Genasun GV-10 Скачать руководство пользователя страница 5

BATTERY

PANEL

Note: 

Drip loop to protect 

charge controller from water.

     

CONNECTING THE SOLAR PANEL

Connect the solar panel to the PANEL+ and PANEL- terminals. While connecting the battery first will not 
damage the GV-10, we recommend connecting the panel first. This eliminates the risk of short-circuiting 
the panel while the GV-10 is operating, which can cause damage.
• 

In most applications, the panel should be connected only to the GV-10.  

• 

Do not use blocking diodes for single-panel installations. The GV-10 prevents reverse-current flow.

• 

Multiple panels may be connected in parallel up to the maximum power limit of the controller, with 
a blocking diode used for each panel (unless otherwise recommended by the panel manufacturer). 
These panels should be the same model and facing the same direction, otherwise we recommend 
using a separate controller for each panel.

• 

Solar panel voltage rises in cold weather.  Check that the solar panel open circuit voltage (Voc) 
will remain below the maximum input voltage of the GV-10 at the coldest possible expected 
temperature.

Note: 

In the GV-10, the negative side of the battery is connected internally to the negative side of 

the solar panel

     

CONNECTING THE BATTERY

Connect the battery to the BATT+ and BATT- terminals.
• 

A small spark while connecting the battery is ok.

• 

Any loads should be connected directly to the battery.  The GV-10 does not provide protection 
against over-discharge.

The GV-10 has a 

 

MULTI

COLOR

 

LED.

Learn about this indicator  

on the following page.

CAUTION, RISK OF FIRE OR EXPLOSION: Do not make the final battery connection near lead-acid 
batteries that have recently been charging.

FUSE

4

3

Note: 

Voltages above 25V applied to the battery terminals will immediately destroy the GV-10.  

We recommend wiring the controller directly to the battery through its own circuit, and not 
through any battery switch or selector.  Do not share wiring between the GV-10 and an alternator.

Содержание GV-10

Страница 1: ...ium Iron Phosphate GV 10 Li 16 7V 14 8V 4s Lithium Cobalt Manganese Nickel GV 10 Li CV V Custom CC CV or Multi Stage Lithium GV 10 Manual For models Solar Charge Controllers with Maximum Power Point Tracking IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS GENASUN GV 10 ALL MODELS MANUAL REVISION 5 0 2020 10 5A 140W SUNFORGE LLC 2598 FORTUNE WAY SUITE K VISTA CA 92081 USA https sunforgellc co...

Страница 2: ...ONCENTRATIONS ATTENTION RISQUE D EXPLOSION NE PAS RÉPARER CONNECTER DÉCONNECTER OU REMPLACER LES FUSIBLES À MOINS QUE LA ZONE SOIT EXEMPTE DE CONCENTRATIONS INFLAMMABLES WARNING REPLACE ONLY WITH THE SAME RATINGS AND TYPE OF FUSE DISCONNECT ALL SOURCES OF SUPPLY BEFORE SERVICING NON ISOLATED ATTENTION REMPLACER SEULEMENT AVEC LE MÊME TYPE ET VALEUR NOMINALE DE FUSIBLE DÉBRANCHER TOUTES LES SOURCES...

Страница 3: ... or voltage range Failure to do so may result in property damage injury or death Genasun highly recommends the use of a BMS with cell balancing Cell balancing is mandatory for lithium iron phosphate Use only 10 30 AWG 5 0 mm2 max copper conductors suitable for a minimum of 60 degrees C If operation at high power or at high ambient temperatures is expected wire with a higher temperature rating may ...

Страница 4: ... batteries as well as some types of AGM batteries A FLOODED setting is available for flooded batteries and other types of AGM batteries The FLOODED setting includes equalization charging Please consult the specification table at the end of this manual to determine the best setting for your battery type To change your GV 10 controller to the FLOODED setting unscrew the four screws on the bottom of ...

Страница 5: ...el Solar panel voltage rises in cold weather Check that the solar panel open circuit voltage Voc will remain below the maximum input voltage of the GV 10 at the coldest possible expected temperature Note In the GV 10 the negative side of the battery is connected internally to the negative side of the solar panel CONNECTING THE BATTERY Connect the battery to the BATT and BATT terminals A small spar...

Страница 6: ... Overload This could be caused by changing the solar panel connections while the controller is operating SETS OF 3 RED BLINKS Battery voltage too low The controller cannot begin charging due to low battery voltage If the nominal battery voltage is correct 12V charge the battery by some other means before use SETS OF 4 RED BLINKS Battery voltage too high If the nominal battery voltage is correct 12...

Страница 7: ...32V or higher For more in depth system troubleshooting please visit the support area of our website https sunforgellc com learning center Specifications GV 10 Li V GV 10 Pb 12V Max Recommended Panel Power 140W GV 10 Li 12 5V 120W GV 10 Li 14 2V 140W GV 10 Li 16 7V 160W Max Input Voltage 34V Recommended Max Panel Voc at STC 27V Max Input Short Circuit Current 2 10 5A Max Input Current 3 19A Nominal...

Страница 8: ...cal MPPT Tracking Speed 15Hz Connection 4 position terminal block for 10 30AWG wire Weight 5 6 5 oz 185 g Dimensions 5 5 5 x 2 5 x 1 2 14 x 6 5 x 3 1 cm Environmental Protection 5 IP40 Nickel Plated Brass Stainless Hardware Certifications cETLus CE FCC RoHS Warranty 5 years GV 10 Li V GV 10 Pb 12V Copyright 2020 SunForge LLC All rights reserved Changes are periodically made to the information here...

Отзывы: