General Information

R-panel Technical Manual

 

Switch Position

Condition System 

Low 

Low 

Low 

High 

Over 

Over 

Manual 

Auto 

Off

 Ready 

Fuel 

Bat 

Oil 

Temp 

Speed 

Crank

Generator Switch is 

OFF 

OFF 

OFF 

OFF 

OFF 

 

 

O

in the OFF Mode

System Ready for 

ON 

OFF 

OFF 

OFF 

OFF 

 

O

Automatic Start

Generator Switch is 

OFF 

OFF 

OFF 

OFF 

OFF 

O

in the MANUAL Mode

Weekly Exerciser 

Flashing  Flashing  Flashing 

Flashing 

Flashing 

O

is not Set (Note A) 

 

           

(---------------------------------------1 sec rate -------------------------------------)

Battery Voltage <12.2V 

ON 

 

 

 

 

O

for > 1 minute 

 

 

(Non-Latching)

Battery Voltage <6V 

OFF 

ON 

 

 

 

 

O

For > 0.05 seconds

Unit Shutdown due 

OFF 

ON 

 

 

 

O

To Low Oil Pressure

Unit Shutdown due 

OFF 

 

ON 

 

 

O

To High Cooant Temp

Unit Shutdown due 

OFF 

 

 

ON 

 

O

To Engine Overspeed

Unit Failed to Start 

OFF 

 

 

 

ON 

O

During it's Crank Cycle

Utility Voltage is 

Flashing 

 

 

 

 

O

< 60% of Nominal 

1 sec rate

Unit Shutdown due 

OFF 

 

Flashing 

 

 

O

To Low Coolant Level

Engine Speed Signal 

OFF 

 

 

Flashing 

 

O

Fault/RPM Signal Loss

Control Board is  

Flashing 

 

 

 

 

O

In GTS Mode 

5 sec ON, 1 sec OFF

DIP Switch #5 is 

OFF 

ON 

ON 

ON 

ON 

ON 

O

not set correctly

@ = Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column
X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto)
Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set

Содержание Digital Controller R-200A

Страница 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200A Digital Controller A new standard of reliability...

Страница 2: ...and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical...

Страница 3: ...emp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indic...

Страница 4: ...0G1303F will work in place of 0G1303B 0G1505A or 0G1505B The addition of the 4 2L engine required creation of a new series of controller see Figure 2 This control ler is part number 0G3958C for 1800...

Страница 5: ...ORMAL 1 6L 35kW NG RESERVED kW RATING FOR 2 4L 3600 RPM AND 4 2L 1800 RPM ENGINE TYPE WHEN POS 7 IS OFF EXERCISE MODE FUEL TYPE ENGINE SELECT FOR 4 2L RESERVED TRANSFER SW MODE 1 6L 2 4L 4 2L Jumper P...

Страница 6: ...l Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X...

Страница 7: ...a 15 second timer will start If the utility is still gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer...

Страница 8: ...n and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode...

Страница 9: ...oller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200A controller continually monitors the bat tery v...

Страница 10: ...n the front panel will be ON all the time if DIP switch position 5 is not set cor rectly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch mu...

Страница 11: ...ill NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator c...

Страница 12: ...run the generator whenever the switch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via...

Страница 13: ...ge and then the charge current will decrease to maintain the battery at that float voltage The 10 Amp battery charger is an equalize type charger An equalize type charger will charge the battery at it...

Страница 14: ...Range 108Vac to 132Vac Input AC Line Frequency 50 or 60Hz AC Line Fuse 2 Amp Slo Blo 5x20mm Littelfuse P N 218002 Battery Fuse 5 Amp Littelfuse Mini Blade Fuse P N 297005 Nominal Charge Rate 2 Amps F...

Страница 15: ...13 Notes R panel Technical Manual...

Страница 16: ...Part No 0G1341 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision E 06 19 07 Printed in U S A...

Отзывы: