Generac Power Systems Digital Controller R-200A Скачать руководство пользователя страница 8

 6 

General Information

R-panel Technical Manual

ACTIVE ALARM

Low Oil Pressure, High Coolant Temp, Low Coolant 
Level, Overspeed, Overcrank, Engine Speed Signal 
Loss and a Dead Battery indication will all be latched 
shutdowns. In the event one of these conditions 
occurs, the unit will be shut down, the appropriate 
LED will be illuminated, and the unit will not start 
again without manual intervention (see Re-Crank 
below).

RE-CRANK

If an engine speed signal failure occurs while the gen-
erator is running the engine will shutdown and then 
attempt a re-crank. A maximum of two re-cranks will 
be attempted after which the overcrank LED will be 
set. If the engine speed signal failure occurred during 
the engine exercise mode the exercise timer will con-
tinue from where it was at the start of the re-crank 
and is not reset.

NORMAL EXERCISE MODE

To select this mode, place DIP switch position 3 in 
the ON position.

In Normal Exercise Mode the generators will exercise 
at their normal running speed.

The R-200A controller will start and run the genera-
tor once every seven (7) days for approximately 12 
minutes. If the utility fails during the exercise period, 
this exercise period is aborted and the R-200A 
Controller transfers the load to the generator output, 
assumes automatic operation and continues to run 
until the utility is returned.

The weekly exercise cycle is set as follows:

1.  Place the AUTO/OFF/MANUAL switch in the 

AUTO position.

2.  Press and hold the "Set Exercise Time " switch for 

five (5) seconds and then release.

At this time all five (5) red LED's will flash for 10 
seconds, then the engine will start and run for it's 
12 minute exercise period, then shut down. The gen-
erator will now start and run each week at approxi-
mately the same time.

If battery power to the R-200A Controller is lost, the 
weekly exercise time setting will be lost. This is indi-
cated by all five (5) red LED's continually flashing in 
ATS mode. In this state the generator will still start 
and run in MANUAL mode, or automatically start and 
run if utility voltage is lost while in AUTO mode, but 
it will NOT perform a weekly exercise cycle.

In the event of a failure while running in this mode, 
the five (5) red LED's will stop flashing, the indi-
vidual fault LED will turn on and the engine will be 
shut down. Once the AUTO/OFF/MANUAL switch is 
switched to OFF, the individual fault LED will turn off 
and the five (5) red LED's will begin flashing to show 
that the exercise mode has not yet been set.

LOW SPEED EXERCISE

To select this mode place DIP switch position 3 in the 
OFF position.

In Low Speed Exercise mode the normal speed 3600 
rpm generators will exercise at 1800 rpm. The nor-
mal 1800 rpm generators will exercise at 1400 rpm 
in this mode.

If the utility fails during the low speed exercise period, 
a 10 second timer will start. If the utility returns to 
a normal operating level, during this 10 second time 
interval the low speed exercise operation will contin-
ue. If the utility is still not present (i.e. utility voltage 
less than 60% of nominal) when the above 10 second 
timer expires then the low speed exercise mode is 
terminated and the engine will ramp up to its normal 
running speed within five (5) seconds. If the utility 
returns during the five (5) second ramp-up period 
the generator will terminate the exercise mode. If the 
utility is still not present, once the generator is up 
to its normal running speed, then the controller will 
transfer the load to the generator. When the utility 
returns the generator will shutdown.

If battery power to the R-200A Controller is lost, the 
weekly exercise time setting will be lost. This is indi-
cated by all 5 red LED's continually flashing in ATS 
mode. In this state the generator will still start and 
run in MANUAL mode, or automatically start and run 
if utility voltage is lost while in AUTO mode, but it will 
NOT perform a weekly exercise cycle.

In the event of a failure while running in this mode, 
the five (5) red LED's will stop flashing, the indi-
vidual fault LED will turn on and the engine will be 
shut down. Once the AUTO/OFF/MANUAL switch is 
switched to OFF, the individual fault LED will turn off 
and the five (5) red LED's will begin flashing to show 
that the exercise mode has not yet been set.

AUTO START

This unit is designed to automatically start in the 
event of a utility failure. A utility failure is defined as 
the utility voltage being less than approximately 60% 
of nominal, while the utility is considered good when 
it is restored to approximately 80% of its nominal 
value.

If the generator is already running under exercise 
when an auto start is required, it will simply transfer 
the load after a 15 second delay and then switch to 
auto operation.

Содержание Digital Controller R-200A

Страница 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200A Digital Controller A new standard of reliability...

Страница 2: ...and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical...

Страница 3: ...emp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indic...

Страница 4: ...0G1303F will work in place of 0G1303B 0G1505A or 0G1505B The addition of the 4 2L engine required creation of a new series of controller see Figure 2 This control ler is part number 0G3958C for 1800...

Страница 5: ...ORMAL 1 6L 35kW NG RESERVED kW RATING FOR 2 4L 3600 RPM AND 4 2L 1800 RPM ENGINE TYPE WHEN POS 7 IS OFF EXERCISE MODE FUEL TYPE ENGINE SELECT FOR 4 2L RESERVED TRANSFER SW MODE 1 6L 2 4L 4 2L Jumper P...

Страница 6: ...l Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X...

Страница 7: ...a 15 second timer will start If the utility is still gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer...

Страница 8: ...n and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode...

Страница 9: ...oller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200A controller continually monitors the bat tery v...

Страница 10: ...n the front panel will be ON all the time if DIP switch position 5 is not set cor rectly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch mu...

Страница 11: ...ill NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator c...

Страница 12: ...run the generator whenever the switch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via...

Страница 13: ...ge and then the charge current will decrease to maintain the battery at that float voltage The 10 Amp battery charger is an equalize type charger An equalize type charger will charge the battery at it...

Страница 14: ...Range 108Vac to 132Vac Input AC Line Frequency 50 or 60Hz AC Line Fuse 2 Amp Slo Blo 5x20mm Littelfuse P N 218002 Battery Fuse 5 Amp Littelfuse Mini Blade Fuse P N 297005 Nominal Charge Rate 2 Amps F...

Страница 15: ...13 Notes R panel Technical Manual...

Страница 16: ...Part No 0G1341 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision E 06 19 07 Printed in U S A...

Отзывы: