3.8.2    SEQUENCE 2 - LINE INTERRUPT DELAY

 

‹

Line interrupt Delay can be set between 0 and 60 seconds. 

• 

Factory default setting is 2 seconds.

If voltage dropout lasts longer than the Line Interrupt Delay set-

• 

ting, the generator start sequence will start.

Once the Generator voltage reaches Load Accept Voltage and 

• 

Load Accept Frequency this will trigger Sequence 3.

3.8.3    SEQUENCE 3 - ENGINE MINIMUM RUN AND 

 

‹

ENGINE WARMUP TIMERS

Engine Minimum Run timer starts. The Engine Minimum Run 

• 

timer can be set from 5 to 30 minutes. Factory default setting 

is 5 minutes.

Engine Warmup timer starts. The Engine Warmup timer can 

• 

be set from 0 to 1,200 seconds. Factory default setting varies 

depending on the engine used.

Standby Operating LED, on front of door, is ON.

• 

The expiration of the Engine Warmup timer triggers sequence 

• 

4.

3.8.4    SEQUENCE 4 - SIGNAL BEFORE TRANSFER

 

‹

Signal Before Transfer timer does not operate in a Utility Fail 

• 

sequence.

Sequence 5 starts immediately.

• 

3.8.5    SEQUENCE 5 - ATS TRANSFER TO GENERATOR 

 

‹

POSITION

ATS transfer mechanism operates to connect the Customer 

• 

Load to the Generator supply. Customer Load will be supplied 

from the Generator until sequence 6 is initiated.

Generator Switch Position LED, on front of door, is ON.

• 

3.8.6    SEQUENCE 6 - UTILITY VOLTAGE PICKUP

 

‹

The ATS controller continues to monitor the Utility source volt-

• 

age. When the Utility voltage is above the voltage dropout set-

ting plus the hysteresis value, sequence 7 will be initiated.

3.8.7    SEQUENCE 7 - RETURN TO UTILITY TIMER

 

‹

Return to Utility timer starts. The Utility source voltage must 

• 

stay above the pickup level. If the Utility voltage falls below the 

pickup value, the Return to Utility timer is reset. The Return to 

Utility timer can be set from 1 to 30 minutes. Factory default 

setting is 1 minute.

The expiration of the Return to Utility timer triggers sequence 

• 

8.

3.8.8    SEQUENCE 8 - SIGNAL BEFORE TRANSFER

 

‹

Signal Before Transfer timer starts. The Signal Before Transfer 

• 

relay is energized for the duration of the timer. The Signal Before 

Transfer timer can be set from 0 to 30 seconds. Factory default 

setting is 2 seconds.

The expiration of the Signal Before Transfer timer triggers 

• 

sequence 9.

3.8.9    SEQUENCE 9 - ATS TRANSFER TO UTILITY 

 

‹

POSITION

ATS transfer mechanism operates to connect the Customer 

• 

Load to the Utility supply. Customer Load will be supplied from 

the Utility.

The connection of the Customer Load to the Utility source trig-

• 

gers sequence 10.

Utility Switch Position LED, on front of door, is ON.

• 

Section 3 — Operation

HTS “Wn” Type Transfer Switch

Summary of Parameters

 Parameter 

Range 

Default 

value

 

Utility voltage deviation 

0 - 25 Vrms 

+/- 25 Vrms

 

Line Interrupt delay 

0 - 60 seconds 

2 seconds

 

Minimum Run timer 

5 - 30 minutes 

5 minutes

 

Engine warmup timer 

0 - 1,200 seconds 

Engine dependent

 

Load Accept Voltage 

85 - 95% of nominal 

90% of nominal

 

Load Accept Frequency 

85 - 95% of nominal 

95% of nominal

 

Signal Before Transfer timer 

0 - 30 seconds 

2 seconds

 

Time Delay Neutral timer 

0 - 10 seconds 

2 seconds

 

Utility Voltage Hysteresis 

2 - 25 Vrms 

10 Vrms

 

Return to Utility timer 

1 - 30 minutes 

1 minute

 

Engine Cooldown timer 

0 - 1,200 seconds 

Engine dependent

Содержание HTS Wn

Страница 1: ...Owner s Manual HTS Wn Type Automatic Transfer Switch 600 through 2600 Amp 600 Volts This manual should remain with the unit...

Страница 2: ...C generator that is used for backup power if a NORMAL UTILITY power source failure occurs must be isolated from the NORMAL UTILITY power source by means of an approved transfer switch Failure to prope...

Страница 3: ...L SHOCK MAY RESULT Because jewelry conducts electricity wearing it may cause dangerous electrical shock Remove all jewelry such as rings watches bracelets etc before working on this equipment If work...

Страница 4: ...d or is substantially reduced and the STANDBY source voltage and frequency have reached an acceptable level The transfer switch prevents electrical feedback between two different power sources such as...

Страница 5: ...enLink via PC RS485 Remote Annunciator Slave 1 5 OPERATION WITH LOSS OF COMMUNICATIONS Local control means that if the generator is running and there is no utility the switch will then transfer to the...

Страница 6: ...r switch as close as possible to the electrical loads that are to be connected to it Stand the enclosure on a flat surface If the surface is not flat it will be necessary to add shims to make the encl...

Страница 7: ...sfer switch 4 position terminal block in the bottom of the transfer switch enclosure labeled comm Ports Engine generator terminal strip in connection panel that houses the circuit breaker Do not conne...

Страница 8: ...mable limits If the communication link to the transfer switch breaks down the following criteria are used for a local determination Dropout any phase outside 70 to 130 of nominal not the average volta...

Страница 9: ...d means such as a main circuit breaker s A manual HANDLE is shipped with the transfer switch Manual operation must be checked BEFORE the transfer switch is operated electrically To check manual operat...

Страница 10: ...etc During the voltage checks the transfer switch is electrically ener gized Perform voltage checks as follows 1 Inside the transfer switch enclosure set the Maintenance Disconnect switch to MANUAL 2...

Страница 11: ...e switch enclosure set the Maintenance Disconnect switch to AUTOMATIC 5 Press the TEST button on the enclosure door Generator startup and transfer to the STANDBY power source should occur Refer to the...

Страница 12: ...ut on J1 17 for curtailment The pin needs to be cycled to start the test and also cycled to stop the test 3 7 6 FAST TEST BUTTON The Fast Test button will only operate if the communications link is ac...

Страница 13: ...SEQUENCE 7 RETURN TO UTILITY TIMER Return to Utility timer starts The Utility source voltage must stay above the pickup level If the Utility voltage falls below the pickup value the Return to Utility...

Страница 14: ...37 and 238 are closed These dry contacts can be connected to via a terminal strip located on the bottom of the subplate Reference wiring diagram 0F5520 or 0F5036 for further details The customer conne...

Страница 15: ...additional lubrication should be required The service technician should lubricate all recommended points whenever major transfer mechanism components are replaced Use only specified greases to lubrica...

Страница 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...

Страница 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...

Страница 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 32: ...30 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 33: ...31 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 36: ...34 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 37: ...35 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 38: ...36 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 1 Parts List on page 38...

Страница 39: ...37 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 2 Parts List on page 38...

Страница 40: ...SW 800A 3P WN600V 072118 1 XFRSW 800A 4P WN600V 072113 1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLS...

Страница 41: ...39 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 1 Parts List on page 41...

Страница 42: ...40 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 2 Parts List on page 41...

Страница 43: ...1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLSS 500 4 0X17 32 AL CU 44 074349A 2 SW CVR WN 600A 3P 0...

Страница 44: ...42 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 1 Parts List on page 44...

Страница 45: ...43 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 2 Parts List on page 44...

Страница 46: ...XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 072124 1 XFRSW 12...

Страница 47: ...45 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 1 Parts List on page 47...

Страница 48: ...46 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 2 Parts List on page 47...

Страница 49: ...AL SIGNAL BEFORE XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 0...

Страница 50: ...48 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 1 Parts List on page 50...

Страница 51: ...49 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 2 Parts List on page 50...

Страница 52: ...L 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 072122 1 XFRSW 2600A 4...

Страница 53: ...51 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 1 Parts List on page 53...

Страница 54: ...52 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 2 Parts List on page 53...

Страница 55: ...457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 0721...

Страница 56: ...s of normal maintenance i e tune ups associated part s adjustments loose leaking clamps installation and start up 3 Any failure caused by contaminated fuels oils coolants antifreeze or lack of proper...

Отзывы: