer the load to the generator ATS Mode The transfer of load when the generator is running is dependent upon the operating conditions as follows MANUAL MODE The unit will not transfer if the utility is present will...

Страница 8: ... will stop flashing the indi vidual fault LED will turn on and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode has not yet been set LOW SPEED EXERCISE To select this mode place DIP switch position 3 in the OFF position In Low Speed Exercise mode the 2 4...

Страница 9: ... visual LED warning only and does not trigger the controller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200 controller continually monitors the bat tery voltage and turns on the low battery LED if the battery voltage falls below approximately 12 2VDC for one minute A low battery voltage is a non lat...

Страница 10: ...front panel will be ON all the time if DIP switch position 5 and DIP switch position 6 are not set correctly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch must be set to the OFF position to turn off the correspond ing fault LED Prior to moving the switch to the OFF position record which LEDs are ON or FLASHING and the date on the back ...

Страница 11: ... NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator control board will NOT activate the transfer output The generator control board WILL monitor all engine conditions and shut down on all the faults listed in this document For the W Type transfer switch to...

Страница 12: ...tch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via a relay contact closure in the W type transfer switch the control board will start and run the generator When the 2 wire start wire connection is opened the control board will stop the generator When the control board is in AUTO MANUA...

Страница 13: ...act in W type transfer switch 5 Momentary Open Switch Input B 6 2 wire Start Return from relay contact in W type transfer switch 7 Manual Auto Input BS 8 19 5VAC Utility Sense Input 9 Alarm Relay Driver Output minimum coil resistance is 90 ohms 10 Transfer Relay Driver Output minimum coil resistance is 60 ohms 11 Manual Input 12 19 5VAC Utility Sense Return 13 Reserved Do not connect any wires to ...

Страница 14: ...on Such an explosion can shat ter the battery and cause blindness or other injury Any area that houses a storage battery must be properly ventilated Do not allow smok ing open flame sparks or any spark producing tools or equipment near the battery Battery electrolyte fluid is an extremely corro sive sulfuric acid solution that can cause severe burns Do not permit fluid to contact eyes skin clothin...

Страница 15: ... Undervoltage Shutdown typ 11 Volts LED Indicators AC Line Voltage 108Vac Green LED ON Battery Connected Charging Yellow LED ON the Green LED must be ON to obtain a valid battery charging indication Yellow LED ON if charge current approx 2 Amps Battery Current Drain AC Power OFF 30mA typ AC Line Connections via terminal block AC Hot AC Neut GND Battery Connections via terminal block Pos Neg Contro...

Страница 16: ...Part No 0F9784 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision B 06 07 06 Printed in U S A ...

Отзывы: