34
Owner’s Manual for G4-ECO Light Tower
Troubleshooting
If problems continue, contact Generac Mobile Products, LLC at 1-800-926-9768 for assistance
Low oil pressure
shutdown
Low oil level
Check oil level.
Oil pump inoperable
Contact a GMP ASD
Unit stalls when export
power is used
Load exceeds unit rating
Turn outlet breaker ON and load sense switch OFF, confirm
generator output is 60 Hz ± 2 Hz. Reapply load.
Mast lights off, checking
inside the control box
Loose lighting connections
Inspect the connections inside the control box.
Loose mast cable connector
Verify outside connector is connected properly to inside control
box.
Generator output incorrect
Check the incoming voltage to the ballast driver by checking the
available voltage on the GFCI receptacle. Incoming voltage
should be 120V ± 5V. If voltage is incorrect, the generator may
require service.
One or more lights do
not turn on
Light breaker tripped.
Inspect light breakers.
Lights not turned on
Inspect electronic control to see if lights are on. Turn lights on.
Problem
Possible Cause
Solution
Содержание G4-ECO
Страница 16: ...27 010832 Introduction and Safety 12 Owner s Manual for G4 ECO Light Tower Figure 1 5 Decal Locations 5 of 5 ...
Страница 32: ...28 Owner s Manual for G4 ECO Light Tower Operation This page intentionally left blank ...
Страница 39: ...Owner s Manual for G4 ECO Light Tower 35 Section 6 Wiring Diagrams AC Schematic ...
Страница 40: ...36 Owner s Manual for G4 ECO Light Tower Wiring Diagrams GTL04 Controller ...
Страница 41: ...Owner s Manual for G4 ECO Light Tower 37 Wiring Diagrams DC Schematic ...
Страница 42: ...38 Owner s Manual for G4 ECO Light Tower Wiring Diagrams LED Light Wiring ...
Страница 43: ......