background image

D

I

A

GR

AM 1

NO JUMPER FOR NON-

FLOODED AND SEALED 

BATTERIES.

ADD JUMPER 

FOR FLOODED 

BATTERIES:

SUPPLIED

JUMPER

Installation & System Connections:  

     

MOUNTING

Mount the controller near your battery securely using the holes provided on the enclosure’s flanges or with a 
means appropriate to the application. 

• 

Mount near the battery (for lead-acid versions only, use within 0.3 m (1 ft) of batteries. See Caution, p.2).

• 

The GV-10 can be mounted in any orientation on the floor or wall. We recommend a position in which all 

labels are clearly visible.

• 

Do not expose to water.

• 

Do not mount in direct sunlight or near a source of heat.

• 

Allow adequate airflow around the controller to achieve maximum output capability.

• 

For outdoor use, the controller must be housed in an enclosure providing protection 

 

at least equivalent to NEMA Type 3.

      SELECTING THE BATTERY TYPE 

(LEAD-ACID / PB MODEL ONLY)

Your GV-10-Pb-12V controller is supplied set to the “SEALED” charging profile, which is appropriate for most types 
of sealed lead-acid and gel batteries, as well as some types of AGM batteries.  A “FLOODED” setting is available for 
flooded batteries and other types of AGM batteries.  The “FLOODED” setting includes equalization charging.  Please 
consult the specification table at the end of this manual to determine the best setting for your battery type. To 
change your GV-10 controller to the “FLOODED” setting, unscrew the four screws on the bottom of the controller, 
remove the top, and install the supplied jumper on the 6-pin connector as shown in diagram 1.  Use care when 
installing the jumper, as incorrect installation can damage the controller. For sealed batteries, do not install the 
jumper.

• 

Connections should be made according to Article 690 of the National Electrical Code (NFPA 70) or the 
standards in force at the installation location.

• 

Electrical connections may be made in any order; however the sequence below is recommended.

Note: 

The positive or negative battery cable must be 

protected by a fast-acting fuse or circuit breaker of 20A or 

less, rated for the maximum battery voltage and connected 

close to the battery terminal or power distribution block.  This 

fuse will protect the wiring in the event of a short circuit or 

controller damage.

1

2

Содержание GV-10

Страница 1: ...ium Iron Phosphate GV 10 Li 16 7V 14 8V 4s Lithium Cobalt Manganese Nickel GV 10 Li CV V Custom CC CV or Multi Stage Lithium GV 10 Manual For models Solar Charge Controllers with Maximum Power Point Tracking IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS GENASUN GV 10 ALL MODELS MANUAL REVISION 5 0 2020 10 5A 140W SUNFORGE LLC 2598 FORTUNE WAY SUITE K VISTA CA 92081 USA https sunforgellc co...

Страница 2: ...ONCENTRATIONS ATTENTION RISQUE D EXPLOSION NE PAS RÉPARER CONNECTER DÉCONNECTER OU REMPLACER LES FUSIBLES À MOINS QUE LA ZONE SOIT EXEMPTE DE CONCENTRATIONS INFLAMMABLES WARNING REPLACE ONLY WITH THE SAME RATINGS AND TYPE OF FUSE DISCONNECT ALL SOURCES OF SUPPLY BEFORE SERVICING NON ISOLATED ATTENTION REMPLACER SEULEMENT AVEC LE MÊME TYPE ET VALEUR NOMINALE DE FUSIBLE DÉBRANCHER TOUTES LES SOURCES...

Страница 3: ... or voltage range Failure to do so may result in property damage injury or death Genasun highly recommends the use of a BMS with cell balancing Cell balancing is mandatory for lithium iron phosphate Use only 10 30 AWG 5 0 mm2 max copper conductors suitable for a minimum of 60 degrees C If operation at high power or at high ambient temperatures is expected wire with a higher temperature rating may ...

Страница 4: ... batteries as well as some types of AGM batteries A FLOODED setting is available for flooded batteries and other types of AGM batteries The FLOODED setting includes equalization charging Please consult the specification table at the end of this manual to determine the best setting for your battery type To change your GV 10 controller to the FLOODED setting unscrew the four screws on the bottom of ...

Страница 5: ...el Solar panel voltage rises in cold weather Check that the solar panel open circuit voltage Voc will remain below the maximum input voltage of the GV 10 at the coldest possible expected temperature Note In the GV 10 the negative side of the battery is connected internally to the negative side of the solar panel CONNECTING THE BATTERY Connect the battery to the BATT and BATT terminals A small spar...

Страница 6: ... Overload This could be caused by changing the solar panel connections while the controller is operating SETS OF 3 RED BLINKS Battery voltage too low The controller cannot begin charging due to low battery voltage If the nominal battery voltage is correct 12V charge the battery by some other means before use SETS OF 4 RED BLINKS Battery voltage too high If the nominal battery voltage is correct 12...

Страница 7: ...32V or higher For more in depth system troubleshooting please visit the support area of our website https sunforgellc com learning center Specifications GV 10 Li V GV 10 Pb 12V Max Recommended Panel Power 140W GV 10 Li 12 5V 120W GV 10 Li 14 2V 140W GV 10 Li 16 7V 160W Max Input Voltage 34V Recommended Max Panel Voc at STC 27V Max Input Short Circuit Current 2 10 5A Max Input Current 3 19A Nominal...

Страница 8: ...cal MPPT Tracking Speed 15Hz Connection 4 position terminal block for 10 30AWG wire Weight 5 6 5 oz 185 g Dimensions 5 5 5 x 2 5 x 1 2 14 x 6 5 x 3 1 cm Environmental Protection 5 IP40 Nickel Plated Brass Stainless Hardware Certifications cETLus CE FCC RoHS Warranty 5 years GV 10 Li V GV 10 Pb 12V Copyright 2020 SunForge LLC All rights reserved Changes are periodically made to the information here...

Отзывы: