 8 

RPM SIGNAL FAILURE (FLASHING RED 
OVERSPEED INDICATOR)

If the R-200A controller does not receive a signal 
from the engine flywheel sensor, the R-200A control-
ler cannot maintain the generator output frequency 
or monitor for an overspeed condition. If this sig-
nal is lost the R-200A controller will shut down the 
engine as follows:

RPM SIGNAL FAILURE DURING CRANKING

The engine control board (R-200A controller) will 
monitor the engine speed signal during engine crank-
ing. If the control board does not see a valid signal 
within the first four seconds of each crank cycle it 
will stop the crank cycle, lock out on a shut down 
fault and flash the overspeed LED.

RPM SIGNAL FAILURE DURING RUNNING

Running mode is handled differently because there 
is always the possibility the engine could slow down 
or stop running due to a temporary overload. To 
avoid shutting down and latching out on a temporary 
problem the following is done. If the engine is up and 
running, and the control board stops receiving a valid 
engine speed input signal it will respond as follows:

1.  It will close the throttle.
2.  It will shut down the engine by turning off the fuel 

supply.

3.  It will wait for 15 seconds to ensure the engine 

has stopped.

4.  It will then energize the starter and monitor the 

engine speed signal.

A.  If the control board does not see the engine 

speed signal it will stop the crank cycle, lock out 
on fault, and flash the overspeed LED.

B.  If the control board does see the engine speed 

input signal during cranking it will start and run 
the engine normally. If the engine speed signal is 
again lost while running it will repeat the above 
procedure one more time.

C.  If the failure should repeat a third time, the con-

trol board will shut down the engine, lock out on 
fault, and flash the over speed LED.

OVERCRANK (RED LED INDICATOR)

Occurs if the engine has not started within the total 
90 second crank cycle. This is a latched fault and will 
shut down the engine.

‹

‹

INVALID DIP SWITCH SETTING
(ALL RED LED’S ON)

All five (5) RED LED’s on the front panel will be ON 
all the time if DIP switch position 5 is not set cor-
rectly.

ALARM CANCEL

When the generator is shut down on a latched fault or 
latching alarm, the AUTO/OFF/MANUAL switch must 
be set to the OFF position to turn off the correspond-
ing fault LED. Prior to moving the switch to the OFF 
position, record which LEDs are ON or FLASHING 
and the date on the back cover of this manual.

AUTOMATIC TRANSFER SWITCH (ATS 
MODE)

When this generator, along with an RTS-type or HS-
type automatic transfer switch has been installed and 
connected, a circuit board in the generator control 
panel constantly monitors the utility voltage and con-
trols the operation of the transfer switch.

To implement this mode of operation, Position 2 of 
the eight-position DIP switch, which is located on the 
generator circuit board (see Figures 1 and 2), must 
be in the OFF position. In ATS Mode utility voltage 
sensing, weekly exercising, and load transferring is 
under the control of the generator.

Should the utility voltage drop below a preset value, 
and remain at this low voltage for a preset amount 
of time, the generator cranks and starts. After the 
generator starts, the transfer switch transfers the 
load circuits to the generator so the generator can 
power them. When the utility source voltage has been 
restored, the transfer switch re-transfers the load 
circuits back to the utility source voltage and the gen-
erator shuts down.

The transfer switch is controlled by the generator 
circuit board via control wires 23 and 194. Wire 23 
connects the collector of an NPN transistor on the 
generator circuit board to the “low side” (Terminal 
23) of the transfer relay coil in the transfer switch. 
Wire 194 connects positive battery voltage from the 
generator circuit board to the “high side” (Terminal 
194) of the transfer relay coil in the transfer switch.

In order for the generator utility voltage sensing 
function to work, it is necessary to provide a 5 amp 
fused 240VAC for 240V or 480V systems or 208VAC 
utility source connection (depending on the generator 
being used) from the transfer switch main N1 and N2 
terminals to the generator wiring panel N1 and N2 
terminals (See Figure 4).

General Information

R-panel Technical Manual

Содержание Digital Controller R-200A

Страница 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200A Digital Controller A new standard of reliability...

Страница 2: ...and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical...

Страница 3: ...emp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indic...

Страница 4: ...0G1303F will work in place of 0G1303B 0G1505A or 0G1505B The addition of the 4 2L engine required creation of a new series of controller see Figure 2 This control ler is part number 0G3958C for 1800...

Страница 5: ...ORMAL 1 6L 35kW NG RESERVED kW RATING FOR 2 4L 3600 RPM AND 4 2L 1800 RPM ENGINE TYPE WHEN POS 7 IS OFF EXERCISE MODE FUEL TYPE ENGINE SELECT FOR 4 2L RESERVED TRANSFER SW MODE 1 6L 2 4L 4 2L Jumper P...

Страница 6: ...l Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X...

Страница 7: ...a 15 second timer will start If the utility is still gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer...

Страница 8: ...n and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode...

Страница 9: ...oller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200A controller continually monitors the bat tery v...

Страница 10: ...n the front panel will be ON all the time if DIP switch position 5 is not set cor rectly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch mu...

Страница 11: ...ill NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator c...

Страница 12: ...run the generator whenever the switch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via...

Страница 13: ...ge and then the charge current will decrease to maintain the battery at that float voltage The 10 Amp battery charger is an equalize type charger An equalize type charger will charge the battery at it...

Страница 14: ...Range 108Vac to 132Vac Input AC Line Frequency 50 or 60Hz AC Line Fuse 2 Amp Slo Blo 5x20mm Littelfuse P N 218002 Battery Fuse 5 Amp Littelfuse Mini Blade Fuse P N 297005 Nominal Charge Rate 2 Amps F...

Страница 15: ...13 Notes R panel Technical Manual...

Страница 16: ...Part No 0G1341 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision E 06 19 07 Printed in U S A...

Отзывы: