Commissioning
Installation and Owner’s Manual for Generac PWRCell Inverter
39
ance standard from the menu at the bottom of the
page. Click Submit to apply the compliance stan
-
dard. The settings entered will not take effect until
the Submit button has been clicked.
Figure 6-28. Utility Compliance Configuration
NOTE:
Verify the Compliance Selection field shows the
desired compliance rule after clicking Submit.
NOTE:
For multi-system sites, compliance must be set
on each inverter separately through each respective Bea
-
con.
Proof of Compliance
See
. The Compliance PDF validates
whether the system has been set up to conform to a util
-
ity compliance ruleset. Please double check that the sys
-
tem is configured properly by observing the ‘In
compliance with’ line in the PDF. If the utility requires
proof of correct configuration, save this PDF and send it
to the utility. It is recommend to keep a copy on file as
well.
1.
To generate a proof of compliance PDF, click on
the Compliance PDF tab in the navigation menu.
2.
Click on Download Report.
3.
A new window will open in the browser with the
report. Verify the information is correct and save
the document or send via email.
Figure 6-29. Proof of Compliance
Set Import / Export Compliance
(optional)
By default, all Generac PWRcell Inverters ship without
restrictions on import and export. Utility interconnection
requirements may require the system to restrict or limit its
ability to import or export power from or to the Utility grid.
There are two PCS CRD200-compliant settings for PWR
-
cell equipment: Zero Import and Export Limit.
NOTE:
These settings are only available for inverter
firmware version 13290 or greater. See
a firmware update, please call 1-855-395-7841.
NOTE:
Import / Export compliance settings rely upon
proper CT functionality. Ensure CTs placement is correct
for the system configuration, and ensure CTs are cali
-
brated and functioning. See
Zero Import
(CRD200 Export Only compliance): allows the battery to
export power to a connected utility grid but will not allow
the battery to be charged from the utility grid. In Zero
Import, the battery will only be charged by connected DC
PV power sources.
NOTE:
Zero Import is one-time settable. Once set, some
utilities may require the request to unset this setting to
come from the utility. To unset Zero Import, please con
-
tact Generac PWRcell Technical Support.
How to set:
1.
Navigate to the inverter device page.
2.
Disable inverter if enabled.
3.
Access the Installer Configuration Tool through the
REbus Beacon. See
4.
Once logged onto the Installer Configuration Tool,
select “Inverter.”
010983
010984