Operation
Owner’s Manual for MLT6SMDS - MLT6SKDS Light Tower
31
Light Operation (Key Switch
Models)
1.
Verify the unit is ON and running smoothly.
2.
See
. Switch main circuit breaker (A)
ON (I).
3.
Switch light circuit breaker (B) ON (I).
Figure 3-11. Light Switches and Breaker
Light Operation (Power Zone–
DLA) (If Equipped)
See
. The lights are turned on and off using
the Power Zone–DLA. To view the light screen, press the
↑ button three times from the Home screen.
NOTE:
The lights can only be turned ON and OFF while
the unit is running in MANUAL mode. They operate
automatically in AUTO mode.
NOTE:
The light tower can only be run with all four
fixtures ON. The upper left light controls all four lights ON
and OFF.
1.
Once the engine is up to temperature and running
smoothly, switch the main circuit breaker ON (I).
2.
To turn the light(s) ON, press the Select (
) button.
To turn the light(s) OFF, press the Select (
)
button.
Figure 3-12. Lights Screen
Engine Derating
All units are subject to derating for altitude and
temperature. Derating reduces the available power for
operating tools and accessories connected to the
receptacles. For every increase in 1,000 ft (305 m) of
elevation, engine performance for this unit typically drops
between 2–4%. Also, engine performance decreases
about 1% for every 10 °F (5.6 ºC) increase in ambient air
temperature over 72 ºF (22 ºC).
Wet Stacking
The unit is powered by a diesel engine. Diesel engines
are subject to “wet stacking” if lightly loaded. Wet
stacking occurs when an engine is run at less than 30%
of its full load capacity, causing unburned fuel to
accumulate in the exhaust system. Wet stacking can be
detected by continuous black exhaust when the unit is
under a constant load. It can also cause fouling of
injectors and buildup on engine valves. Diesel engines
operate properly when applied loads are between 30–
100% capacity. Appropriate generator sizing is
determined by the anticipated load. If the unit is in a wet
stack condition, load the unit heavily for five hours or until
the exhaust is clear.
(000277)
WARNING
Burn hazard. Never operate lights with a
damaged or missing lens cover. Lamps are
hot and pressurized while in use. Unprotected
lamps can shatter, causing severe injury.
008712
A
B
002327
Содержание MAGNUM MLT6SKDS
Страница 46: ...Maintenance 42 Owner s Manual for MLT6SMDS MLT6SKDS Light Tower This page intentionally left blank...
Страница 52: ...Wiring Diagrams 48 Owner s Manual for MLT6SMDS MLT6SKDS Light Tower AC Wiring Diagram MLT6SKDS With Power Zone...
Страница 65: ...Service Log Owner s Manual for MLT6SMDS MLT6SKDS Light Tower 61 This page intentionally left blank...
Страница 66: ...Service Log 62 Owner s Manual for MLT6SMDS MLT6SKDS Light Tower This page intentionally left blank...
Страница 67: ......