Section 2 — Installation

HTS “Wn” Type Transfer Switch

NOTE:

Unless otherwise specified, a NEUTRAL block is not supplied 

with the transfer switch on single phase, 3-pole units where the 

NEUTRAL line is to be switched during transfer action. Similarly, 

a NEUTRAL block is not supplied on 3-phase, 4-pole units where 

the NEUTRAL line is to be switched during transfer.

Solderless, screw-type terminal lugs are standard. Conductor 

sizes must be adequate to handle the maximum current to which 

they will be subjected. The installation must comply fully with all 

applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove any surface 

oxides from the cable ends with wire brush. If ALUMINUM conduc-

tors are used, apply joint compound. Tighten terminal lugs to the 

torque values in the following chart.

SWITCH RATING

WIRE SIZE

TORQUE RATING

600 AMP

500MCM-1/0

375 INCH-LBS

800/1000 AMP

500MCM-1/0

375 INCH-LBS

1200/2600 AMP

750MCM-1/0

500 INCH-LBS

All power cables should enter the switch next to transfer mecha-

nism terminals. Standard terminal lugs on the transfer mechanism 

are solderless, screw-type.
Be sure to maintain proper electrical clearance between live metal 

parts and grounded metal. Allow at least one inch for circuits over 

400 amps.

2.5  

CONNECTING CONTROLLER 
COMMUNICATION WIRES

Use shielded 2-wire communications cable (such as Belden 

#9460) to make the communications line connection from the 

HTS transfer switch to the engine generator connection panel. 

This cable is to be routed in a separate conduit between the HTS 

transfer switch and the engine generator. The cable is to be con-

nected as follows:
HTS transfer switch - 4 position terminal block, in the bottom of 

the transfer switch enclosure (labeled "comm. Ports").
Engine generator - terminal strip in connection panel that houses 

the circuit breaker. Do not connect the shield at this end.

2.6  SETTING DIP SWITCHES

The dip switches, in the HTS, 

are read once, only at power up

. If 

the communications to the Power Manager or the engine controller 

are working, it will overwrite the dip switch settings. In this way 

there are no conflicts and also the transfer switch will use the latest 

settings even if the communications fail.

2.6.1   DIP SWITCH 1

 

‹

Voltage Codes

THREE PHASE DIP SWITCH SELECTED
 

Code 

Dip1_3 2 1

 

0 = 480 Vac 

0 0 0

 

1 = 600 Vac 

0 0 1

 

2 = 415 Vac 

0 1 0

 

3 = 240 Vac 

0 1 1

 

4 = 220 Vac 

1 0 0

 

5 = 208 Vac 

1 0 1

 

6 = 480 Vac (spare) 

1 1 0

 

7 = 480 Vac (spare) 

1 1 1

All voltages listed, are Line - Line and all three phases are 

checked.
SINGLE PHASE DIP SWITCH SELECTED
  Code 

Dip1  3 2 1

  0 = xxx vac 

0 0 0

  1 = xxx vac 

0 0 1

  2 = xxx vac 

0 1 0

  3 = 240 vac 

0 1 1

  4 = 220 vac 

1 0 0 (usually 50Hz)

  5 = xxx vac 

1 0 1

  6 = xxx vac 

1 1 0

  7 = xxx vac 

1 1 1

All voltages are expressed as line - line, but checked as line - neu-

tral, line - neutral and line - line.
As of the V1.8 software release, there will only be one PCB for all 

voltage codes.

 TDN/INPHASE - Dip1- switch 4:  Set this switch to ON to select 

• 

TDN type transfers.

CTTS/OTTS - Dip1 - switch 5:  Set this switch to OFF for a OTTS 

• 

type transfer switch.

THREE PHASE - Dip1 - switch 6:  Set this switch to ON for 3 

• 

phase wiring. Set this switch to OFF for single-phase wiring.

MODBUS ADDRESS - Dip1- switches 7,8:  The base Modbus 

• 

address for the transfer switch is set at 240. The transfer switch 

will NOT respond to the universal address 250. By changing the 

address dip switches, the full range of available addresses for 

transfer switches is:

  

 

GenLink 

DCP

  Modbus address 

Dip1 - 8  7 

Switch Number

 

240 

0  0 

1

 

241 

0  1 

2

 

242 

1  0 

3

 

243 

1  1 

4

Содержание HTS Wn

Страница 1: ...Owner s Manual HTS Wn Type Automatic Transfer Switch 600 through 2600 Amp 600 Volts This manual should remain with the unit...

Страница 2: ...C generator that is used for backup power if a NORMAL UTILITY power source failure occurs must be isolated from the NORMAL UTILITY power source by means of an approved transfer switch Failure to prope...

Страница 3: ...L SHOCK MAY RESULT Because jewelry conducts electricity wearing it may cause dangerous electrical shock Remove all jewelry such as rings watches bracelets etc before working on this equipment If work...

Страница 4: ...d or is substantially reduced and the STANDBY source voltage and frequency have reached an acceptable level The transfer switch prevents electrical feedback between two different power sources such as...

Страница 5: ...enLink via PC RS485 Remote Annunciator Slave 1 5 OPERATION WITH LOSS OF COMMUNICATIONS Local control means that if the generator is running and there is no utility the switch will then transfer to the...

Страница 6: ...r switch as close as possible to the electrical loads that are to be connected to it Stand the enclosure on a flat surface If the surface is not flat it will be necessary to add shims to make the encl...

Страница 7: ...sfer switch 4 position terminal block in the bottom of the transfer switch enclosure labeled comm Ports Engine generator terminal strip in connection panel that houses the circuit breaker Do not conne...

Страница 8: ...mable limits If the communication link to the transfer switch breaks down the following criteria are used for a local determination Dropout any phase outside 70 to 130 of nominal not the average volta...

Страница 9: ...d means such as a main circuit breaker s A manual HANDLE is shipped with the transfer switch Manual operation must be checked BEFORE the transfer switch is operated electrically To check manual operat...

Страница 10: ...etc During the voltage checks the transfer switch is electrically ener gized Perform voltage checks as follows 1 Inside the transfer switch enclosure set the Maintenance Disconnect switch to MANUAL 2...

Страница 11: ...e switch enclosure set the Maintenance Disconnect switch to AUTOMATIC 5 Press the TEST button on the enclosure door Generator startup and transfer to the STANDBY power source should occur Refer to the...

Страница 12: ...ut on J1 17 for curtailment The pin needs to be cycled to start the test and also cycled to stop the test 3 7 6 FAST TEST BUTTON The Fast Test button will only operate if the communications link is ac...

Страница 13: ...SEQUENCE 7 RETURN TO UTILITY TIMER Return to Utility timer starts The Utility source voltage must stay above the pickup level If the Utility voltage falls below the pickup value the Return to Utility...

Страница 14: ...37 and 238 are closed These dry contacts can be connected to via a terminal strip located on the bottom of the subplate Reference wiring diagram 0F5520 or 0F5036 for further details The customer conne...

Страница 15: ...additional lubrication should be required The service technician should lubricate all recommended points whenever major transfer mechanism components are replaced Use only specified greases to lubrica...

Страница 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...

Страница 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...

Страница 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 32: ...30 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 33: ...31 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 36: ...34 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 37: ...35 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 38: ...36 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 1 Parts List on page 38...

Страница 39: ...37 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 2 Parts List on page 38...

Страница 40: ...SW 800A 3P WN600V 072118 1 XFRSW 800A 4P WN600V 072113 1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLS...

Страница 41: ...39 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 1 Parts List on page 41...

Страница 42: ...40 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 2 Parts List on page 41...

Страница 43: ...1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLSS 500 4 0X17 32 AL CU 44 074349A 2 SW CVR WN 600A 3P 0...

Страница 44: ...42 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 1 Parts List on page 44...

Страница 45: ...43 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 2 Parts List on page 44...

Страница 46: ...XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 072124 1 XFRSW 12...

Страница 47: ...45 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 1 Parts List on page 47...

Страница 48: ...46 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 2 Parts List on page 47...

Страница 49: ...AL SIGNAL BEFORE XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 0...

Страница 50: ...48 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 1 Parts List on page 50...

Страница 51: ...49 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 2 Parts List on page 50...

Страница 52: ...L 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 072122 1 XFRSW 2600A 4...

Страница 53: ...51 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 1 Parts List on page 53...

Страница 54: ...52 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 2 Parts List on page 53...

Страница 55: ...457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 0721...

Страница 56: ...s of normal maintenance i e tune ups associated part s adjustments loose leaking clamps installation and start up 3 Any failure caused by contaminated fuels oils coolants antifreeze or lack of proper...

Отзывы: