STARTING AND STOPPING - SEQUENCE DIAGRAMS
Remote start
contacts
CLOSED?
Start the Engine
At
load accept
limits?
Warmup timer
expired?
Issue load
accept signal
Remote start
contacts
OPEN?
Cooldown
timer expired?
Stop the Engine
2-wire Remote Starting and
Stopping Sequence
Keyswitch in Auto Position
NOTE: Shutdown Alarms will
cause the engine to turn off
or not start.
NO
NO
NO
NO
NO
Time to
exercise?
Start the Engine
Exercise
time
expired?
Stop the Engine
Exercise without transfer
starting and stopping sequence
keyswitch in auto position.
NOTE: Shutdown Alarms will
cause the engine to turn off
or not start.
NO
NO
NOTE: A Remote Start signal
will terminate exercise and
proceed to normal running mode.
HTS indicates
loss of Utility?
Start the Engine
At
load accept
limits?
Warmup timer
expired?
Command HTS
to transfer to
Generator Power
HTS indicates
return of
Utility?
Cooldown
timer expired?
Stop the Engine
Loss of utility with HTS
starting and stopping
sequence keyswitch in
auto position.
NOTE: Shutdown Alarms will
cause the engine to turn off
or not start.
NO
NO
NO
NO
NO
7
General Information
H-100 Control Panel Technical Manual
Содержание H-100
Страница 1: ...POWER SYSTEMS INC H 100 Control Panel Technical Manual This manual should remain with the unit ...
Страница 50: ...48 Notes H 100 Control Panel Technical Manual ...
Страница 51: ...49 Notes H 100 Control Panel Technical Manual ...
Страница 52: ...Part No 0F3750 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision A 03 13 06 Printed in U S A ...