GENERATOR OPERATION

The R-200A controller monitors the front panel 
switch position and reads the DIP switch position set-
tings when the control board is initially powered-up.

In the OFF position the controller will only be incre-
menting the exercise timer and monitoring the bat-
tery voltage and low fuel pressure sensor.

In the MANUAL position the controller will start and 
run the generator. 

In the AUTO position the controller will go into a 
"standby" mode, where the controller will monitor 
the utility voltage and the exercise timer, and deter-
mine if the generator needs to be started and the load 
transferred. 

Battery voltage is continuously monitored and a 
warning LED is lit if the battery voltage drops below 
approximately 12.2 volts for longer than one (1) min-
ute. The LED will turn off when the battery voltage 
goes back above approximately 12.5 volts.

If, however, the battery voltage drops below 6V during 
cranking the low battery LED will stay lit.

While starting and running the engine, the controller 
will monitor the engine condition and shut the engine 
down on;

Over Crank
Over Speed
High Coolant Temperature
Low Coolant Level
Low Oil Pressure
Engine Speed Signal Loss/RPM Sensor Loss (the 

overspeed LED flashes to indicate this fault)

Dead Battery (battery voltage < 6V during crank-

ing)

ENGINE TIMING

Nominal engine timing when Natural Gas (NG) fuel 
is selected is: 

1.6L engine is 34 degrees BTDC at 3600 rpm; 28 

degrees BTDC at 1800 rpm

2.4L engine is 30 degrees BTDC
4.2L engine is 15 degrees BTDC

Nominal engine timing when LP fuel is selected is: 

1.6L engine is 22 degrees BTDC at 3600 rpm; 20 

degrees BTDC at 1800 rpm

2.4L engine is 21 degrees BTDC
4.2L engine is 15 degrees BTDC








UTILITY FAILURE

When the utility fails, a 15 second timer will start. 
If the utility is still gone when the timer expires the 
engine will crank and start. Once started a 10 sec-
ond engine warm-up timer will be initiated. When 
the warm-up timer expires, the R-200A controller 
will transfer the load to the generator (ATS Mode). 
The transfer of load when the generator is running is 
dependent upon the operating conditions as follows:

MANUAL MODE

The unit will not transfer if the utility is present, it 
will un-transfer if the utility voltage is above 80% of 
nominal for > 15 seconds and will re-transfer if the 
utility voltage drops below 60% of nominal for >15 
seconds.

AUTO MODE

The engine will run if the utility fails for >15 sec-
onds, will not transfer if the utility is present, will 
un-transfer if the utility is above 80% of nominal for 
>15 seconds, and will stop the engine after a one 1 
minute cool-down time.

EXERCISE MODE

The unit will not exercise if the generator is already 
running (in manual or auto mode). The generator 
will only transfer if the utility fails during the exer-
cise period for >15 seconds, and the switch is in the 
AUTO mode above.

UTILITY RESTORED

When the utility returns, a 15 second timer will start. 
At the completion of this time, if the utility supply has 
been above 80% of nominal voltage for the previous 
15 seconds, the control will transfer the load back to 
the utility. When the load is transferred a one (1) min-
ute cool down timer will start, after which the engine 
will be shutdown.

INITIAL CRANKING

The initial crank cycle will be a 15 second crank fol-
lowed by a seven (7) second rest. This will be followed 
by 5 additional cycles of seven (7) second cranks fol-
lowed by seven (7) second rests. If the engine still 
fails to start, the overcrank LED will be illuminated. 

Based on the above, the maximum number of engine 
crank events is six (6), which is approximately 90 
seconds, prior to illuminating the overcrank LED.

‹

‹

‹

General Information

R-panel Technical Manual

Содержание Digital Controller R-200A

Страница 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200A Digital Controller A new standard of reliability...

Страница 2: ...and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical...

Страница 3: ...emp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indic...

Страница 4: ...0G1303F will work in place of 0G1303B 0G1505A or 0G1505B The addition of the 4 2L engine required creation of a new series of controller see Figure 2 This control ler is part number 0G3958C for 1800...

Страница 5: ...ORMAL 1 6L 35kW NG RESERVED kW RATING FOR 2 4L 3600 RPM AND 4 2L 1800 RPM ENGINE TYPE WHEN POS 7 IS OFF EXERCISE MODE FUEL TYPE ENGINE SELECT FOR 4 2L RESERVED TRANSFER SW MODE 1 6L 2 4L 4 2L Jumper P...

Страница 6: ...l Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X...

Страница 7: ...a 15 second timer will start If the utility is still gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer...

Страница 8: ...n and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode...

Страница 9: ...oller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200A controller continually monitors the bat tery v...

Страница 10: ...n the front panel will be ON all the time if DIP switch position 5 is not set cor rectly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch mu...

Страница 11: ...ill NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator c...

Страница 12: ...run the generator whenever the switch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via...

Страница 13: ...ge and then the charge current will decrease to maintain the battery at that float voltage The 10 Amp battery charger is an equalize type charger An equalize type charger will charge the battery at it...

Страница 14: ...Range 108Vac to 132Vac Input AC Line Frequency 50 or 60Hz AC Line Fuse 2 Amp Slo Blo 5x20mm Littelfuse P N 218002 Battery Fuse 5 Amp Littelfuse Mini Blade Fuse P N 297005 Nominal Charge Rate 2 Amps F...

Страница 15: ...13 Notes R panel Technical Manual...

Страница 16: ...Part No 0G1341 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision E 06 19 07 Printed in U S A...

Отзывы: