20 

Changing Engine Oil

 CauTION

Avoid prolonged or repeated skin contact with used 

motor oil.

Used motor oil has been shown to cause skin cancer in 

certain laboratory animals.
Thoroughly wash exposed areas with soap and water.

KEEP OUT OF REACH OF CHILDREN. DON’T 

POLLUTE. CONSERVE RESOURCES. RETURN USED 

OIL TO COLLECTION CENTERS. 

  1.  Confirm 15 Amp fuse is removed from control panel.
  2.  Place oil drain hose into an approved container.
  3.  Remove brass fitting from end of drain hose.

NOTE

: Change oil while the engine is still warm from 

running, as described in the engine operator’s manual.

notice

Any attempt to crank or start the engine before it has 

been properly serviced with the recommended oil will 

result in equipment failure.

Refer to 

Maintenance

 and engine manual for oil fill 

information.
Damage to equipment resulting from failure to follow this 

instruction will void engine and generator warranty.

  4.  When oil has drained, replace brass fitting on hose.
  5.  If all engine servicing is complete, replace 15 Amp fuse 

in control panel and reset exercise timer. See 

Setting 

Exercise Timer

 in 

Operation

.

To fill your engine with oil:

Follow the oil grade recommendation and oil fill instructions 

given in the engine operator’s manual.
To make the task of adding oil more convenient, we 

recommend use of a funnel attached to a length of tubing 

long enough to reach from the Coolant Fill door to the oil fill 

opening on the engine valve cover.

Engine Coolant System

With the engine cold, check the coolant level in the coolant 

reservoir, seen inside the Control Panel door. Maintenance 

instructions for engine coolant are found in the engine 

operator’s manual.

Battery

Servicing of batteries are to be performed or supervised 

by personnel knowledgeable of batteries and the 

required precautions. Keep unauthorized personnel away 

from batteries.

 WaRNING

Battery posts, terminals and related 

accessories contain lead and lead compounds, 

chemicals known to the State of California to 

cause cancer and reproductive harm. Wash 

hands after handling.

Servicing the Battery

If it is necessary to service the battery, proceed as follows:
  1.  Open “Control Panel” access door.
  2.  Set generator’s system switch to 

OFF

.

  3.  Remove 15 Amp fuse from control panel.
  4.  Service or replace battery as required.
  5.  Connect red battery cable to battery positive terminal 

(indicated by 

POSITIVE

POS

, or (

+

)).

  6.  Connect negative battery cable to negative battery 

terminal (indicated by 

NEGATIVE

NEG

, or (

-

).

  7.  Ensure hardware on both positive and negative battery 

terminals is secure.

  8.  Reinstall 15 Amp fuse in control panel.
  9.  Set generator’s system switch to 

AUTO

.

 10.  Reset exercise timer. See 

Setting Exercise Timer

 11.  Close “Control Panel” access door.

DON’T POLLUTE. CONSERVE RESOURCES, 

RETURN USED BATTERY TO RECYCLING 

COLLECTION CENTER.

Charging the Battery

If it is necessary to charge the battery, proceed as follows:
  1.  Set generator’s system switch to 

OFF

.

  2.  Remove 15 Amp fuse from control panel.
  3.  Disconnect negative battery cable from negative battery 

terminal (indicated by 

NEGATIVE

NEG

, or (

-

).

notice

Failure to disconnect negative battery cable will result in 

equipment failure.

DO NOT attempt to jump start the battery.
Damage to equipment resulting from failure to follow this 

instruction will void warranty.


  4.  Charge battery with battery charger at 2 Amps until 

battery holds 12 Volts.

NOTE

: DO NOT exceed 13.7 volts when charging.

Содержание GEN27WN

Страница 1: ...Questions Help is just a moment away Call Home Generator Helpline 877 369 9400 M F 8 5 CT Liquid Cooled Residential Generator System Operator s Manual GEN27WN GEN30WL GEN42WN GEN45WL...

Страница 2: ...id them Because Rheem does not necessarily know all the applications this equipment could be used for it is important that you read and understand these instructions thoroughly before attempting to st...

