General Information
Owner’s Manual for Australian 3-Phase 50 Hz Air-Cooled Generator Sets
9
Specifications
Generator Set
Engine
A detailed specification sheet for a particular generator set is available from an IASD.
Model
20 kVA
Rated voltage
380 / 400 / 416
Rated maximum load
current (a) at rated
voltage*
30.4 / 28.9 / 27.18
Main line circuit breaker
(generator set disconnect)
32 A
Phase
3
Rated AC frequency
50 Hz
Battery requirement
12V, Group 25R 540 CCA minimum, or Group 35 AGM 650 CCA minimum
(See
Enclosure
Aluminum
Weight (kg / lbs)
192.8 / 425
Normal operating range
This unit is tested in accordance to UL 2200 standards with an operating temperature of -29 °C (-20
°F) to 50 °C (122 °F). For areas where temperatures fall below 0 °C (32 °F), a cold weather kit is
recommended. There may be a decrease in engine power when operated above 25 °C (77 °F).
(Please reference the engine specifications section.)
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04
Standard for Motors and Generators.
* Natural gas ratings will depend on specific fuel BTU / joules content. Typical derates are between 10–20% of the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For example, a 15A circuit in the main panel must be a 15A circuit in the transfer
switch.
Model
20 kVA
Engine type
Generac G-Force 1000 Series
Number of cylinders
2
Displacement
999 cc
Cylinder block
Aluminum w/ cast iron sleeve
Recommended spark plug
See
Spark plug gap
1.02 mm (0.040 in)
Valve clearance
0.05–0.1 mm (0.002–0.004 in)
Starter
12 VDC
Oil capacity including filter
Approx. 1.8 L (1.9 qts)
Recommended oil filter
See
Recommended air filter
See
Engine power is subject to and limited by such factors as fuel BTU/joules, ambient temperature and altitude. Engine power decreases approxi-
mately 3.5% for each 304.8 m (1,000 ft) above sea level, and also will decrease approximately 1% for each 6 °C (10 °F) above 15 °C (60 °F) ambi-
ent temperature.