H-100 DIGITAL OUTPUT FUNCTIONS
Number
Default Function Name
Function Description
1
COMMON ALARM
An alarm is active
2
COMMON WARNING
A warning is active
3
GEN RUNNING
Generator is running
4
ALARMS ENABLED
All alarm hold off delays have expired, so all alarms are enabled
5
READY FOR LOAD
Generator is warmed up and ready to accept power loading
6
GEN READY TO RUN
Generator is ready to start
7
GEN STOPPED-ALRM
Generator stopped due to a shutdown alarm
8
GEN STOPPED
Generator is stopped
9
GEN IN MANUAL
Generator in MANUAL mode ( key switch in MANUAL or ILC overriden)
10
GEN IN AUTO
Generator in AUTO mode ( key switch in AUTO or ILC overriden )
11
GEN IN OFF
Generator in OFF mode ( key switch in OFF or ILC overriden )
12
OVERCRANK ALARM
Generator has unsuccessfully tried to start the designated number of times
13
OIL INHIBIT ALRM
Oil pressure too high for a stopped engine
14
ANNUNC SPR LIGHT
ILC controlled: this function operates the spare remote annunciator light
15
OIL TEMP HI ALRM
Oil Temperature has gone above maximum alarm limit
16
OIL TEMP LO ALRM
Oil Temperature has gone below minimum alarm limit
17
OIL TEMP HI WARN
Oil Temperature has gone above maximum warning limit
18
OIL TEMP LO WARN
Oil Temperature has gone below maximum warning limit
19
OIL TEMP FAULT
Oil Temperature sensor exceeds nominal limits for valid sensor reading
20
COOL TMP HI ALRM
Coolant Temperature has gone above maximum alarm limit
21
COOL TMP LO ALRM
Coolant Temperature has gone below minimum alarm limit
22
COOL TMP HI WARN
Coolant Temperature has gone above maximum warning limit
23
COOL TMP LO WARN
Coolant Temperature has gone below maximum warning limit
24
COOL TMP FAULT
Coolant Temperature sensor exceeds nominal limits for valid sensor reading
25
OIL PRES HI ALRM
Oil Pressure has gone above maximum alarm limit
26
OIL PRES LO ALRM
Oil Pressure has gone below minimum alarm limit
27
OIL PRES HI WARN
Oil Pressure has gone above maximum warning limit
28
OIL PRES LO WARN
Oil Pressure has gone below maximum warning limit
29
OIL PRES FAULT
Oil Pressure sensor exceeds nominal limits for valid sensor reading
30
COOL LVL HI ALRM
Coolant Level has gone above maximum alarm limit
31
COOL LVL LO ALRM
Coolant Level has gone below minimum alarm limit
32
COOL LVL HI WARN
Coolant Level has gone above maximum warning limit
33
COOL LVL LO WARN
Coolant Level has gone below maximum warning limit
34
COOL LVL FAULT
Coolant Level sensor exceeds nominal limits for valid sensor reading
35
ANALOG 5 HI ALRM
Analog Input #5 has gone above maximum alarm limit
FUEL LVL HI ALRM
Fuel Level
36
ANALOG 5 LO ALRM
Analog Input #5 has gone below minimum alarm limit
FUEL LVL LO ALRM
Fuel Level
37
ANALOG 5 HI WARN
Analog Input #5 has gone above maximum warning limit
FUEL LVL HI WARN
Fuel Level
38
ANALOG 5 LO WARN
Analog Input #5 has gone below maximum warning limit
FUEL LVL LO WARN
Fuel Level
39
ANALOG 5 FAULT
Analog Input #5 sensor exceeds nominal limits for valid sensor reading
FUEL LVL FAULT
Fuel Level
40
ANALOG 6 HI ALRM
Analog Input #6 has gone above maximum alarm limit
FUEL PRS HI ALRM
Fuel Pressure
INLT TMP HI ALRM
Inlet Air Temperature
41
ANALOG 6 LO ALRM
Analog Input #6 has gone below minimum alarm limit
FUEL PRS LO ALRM
Fuel Pressure
INLT TMP LO ALRM
Inlet Air Temperature
42
Appendix B
H-100 Control Panel Technical Manual