3
THE MEASUREMENT "ENGINE"
The measurement “engine” is the key feature of the
system. All the inputs to the controller are processed
by this module. Each physical input is measured and
the result processed by an individual set of rules that
are set via a PC and GenLink. Normally, a product
is delivered with the inputs and outputs pre-con-
figured and nothing needs to be done, however the
manufacturer has provided complete flexibility to
each measurement (except where product safety is
concerned). The inputs are divided into analog and
digital channels.
ANALOG CHANNELS
There are 23 analog channels of which 14 have fixed
functions. The remaining 9 channels are split between
product specific inputs (such as oil temperature),
and customer spares. The exact split depends on the
product. Table 1 shows the channel allocation.
Some of the 14 fixed channels are “DERIVED” read-
ings in that they are calculated from the other read-
ings. For example, power is calculated from both volt-
age and current. These are not real hardware chan-
nels, but they result in an analog reading that can be
treated as a “fixed channel” just like any other.
ANALOG MATHS
Each of the 23 channels is processed by a set of mea-
suring rules using constants that are set via GenLink.
Usually these constants can be changed by the cus-
tomer. In the following illustration, the measurement
is represented by M and the GenLink constants are
in italics. The measurement is processed in the fol-
lowing order and the result is then stored for cus-
tomer display or use.
M = M *
Calibration Factor
This is used to calibrate out any reading inaccura-
cies where calibration factor is a number such that
1024 is equivalent to 1, so it’s really M * calibration
factor/ 1024. GenLink will hide this computation so
you can enter floating point numbers such as 1.1 or
0.987 etc.
THEN
M = M processed by function x:
General Information
H-100 Control Panel Technical Manual
CPU
Channel
Derived
No.
Channel Title
Update Rate
Value
7
User Configurable #1 (Usually Oil Temp)
3.84 ms
No
8
User Configurable #2 (Usually Coolant Temp)
3.84 ms
No
9
User Configurable #3 (Usually Oil Pressure)
3.84 ms
No
10
User Configurable #4 (Usually Coolant Level)
3.84 ms
No
11
User Configurable #5 (Usually Fuel level)
3.84 ms
No
12
User Configurable #6 - Spare -
3.84 ms
No
13
User Configurable #7 (Usually throttle position)
3.84 ms
No
14
Special Oxygen sensor
3.84 ms
No
15
Special Battery charge sensor
3.84 ms
No
16
Battery Voltage/ PSU voltages
3.84 ms
No
1
Generator Phase A RMS Current
Phase A ZERO CROSSING
No
2
Generator Phase B RMS Current
Phase B ZERO CROSSING
No
3
Generator Phase C RMS Current
Phase C ZERO CROSSING
No
-
Generator average current
Every Phase ZERO CROSSING
Yes
4
Generator Phase A RMS Voltage
Phase A ZERO CROSSING
No
5
Generator Phase B RMS Voltage
Phase B ZERO CROSSING
No
6
Generator Phase C RMS Voltage
Phase C ZERO CROSSING
No
-
Generator average voltage
Every Phase ZERO CROSSING
Yes
-
Total Generator Power KW
Every Phase ZERO CROSSING
Yes
-
Total Generator Power Factor
Every Phase ZERO CROSSING
Yes
-
Generator Frequency
Every Phase ZERO CROSSING
Yes
-
RPM #1
4 - 8 ms variable (geared)
Yes
-
Oxygen sensor zero crossings
Every O2 ZERO CROSSING
No
Table 1
Содержание H-100
Страница 1: ...POWER SYSTEMS INC H 100 Control Panel Technical Manual This manual should remain with the unit ...
Страница 50: ...48 Notes H 100 Control Panel Technical Manual ...
Страница 51: ...49 Notes H 100 Control Panel Technical Manual ...
Страница 52: ...Part No 0F3750 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision A 03 13 06 Printed in U S A ...