3.7.1   SYSTEM READY LED

 

‹

The "System Ready LED" is lit if the Gxxx or Hxxx panel is in Auto, 

there are no transfer errors (excluding comm's error or fail to 

synch), and the Maintenance Disconnect Switch is in AUTO. If the 

comm's are bad then the system ready light will flash but the sys-

tem will still function with local control. Under all circumstances, if 

the Generator is not in the AUTO position, the switch controller will 

locally close the switch to Utility power if it is available.

3.7.2   STANDBY OPERATING LED

 

‹

This LED will light when the Generator is running. This is deter-

mined by the Generator frequency being between 20 and 80 Hz. 

This LED will flash along with the Utility Available LED to indicate 

a "fail to sync" condition.

3.7.3   SWITCH POSITION LED'S

 

‹

The transfer switch position is monitored by two auxiliary contacts 

mounted on the transfer switch mechanism. These LED's display 

the position of the main contacts.
If there is a transfer switch error (fail to close or open) the appro-

priate Led will flash. In the case of an OTTS switch, both LED's 

will flash.

3.7.4   UTILITY AVAILABLE LED

 

‹

This LED indicates that Utility voltage is present but does not 

indicate that it is within the tolerances set by the H panel (as this 

is determined in the H panel). It does indicate that Utility voltage is 

within 70-130% of nominal.
This led will flash along with the standby operating led to indicate 

a "fail to sync" condition.

3.7.5    TEST SWITCH AND CURTAILMENT INPUT

 

‹

The Test switch will only operate if the communications link is 

active, also the generator must be stopped, i.e., not in minimum 

run or cooldown.
Pressing the switch will cause the generator controller to com-

mand a transfer to standby using all the pre-programmed timers 

and settings. The unit will transfer back to utility after the switch is 

pressed again and the "return to utility" timer expires. Pressing the 

"return to normal" switch will force this timer to expire and the unit 

to return to the utility position. The switch can also be "mimicked" 

via a digital input on (J1-17) for curtailment. The pin needs to be 

cycled to start the test and also cycled to stop the test.

3.7.6   FAST TEST BUTTON

 

‹

The Fast Test button will only operate if the communications link 

is active. Pressing the button will cause the Generator controller to 

command a transfer to STANDBY using all the standard settings 

but with reduced time delays. Specifically the following timers are 

reduced to 1 second:

Line Interrupt Delay timer

• 

Engine Warmup timer

• 

Engine Minimum Run timer

• 

Engine Cooldown timer

• 

Return to Utility timer

• 
NOT affected are:

Signal Before Transfer timer

• 

Time Delay Neutral timer

• 
The unit will initiate a transfer back to Utility after 5 seconds of the 

transfer mechanism in the Standby position.

3.7.7   RETURN TO NORMAL SWITCH

 

‹

This switch will abort the Return to Utility timer and cause the 

system to return to Utility operation (assuming the Utility source is 

good). It will not operate if the Communications link is bad.

3.7.8    MAINTENANCE DISCONNECT SWITCH (AUTO/

 

‹

MANUAL)

In the Manual position, the transfer switch is physically isolated 

from the signals that tell it to operate, the transfer mechanism will 

not change state in the Manual position. This position should be 

used when manually operating the transfer switch mechanism. In 

the Auto position, the transfer switch is operated by the switch 

controller. For automatic operation the switch should be left in the 

Auto position.

3.8  SEQUENCE OF OPERATION

When acceptable Utility source voltage is available, the Maintenance 

Disconnect switch is in AUTO and the communication link to the 

generator is good, observe the following:

Utility Available LED, on front of door, is ON.

• 

Utility Switch Position LED, on front of door, is ON.

• 

System Ready LED, on front of door, is ON.

• 

3.8.1    SEQUENCE 1 - UTILITY VOLTAGE DROPOUT

 

‹

Utility Voltage goes outside of the value set in the generator 

• 

control panel (range is 5-25 Vrms of nominal voltage, factory 

default setting is +/- 25 Vrms). If the communication link is not 

good the ATS controller will take control and the range is 70 to 

130% of the nominal voltage selected with a 5 second utility 

loss timer and a 30 second utility return timer.

Voltage dropout triggers sequence 2.

• 

Section 3 — Operation

HTS “Wn” Type Transfer Switch

Содержание HTS Wn

Страница 1: ...Owner s Manual HTS Wn Type Automatic Transfer Switch 600 through 2600 Amp 600 Volts This manual should remain with the unit...

Страница 2: ...C generator that is used for backup power if a NORMAL UTILITY power source failure occurs must be isolated from the NORMAL UTILITY power source by means of an approved transfer switch Failure to prope...

Страница 3: ...L SHOCK MAY RESULT Because jewelry conducts electricity wearing it may cause dangerous electrical shock Remove all jewelry such as rings watches bracelets etc before working on this equipment If work...

Страница 4: ...d or is substantially reduced and the STANDBY source voltage and frequency have reached an acceptable level The transfer switch prevents electrical feedback between two different power sources such as...

Страница 5: ...enLink via PC RS485 Remote Annunciator Slave 1 5 OPERATION WITH LOSS OF COMMUNICATIONS Local control means that if the generator is running and there is no utility the switch will then transfer to the...

Страница 6: ...r switch as close as possible to the electrical loads that are to be connected to it Stand the enclosure on a flat surface If the surface is not flat it will be necessary to add shims to make the encl...

Страница 7: ...sfer switch 4 position terminal block in the bottom of the transfer switch enclosure labeled comm Ports Engine generator terminal strip in connection panel that houses the circuit breaker Do not conne...

Страница 8: ...mable limits If the communication link to the transfer switch breaks down the following criteria are used for a local determination Dropout any phase outside 70 to 130 of nominal not the average volta...

Страница 9: ...d means such as a main circuit breaker s A manual HANDLE is shipped with the transfer switch Manual operation must be checked BEFORE the transfer switch is operated electrically To check manual operat...

Страница 10: ...etc During the voltage checks the transfer switch is electrically ener gized Perform voltage checks as follows 1 Inside the transfer switch enclosure set the Maintenance Disconnect switch to MANUAL 2...

Страница 11: ...e switch enclosure set the Maintenance Disconnect switch to AUTOMATIC 5 Press the TEST button on the enclosure door Generator startup and transfer to the STANDBY power source should occur Refer to the...

Страница 12: ...ut on J1 17 for curtailment The pin needs to be cycled to start the test and also cycled to stop the test 3 7 6 FAST TEST BUTTON The Fast Test button will only operate if the communications link is ac...

Страница 13: ...SEQUENCE 7 RETURN TO UTILITY TIMER Return to Utility timer starts The Utility source voltage must stay above the pickup level If the Utility voltage falls below the pickup value the Return to Utility...

Страница 14: ...37 and 238 are closed These dry contacts can be connected to via a terminal strip located on the bottom of the subplate Reference wiring diagram 0F5520 or 0F5036 for further details The customer conne...

Страница 15: ...additional lubrication should be required The service technician should lubricate all recommended points whenever major transfer mechanism components are replaced Use only specified greases to lubrica...

Страница 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...

Страница 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...

Страница 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 32: ...30 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 33: ...31 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 36: ...34 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 37: ...35 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 38: ...36 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 1 Parts List on page 38...

Страница 39: ...37 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 2 Parts List on page 38...

Страница 40: ...SW 800A 3P WN600V 072118 1 XFRSW 800A 4P WN600V 072113 1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLS...

Страница 41: ...39 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 1 Parts List on page 41...

Страница 42: ...40 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 2 Parts List on page 41...

Страница 43: ...1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLSS 500 4 0X17 32 AL CU 44 074349A 2 SW CVR WN 600A 3P 0...

Страница 44: ...42 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 1 Parts List on page 44...

Страница 45: ...43 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 2 Parts List on page 44...

Страница 46: ...XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 072124 1 XFRSW 12...

Страница 47: ...45 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 1 Parts List on page 47...

Страница 48: ...46 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 2 Parts List on page 47...

Страница 49: ...AL SIGNAL BEFORE XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 0...

Страница 50: ...48 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 1 Parts List on page 50...

Страница 51: ...49 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 2 Parts List on page 50...

Страница 52: ...L 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 072122 1 XFRSW 2600A 4...

Страница 53: ...51 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 1 Parts List on page 53...

Страница 54: ...52 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 2 Parts List on page 53...

Страница 55: ...457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 0721...

Страница 56: ...s of normal maintenance i e tune ups associated part s adjustments loose leaking clamps installation and start up 3 Any failure caused by contaminated fuels oils coolants antifreeze or lack of proper...

Отзывы: