 2 

Section 1 — General Information

HTS “Wn” Type Transfer Switch

1.1   INTRODUCTION

This manual has been prepared especially for the purpose of famil-

iarizing personnel with the design, application, installation, opera-

tion and servicing of the applicable equipment. Read the manual 

carefully and comply with all instructions. This will help to prevent 

accidents or damage to equipment that might otherwise be caused 

by carelessness, incorrect application, or improper procedures.
Every effort has been expended to make sure that the contents 

of this manual are both accurate and current. The manufacturer 

reserves the right to change, alter or otherwise improve the prod-

uct at any time without prior notice.

1.2   EQUIPMENT DESCRIPTION

The commercial transfer switch range (HTS) is designed to oper-

ate in conjunction with the Power Manager Gxxx and Hxxx series 

of Generator controllers. The transfer switch has a simple 2-wire 

communications link to the Generator controller and can thus be 

mounted remote from the Generator. 
Utility voltage is monitored by the HTS and fed back to the engine 

generator control panel for comparison against setpoints, used to 

determine if the Utility voltage is "good".
Operation of the switch is instigated by the generator control 

panel, however, all aspects of TDN timing or inphase transfer are 

handled locally at the HTS. The HTS monitors a single phase of the 

Generator voltage in order to perform inphase transfers.
All timers and voltage setpoints are programmable in the G/H 

control panel. Some of the decisions are made by the HTS itself 

so the appropriate parameters are passed to the HTS via the com-

munication link. If the communication link were to break, the HTS 

will still function. It will monitor the Utility and Generator voltages 

and make the transfer determination itself, rather than being com-

manded by the generator control panel. It will either use the last 

parameters sent, or, if no parameters were ever sent (communica-

tions were never established), it will take its settings from onboard 

DIP Switches and a set of resident parameters.
The automatic transfer switch is used for transferring critical elec-

trical load from a NORMAL (UTILITY) power source to a STANDBY 

(EMERGENCY) power source. Such a transfer of electrical loads 

occurs automatically when the NORMAL power source has failed 

or is substantially reduced and the STANDBY source voltage and 

frequency have reached an acceptable level. The transfer switch 

prevents electrical feedback between two different power sources 

(such as the NORMAL and STANDBY sources) and, for that rea-

son, codes require it in all standby electric system installations.

1.3  

TRANSIENT VOLTAGE SURGE 
SUPPRESSION

The Transient Voltage Surge Suppression (TVSS) is provided to 

protect the load from electrical surges and/or transient voltage 

spikes. This device is physically located on the side wall of the 

enclosure. It is electrically connected to the load side of the trans-

fer switch. A 30 amp circuit breaker is provided to disconnect the 

TVSS from the transfer switch for maintenance or replacement.

The TVSS is made up of multiple solid state Metal Oxide Varistors 

(MOV) connected in parallel for each mode of protection. These 

devices are equipped with integrated short circuit and individual 

component level fusing. They are self-resetting and fully auto-

matic.

1.3.1   MODES OF PROTECTION

 

‹

The TVSS provides protection on all modes:

Single-phase (6) - L-L, L-N, L-N, L-G, L-G and N-G.

• 

Three-phase (10) - L-L, L-L, L-L, L-N, L-N, L-N, 

• 

L-G, L-G, L-G and N-G.

1.3.2   RATINGS

 

‹

Surge Capacity: 88 kA per mode.

• 

1.3.3   CERTIFICATION

 

‹

The TVSS is UL recognized to the requirements of UL 1449 2nd 

edition.

1.3.4   TVSS DISCONNECT

 

‹

Each TVSS is provided with a disconnect. The disconnect is a 30 

amp circuit breaker, 2-pole for single-phase and 3-pole for three-

phase. This is to allow replacement of the TVSS module without 

interruption of the electrical supply to the load.

DANGER

  REPLACEMENT OF THE TVSS MODULE WHILE 

THE ATS IS ENERGIZED SHOULD ONLY BE 

PERFORMED BY A QUALIFIED ELECTRICIAN. 

  BE SURE TO TURN ON TVSS DISCONNECT 

CIRCUIT BREAKER WHEN THE PROCEDURE IS 

COMPLETE. IF THE CIRCUIT BREAKER IS NOT 

TURNED ON THE TVSS MODULE WILL NOT 

PROVIDE ANY SURGE PROTECTION FOR THE 

CUSTOMER LOAD.

1.3.5   STATUS INDICATORS

 

‹

Each TVSS module has comprehensive, solid state, continual 

visual status monitoring of each protection mode present. There 

are two LED’s provided, located on the cover of the module. The 

GREEN LED (left side) is used to indicate that the TVSS module is 

energized and in working order. The RED LED (right side) will turn 

on in the event the suppressor capability is exceeded or if there is 

an internal safety component activating.
When the power is first applied, the unit does a brief internal diag-

nostic test. During this test, the RED LED will illuminate briefly, go 

off and then the GREEN LED will illuminate.

Содержание HTS Wn

Страница 1: ...Owner s Manual HTS Wn Type Automatic Transfer Switch 600 through 2600 Amp 600 Volts This manual should remain with the unit...

Страница 2: ...C generator that is used for backup power if a NORMAL UTILITY power source failure occurs must be isolated from the NORMAL UTILITY power source by means of an approved transfer switch Failure to prope...

Страница 3: ...L SHOCK MAY RESULT Because jewelry conducts electricity wearing it may cause dangerous electrical shock Remove all jewelry such as rings watches bracelets etc before working on this equipment If work...

Страница 4: ...d or is substantially reduced and the STANDBY source voltage and frequency have reached an acceptable level The transfer switch prevents electrical feedback between two different power sources such as...

Страница 5: ...enLink via PC RS485 Remote Annunciator Slave 1 5 OPERATION WITH LOSS OF COMMUNICATIONS Local control means that if the generator is running and there is no utility the switch will then transfer to the...

Страница 6: ...r switch as close as possible to the electrical loads that are to be connected to it Stand the enclosure on a flat surface If the surface is not flat it will be necessary to add shims to make the encl...

Страница 7: ...sfer switch 4 position terminal block in the bottom of the transfer switch enclosure labeled comm Ports Engine generator terminal strip in connection panel that houses the circuit breaker Do not conne...

Страница 8: ...mable limits If the communication link to the transfer switch breaks down the following criteria are used for a local determination Dropout any phase outside 70 to 130 of nominal not the average volta...

Страница 9: ...d means such as a main circuit breaker s A manual HANDLE is shipped with the transfer switch Manual operation must be checked BEFORE the transfer switch is operated electrically To check manual operat...

Страница 10: ...etc During the voltage checks the transfer switch is electrically ener gized Perform voltage checks as follows 1 Inside the transfer switch enclosure set the Maintenance Disconnect switch to MANUAL 2...

Страница 11: ...e switch enclosure set the Maintenance Disconnect switch to AUTOMATIC 5 Press the TEST button on the enclosure door Generator startup and transfer to the STANDBY power source should occur Refer to the...

Страница 12: ...ut on J1 17 for curtailment The pin needs to be cycled to start the test and also cycled to stop the test 3 7 6 FAST TEST BUTTON The Fast Test button will only operate if the communications link is ac...

Страница 13: ...SEQUENCE 7 RETURN TO UTILITY TIMER Return to Utility timer starts The Utility source voltage must stay above the pickup level If the Utility voltage falls below the pickup value the Return to Utility...

Страница 14: ...37 and 238 are closed These dry contacts can be connected to via a terminal strip located on the bottom of the subplate Reference wiring diagram 0F5520 or 0F5036 for further details The customer conne...

Страница 15: ...additional lubrication should be required The service technician should lubricate all recommended points whenever major transfer mechanism components are replaced Use only specified greases to lubrica...

Страница 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...

Страница 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...

Страница 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...

Страница 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...

Страница 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...

Страница 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...

Страница 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...

Страница 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...

Страница 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...

Страница 32: ...30 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 33: ...31 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 208 240V Drawing No 0F7042 B...

Страница 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...

Страница 36: ...34 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 37: ...35 Section 7 Wiring Diagrams Electrical Schematics Electrical Schematic 480 600V Drawing No 0F7044 B...

Страница 38: ...36 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 1 Parts List on page 38...

Страница 39: ...37 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F6446 D Page 2 Parts List on page 38...

Страница 40: ...SW 800A 3P WN600V 072118 1 XFRSW 800A 4P WN600V 072113 1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLS...

Страница 41: ...39 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 1 Parts List on page 41...

Страница 42: ...40 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7313 D Page 2 Parts List on page 41...

Страница 43: ...1 XFRSW1000A 3P WN600V 072119 1 XFRSW1000A 4P WN600V ITEM PART NO QTY DESCRIPTION 43 080433 REF LUG SLDLSS 500 1X13 32 AL CU 063925 REF LUG SLDLSS 500 4 0X17 32 AL CU 44 074349A 2 SW CVR WN 600A 3P 0...

Страница 44: ...42 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 1 Parts List on page 44...

Страница 45: ...43 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7515 D Page 2 Parts List on page 44...

Страница 46: ...XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 072124 1 XFRSW 12...

Страница 47: ...45 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 1 Parts List on page 47...

Страница 48: ...46 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F7516 D Page 2 Parts List on page 47...

Страница 49: ...AL SIGNAL BEFORE XFER 38 0D4203 1 ASSY NEUTRAL BLOCK 1600A ATS 39 0A9457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 45 LG 41 091472A 1 COVER WIRE DUCT 1 IN 45 LG ITEM PART NO QTY DESCRIPTION 42 0...

Страница 50: ...48 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 1 Parts List on page 50...

Страница 51: ...49 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8939 E Page 2 Parts List on page 50...

Страница 52: ...L 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 072122 1 XFRSW 2600A 4...

Страница 53: ...51 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 1 Parts List on page 53...

Страница 54: ...52 Section 8 Exploded Views Parts Lists Assembly Drawing No 0F8940 E Page 2 Parts List on page 53...

Страница 55: ...457 1 DECAL NEUTRAL 40 091472 1 DUCT WIRING 1 X 1 5 138 LG 41 091472A 1 COVER WIRE DUCT 1 IN 138 LG 42 072115 1 XFRSW 2000A 3P WN600V 072121 1 XFRSW 2000A 4P WN600V 072116 1 XFRSW 2600A 3P WN600V 0721...

Страница 56: ...s of normal maintenance i e tune ups associated part s adjustments loose leaking clamps installation and start up 3 Any failure caused by contaminated fuels oils coolants antifreeze or lack of proper...

Отзывы: