4
General Information
R-panel Technical Manual
Switch Position
Condition System
Low
Low
Low
High
Over
Over
Manual
Auto
Off
Ready
Fuel
Bat
Oil
Temp
Speed
Crank
Generator Switch is
OFF
@
X
OFF
OFF
OFF
OFF
O
in the OFF Mode
System Ready for
ON
@
X
OFF
OFF
OFF
OFF
O
Automatic Start
Generator Switch is
OFF
@
X
OFF
OFF
OFF
OFF
O
in the MANUAL Mode
Weekly Exerciser
X
@
Flashing Flashing Flashing
Flashing
Flashing
O
O
O
is not Set (Note A)
(---------------------------------------1 sec rate -------------------------------------)
Battery Voltage <12.2V
X
@
ON
O
O
O
for > 1 minute
(Non-Latching)
Battery Voltage <6V
OFF
@
ON
O
O
For > 0.05 seconds
Unit Shutdown due
OFF
@
X
ON
O
O
To Low Oil Pressure
Unit Shutdown due
OFF
@
X
ON
O
O
To High Cooant Temp
Unit Shutdown due
OFF
@
X
ON
O
O
To Engine Overspeed
Unit Failed to Start
OFF
@
X
ON
O
O
During it's Crank Cycle
Utility Voltage is
Flashing
@
X
O
O
< 60% of Nominal
1 sec rate
Unit Shutdown due
OFF
@
X
Flashing
O
O
To Low Coolant Level
Engine Speed Signal
OFF
@
X
Flashing
O
O
Fault/RPM Signal Loss
Control Board is
Flashing
@
X
O
O
O
In GTS Mode
5 sec ON, 1 sec OFF
DIP Switch #5 is
OFF
@
ON
ON
ON
ON
ON
O
O
O
not set correctly
@ = Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column
X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto)
Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set