Owner’s Manual for G4-ECO Light Tower
19
General Information
Setting the Timer
This preset automatically turns the unit ON at a user-
defined time. The unit will remain ON until a delay period
set by the user elapses. When the delay period elapses
the unit will shut OFF.
The unit allows for up to 14 scheduled timers. Within the
Timer menu these presets are named: Program 1-14. In
each program it is possible to set the day and time the
unit starts and the duration of operation.
To set a Program:
NOTE:
See
Navigating Within the Operator Menu
for
information on accessing and adjusting settings.
1.
Access the Operator menu.
2.
Access the Timer menu.
3.
Access the desired Program.
4.
Within the Program menu, adjust the following:
•
Set Enable to Yes.
•
Set the Beginning At to the desired start time.
Available values are 00:00 to 23:59.
•
Set Duration to the desired duration of operation.
Available values are 00:00 to 99:59.
•
Set Day to the desired day of operation. Available
values are Monday through Sunday.
5.
Exit the Program and Timer menus.
6.
Set the unit to Automatic mode using the controller
Manual/Auto button.
7.
Use the controller Manual/Auto button to set the
unit to Automatic mode.
NOTE:
When Automatic mode is selected, the default
manual mode icon
will be replaced by the timer icon:
.
Setting the Clock
NOTE:
See
Navigating Within the Operator Menu
for
information on accessing and adjusting settings.
1.
Access the Operator menu.
2.
Access the Clock menu.
3.
Access the desired Program.
4.
Within the Clock menu, adjust the following:
•
Set Hours to the current time.
•
Set Minutes to the current time.
•
Set Day to the current day.
•
Set Month to the current month.
•
Set Year to the last two digits of the current year.
5.
Exit the Clock and Operator menus.
Resetting Maintenance Alarms
When a maintenance fault occurs, a maintenance alarm
icon will appear on the controller screen identifying the
fault. See
Table 2-1. Maintenance Alarms
Icon
Description
Low oil pressure
Engine oil pressure has fallen below its con-
figured low oil pressure alarm level.
High temperature engine coolant
Engine coolant temperature has risen above
its configured temperature alarm level.
Low fuel level
Engine fuel level has fallen below its config-
ured low fuel level alarm.
Battery charger fault
Battery has failed to charge.
Fail to stop
The engine continues to run after instructed to
stop.
Fail to start
The engine has failed to start after the config-
ured number of start attempts.
Over voltage/frequency
Generator/utility AC has risen above its con-
figured alarm level.
Under voltage/frequency
Generator/utility ACT has fallen below its con-
figured alarm level.
To clear the alarm, the fault must be resolved and the
alarm reset. See
for help on
diagnosing and correcting maintenance issues.
To clear the alarm:
NOTE:
See
Navigating Within the Operator Menu
for
information on accessing and adjusting settings.
1.
Access the Operator menu.
2.
Access the Maintenan. OK menu.
3.
Set Maintenan. OK to YES.
4.
Exit the Maintenan. OK and Operator menus.
Содержание G4-ECO
Страница 16: ...27 010832 Introduction and Safety 12 Owner s Manual for G4 ECO Light Tower Figure 1 5 Decal Locations 5 of 5 ...
Страница 32: ...28 Owner s Manual for G4 ECO Light Tower Operation This page intentionally left blank ...
Страница 39: ...Owner s Manual for G4 ECO Light Tower 35 Section 6 Wiring Diagrams AC Schematic ...
Страница 40: ...36 Owner s Manual for G4 ECO Light Tower Wiring Diagrams GTL04 Controller ...
Страница 41: ...Owner s Manual for G4 ECO Light Tower 37 Wiring Diagrams DC Schematic ...
Страница 42: ...38 Owner s Manual for G4 ECO Light Tower Wiring Diagrams LED Light Wiring ...
Страница 43: ......