20
Changing Engine Oil
CauTION
Avoid prolonged or repeated skin contact with used
motor oil.
Used motor oil has been shown to cause skin cancer in
certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
•
•
KEEP OUT OF REACH OF CHILDREN. DON’T
POLLUTE. CONSERVE RESOURCES. RETURN USED
OIL TO COLLECTION CENTERS.
1. Confirm 15 Amp fuse is removed from control panel.
2. Place oil drain hose into an approved container.
3. Remove brass fitting from end of drain hose.
NOTE
: Change oil while the engine is still warm from
running, as described in the engine operator’s manual.
notice
Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will
result in equipment failure.
Refer to
Maintenance
and engine manual for oil fill
information.
Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
•
•
4. When oil has drained, replace brass fitting on hose.
5. If all engine servicing is complete, replace 15 Amp fuse
in control panel and reset exercise timer. See
Setting
Exercise Timer
in
Operation
.
To fill your engine with oil:
Follow the oil grade recommendation and oil fill instructions
given in the engine operator’s manual.
To make the task of adding oil more convenient, we
recommend use of a funnel attached to a length of tubing
long enough to reach from the Coolant Fill door to the oil fill
opening on the engine valve cover.
Engine Coolant System
With the engine cold, check the coolant level in the coolant
reservoir, seen inside the Control Panel door. Maintenance
instructions for engine coolant are found in the engine
operator’s manual.
Battery
Servicing of batteries are to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
from batteries.
WaRNING
Battery posts, terminals and related
accessories contain lead and lead compounds,
chemicals known to the State of California to
cause cancer and reproductive harm. Wash
hands after handling.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Open “Control Panel” access door.
2. Set generator’s system switch to
OFF
.
3. Remove 15 Amp fuse from control panel.
4. Service or replace battery as required.
5. Connect red battery cable to battery positive terminal
(indicated by
POSITIVE
,
POS
, or (
+
)).
6. Connect negative battery cable to negative battery
terminal (indicated by
NEGATIVE
,
NEG
, or (
-
).
7. Ensure hardware on both positive and negative battery
terminals is secure.
8. Reinstall 15 Amp fuse in control panel.
9. Set generator’s system switch to
AUTO
.
10. Reset exercise timer. See
Setting Exercise Timer
.
11. Close “Control Panel” access door.
DON’T POLLUTE. CONSERVE RESOURCES,
RETURN USED BATTERY TO RECYCLING
COLLECTION CENTER.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator’s system switch to
OFF
.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable from negative battery
terminal (indicated by
NEGATIVE
,
NEG
, or (
-
).
notice
Failure to disconnect negative battery cable will result in
equipment failure.
DO NOT attempt to jump start the battery.
Damage to equipment resulting from failure to follow this
instruction will void warranty.
•
•
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts.
NOTE
: DO NOT exceed 13.7 volts when charging.