Страница 3: ...cuits 10 Delivery Inspection 11 Features and Controls 12 30 kW Residential Generator 12 45 kW Home Generator 13 System Control Panel 14 Operation 16 Automatic Operation 16 Setting Exercise Timer 17 Ma...

Страница 4: ...monoxide can cause headache fatigue dizziness vomiting confusion seizures nausea fainting or death Operate generator ONLY outdoors Install a battery operated carbon monoxide alarm near the bedrooms K...

Страница 5: ...he 15 Amp fuse BEFORE working on the equipment warning Propane and Natural Gas are extremely flammable and explosive Fire or explosion can cause severe burns or death Install the fuel supply system ac...

Страница 6: ...or can damage it and shorten its life Use generator only for intended uses If you have questions about intended use contact your authorized dealer Operate generator only on level surfaces Adequate uno...

Страница 7: ...Safety Label Locations 30kW...

Страница 8: ...Safety Label Locations 45kW...

Страница 9: ...with your system A thorough understanding of these options will provide some control over the cost of your installation as well as ensure your final satisfaction and security Federal and local codes...

Страница 10: ...to include as Essential Circuits Depending on the power consumed by these circuits most or all of them can be switched to the residential generator for the duration of normal power interruption The wa...

Страница 11: ...average load factor of 80 of the standby rating The standby rating is only applicable for optional standby power where the generator set serves as the backup to the normal utility source Use the watt...

Страница 12: ...attery Door opening Provides access to starting battery and air cleaner E Oil Dip Stick Used to check the engine oil level F Engine Label Identifies engine model and type G Oil Fill Cap Remove to serv...

Страница 13: ...High performance muffler lowers engine noise to comply with most residential codes J Coolant Fill Door Provides access for servicing engine with oil and coolant K Oil Filter Filters engine oil to pro...

Страница 14: ...s blown melted open or was removed the engine cannot crank or start Replace the fuse using only an identical ATO 15A fuse E System Switch This two position switch is the most important control on the...

Страница 15: ...remain closed at all other times Each residential generator is equipped with two identical keys These keys fit the locks that secure the access doors To Open an Access Door 1 Insert key into lock of a...

Страница 16: ...unit in AUTO mode the battery receives a trickle charge while the engine is not running The trickle charge cannot be used to recharge a battery that is completely discharged 15 Amp Fuse The generator...

Страница 17: ...Maintenance Servicing the System To service the residential generator system 1 Remove 15 Amp fuse from control panel 2 Set control panel system switch to OFF 3 Set the generator s main circuit breake...

Страница 18: ...ct an Authorized Dealer Low Voltage Generator FC_3 This fault is indicated by fault code FC_3 and three blinks on the LED indicator This condition is caused by a restriction in the fuel flow a broken...

Страница 19: ...ructed in the operator s manual All adjustments should be made at least once each season Follow the requirements in the operator s manual Generator maintenance consists of keeping the unit clean Opera...

Страница 20: ...s for engine coolant are found in the engine operator s manual Battery Servicing of batteries are to be performed or supervised by personnel knowledgeable of batteries and the required precautions Kee...

Страница 21: ...To Clean the Generator notice Improper treatment of generator can damage it and shorten its life DO NOT expose generator to excessive moisture dust dirt or corrosive vapors DO NOT insert any objects t...

Страница 22: ...rvice facility 4 See Gaseous Fuel System in the Installation Manual 5 Remove kink Replace if necessary Engine will not start or starts and runs rough 1 15 Amp fuse missing or blown 2 Fuel supply turne...

Страница 23: ...er g to wear items such as oil gauges o rings filters fuses or spark plugs etc ADDITIONAL EXCLUSIONS UNDER COMMERCIAL APPLICATION 1 Wear items such as engine oil oil gauges o rings filters fuses spark...

Страница 24: ...und in your telephone directory or by contacting a RHEEM RUUD or PROTECH air conditioning distributor If necessary the following office can advise you of the nearest distributor 4744 Island Ford Road...

Страница 25: ...Reserved 25...

Страница 26: ...40 Volts 125 Amps Rated AC Voltage 120 240 Volts Phase Single phase Rated Frequency 60 Hertz Normal Operating Range 20 F 28 8 C to 104 F 40 C Output Sound Level 65 dB A at 23 ft 7 m at normal load Shi...