Electrical Connections
Installation Manual for Generac PWRCell Inverter
23
Table 5-10. CT Setpoints
Setpoint
Behavior
Default
Units
CalOverride
•
Overrides CT calibration.
•
When set to OFF, the inverter detects the CTs number and direction of
CTs.
•
A value of ON assumes a specific orientation and direction of CTs.
OFF
N/A
CTTurnsRatio
•
Turns ratio of the CTs installed.
•
Default turns ratio of 1,500 is compatible with included clamp type CTs
•
If installation restriction requires larger accessory CTs, set point shall be
adjusted to 3,000. Verify turn ratio of CTs before modifying this setting.
1,500
Turns
Table 5-11. Automatic Detection Troubleshooting Table
Event Name
Event Code Description
Possible Solution
ct cal = 1
0x8061
Line 1 doesn’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 2
0x8062
Line 2 doesn’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 3
0x8063
Line 1 & 2 don’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 4
0x8064
Line 3 doesn’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 5
0x8065
Line 1 & 3 don’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 6
0x8066
Line 2 & 3 don’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 7
0x8067
Line 1 & 2 & 3 don’t have a valid CT calibration
Check wiring and CT integrity
ct cal = 9
0x8069
Line 1 has multiple CTs on it (or a CT is on the
neutral wire)
Check wiring and CT integrity
ct cal = A
0x806A
Line 2 has multiple CTs on it (or a CT is on the
neutral wire)
Check wiring and CT integrity
ct cal = B
0x806B
Lines 1 and 2 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Check wiring and CT integrity
ct cal = C
0x806C
Line 3 has multiple CTs on it (or a CT is on the
neutral wire)
Check wiring and CT integrity
ct cal = D
0x806D
Lines 1 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Check wiring and CT integrity
ct cal = E
0x806E
Lines 2 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Check wiring and CT integrity
ct cal = F
0x806F
Lines 1 & 2 & 3 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Check wiring and CT integrity
ct cal success
0x8070
Calibration was successful
Check wiring and CT integrity